| 2007-12-19 16:35:20 | ** DENIED REVISION ** |
| | |
| | |
| | 1) NOTE: PLEASE KNOW EVEN AS PLANS ARE NOW UNDER THE |
| | RESPONSIBILITY OF THE LICENSED ELECTRICAL CONTRACTOR AS |
| | PERMITTED IN FS 471 AND 489, PLEASE BE SURE PLANS |
| | CONTAIN THE SIGNATURE OF THE QUALIFIER. |
| | FBC 106.1.2, 106.5 ETC |
| | |
| | 2) NOTE: PLEASE SEE PLANS NOW HAVE RISER COMPLETELY |
| | REVISED. PLEASE CLARIFY IF THE NEW SERVICE IS A |
| | METER/MAIN COMBO. NO METER SHOWN ON RISER. |
| | PLEASE SEE PLANS ON E-2 STILL ACTUALLY SHOW A SEPARATE |
| | METER AND SEPARATE MAIN. |
| | PLEASE SEE THERE IS NO MENTION OF ANY MAINS OR OVER |
| | CURRENT PROTECTION FOR EITHER OF THE 200AMPS SUB |
| | PANELS. PLEASE PROVIDE SCHEDULE FOR *ASSUMED* |
| | METER/MAIN EQUIPMENT. |
| | 230.70, 230.71, 230.72, 240.4 AND 310.16 ETC |
| | FBC 106.3.5.4 |
| | |
| | 3) NOTE: PLEASE KNOW THE NEW SPEAKERS SHOWN ON PLANS |
| | WILL BE REQUIRED TO BE UNDER A SEPARATE PERMIT. THESE |
| | PLANS MAY BE REFERENCED FOR PERMIT ONCE REVISIONS ARE |
| | CORRECTED. |
| | ** THIS IS NOTED FOR INFORMATION. |
| | |
| | 4) NOTE: PLEASE SEE NFPA-72 11.8.3 AS THE SMOKE ALARM |
| | IN KITCHEN IS BEING SHOWN WITHIN 20FT OF COOKING |
| | APPLIANCE WHICH IS NOT PERMITTED. PLEASE KEEP IN MIND |
| | THE EXCEPTION IS THAT THE UNIT INSTALLED MUST BE A |
| | *PHOTO-ELECTRIC* RE-SETTING TYPE. |
| | ** THIS IS FOR INFORMATION WHICH WILL BE NEEDED BEFORE |
| | INSTALLATION OF UNIT AND FINAL. |
| | |
| | 5) NOTE: PLEASE SEE THE HALLWAY BETWEEN DINING ROOM AND |
| | LIVING ROOM WILL REQUIRE A MINIMUM OF ONE LIGHT FIXTURE |
| | FOR EGRESS. |
| | THIS COULD BE REDLINED AND REVISED BEFORE FINAL OR |
| | REVISED SHOWING A FIXTURE OF SOME TYPE AT THIS TIME. |
| | THIS ALSO INCLUDES FOYER AREA. |
| | 210.70, LS101 7.8 |
| | |
| | 6) NOTE: PLEASE SEE MISSING * EQUIPMENT GROUNDING |
| | CONDUCTORS* AFTER THE FIRST MEANS OF DISCONNECT FOR |
| | ALL. |
| | PLEASE SEE 250.122 FOR SIZING. |
| | 250.24, 250.110 ETC |
| | |
| | 7) NOTE: PLEASE INCLUDE AIC RATING FOR NEW SERVICE |
| | MAINS/EQUIPMENT. |
| | 110.9 |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | ** ITEMS ON SHEETS E-2 & 3 MAY BE ADJUSTED AT THIS |
| | TIME, OR MAY BE REDLINED AND REVISED BEFORE FINAL. |
| | ITEMS ON SHEET E-4 NEED TO BE CORRECTED AT THIS TIME. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |