2007-04-13 09:51:22** REDLINED NOTES **
  
 * LOADS ON APPLIANCE LOAD SUMMARY STILL DO NOT
 CORRELATE WITH THE LOAD CALCULATIONS, LOADS ON LOAD
 CALCULATIONS APPLY.
  
 * PANEL "B" STILL SHOWN AS 100AMP RATED AND 42CIR, THIS
 IS TO VIF.
  
  
 ** ALL REVISIONS ARE TO BE SUBMITTED BEFORE ROUGH
 ELECRTRICAL INPSECTION.