Plan Review Notes
Plan Review Notes For Permit 06061461
Permit Number 06061461
Review Stop E
Sequence Number 5
Notes
Date Text
2007-12-19 16:35:20** DENIED REVISION **
  
  
 1) NOTE: PLEASE KNOW EVEN AS PLANS ARE NOW UNDER THE
 RESPONSIBILITY OF THE LICENSED ELECTRICAL CONTRACTOR AS
 PERMITTED IN FS 471 AND 489, PLEASE BE SURE PLANS
 CONTAIN THE SIGNATURE OF THE QUALIFIER.
 FBC 106.1.2, 106.5 ETC
  
 2) NOTE: PLEASE SEE PLANS NOW HAVE RISER COMPLETELY
 REVISED. PLEASE CLARIFY IF THE NEW SERVICE IS A
 METER/MAIN COMBO. NO METER SHOWN ON RISER.
 PLEASE SEE PLANS ON E-2 STILL ACTUALLY SHOW A SEPARATE
 METER AND SEPARATE MAIN.
 PLEASE SEE THERE IS NO MENTION OF ANY MAINS OR OVER
 CURRENT PROTECTION FOR EITHER OF THE 200AMPS SUB
 PANELS. PLEASE PROVIDE SCHEDULE FOR *ASSUMED*
 METER/MAIN EQUIPMENT.
 230.70, 230.71, 230.72, 240.4 AND 310.16 ETC
 FBC 106.3.5.4
  
 3) NOTE: PLEASE KNOW THE NEW SPEAKERS SHOWN ON PLANS
 WILL BE REQUIRED TO BE UNDER A SEPARATE PERMIT. THESE
 PLANS MAY BE REFERENCED FOR PERMIT ONCE REVISIONS ARE
 CORRECTED.
 ** THIS IS NOTED FOR INFORMATION.
  
 4) NOTE: PLEASE SEE NFPA-72 11.8.3 AS THE SMOKE ALARM
 IN KITCHEN IS BEING SHOWN WITHIN 20FT OF COOKING
 APPLIANCE WHICH IS NOT PERMITTED. PLEASE KEEP IN MIND
 THE EXCEPTION IS THAT THE UNIT INSTALLED MUST BE A
 *PHOTO-ELECTRIC* RE-SETTING TYPE.
 ** THIS IS FOR INFORMATION WHICH WILL BE NEEDED BEFORE
 INSTALLATION OF UNIT AND FINAL.
  
 5) NOTE: PLEASE SEE THE HALLWAY BETWEEN DINING ROOM AND
 LIVING ROOM WILL REQUIRE A MINIMUM OF ONE LIGHT FIXTURE
 FOR EGRESS.
 THIS COULD BE REDLINED AND REVISED BEFORE FINAL OR
 REVISED SHOWING A FIXTURE OF SOME TYPE AT THIS TIME.
 THIS ALSO INCLUDES FOYER AREA.
 210.70, LS101 7.8
  
 6) NOTE: PLEASE SEE MISSING * EQUIPMENT GROUNDING
 CONDUCTORS* AFTER THE FIRST MEANS OF DISCONNECT FOR
 ALL.
 PLEASE SEE 250.122 FOR SIZING.
 250.24, 250.110 ETC
  
 7) NOTE: PLEASE INCLUDE AIC RATING FOR NEW SERVICE
 MAINS/EQUIPMENT.
 110.9
 FBC 106.1.2, 106.3.5.4
  
 ** ITEMS ON SHEETS E-2 & 3 MAY BE ADJUSTED AT THIS
 TIME, OR MAY BE REDLINED AND REVISED BEFORE FINAL.
 ITEMS ON SHEET E-4 NEED TO BE CORRECTED AT THIS TIME.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved