Plan Review Notes
Plan Review Notes For Permit 06061461
Permit Number 06061461
Review Stop E
Sequence Number 3
Notes
Date Text
2007-02-25 08:25:02*** UNSAT 3RD REVIEW ***
  
 ** PLEASE KNOW THIS IS THE FIRST REVIEW UNDER PERMIT
 APPLICATION.
  
 ** PLEASE SEE THAT THE PREVIOUS SUBMITTED SHEET E-2 IS
 THE SAME SHEET
  
  
 **
 1) NOTE: PLEASE SEE THAT PERMIT APPLICATION HAS ONLY
 NOW BEEN MADE AND IT IS AFTER THE NEW CODES HAVE GONE
 INTO EFFECT.
 PLEASE BE SURE ALL PLANS REFLECT THE LATEST ADOPTED
 CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISION. (THIS WILL AFFECT PLANS
 SUBMITTED).
 2005 NFPA-70 (NEC).
 2002 NFPA-72
 2003 NFPA-101
 ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE
 REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR
 REVIEWER(S).
 PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH
 REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD
 BE REVISED ACCORDINGLY.
  
 2) NOTE: PLEASE SEE 2004 FBC W/2006 FOR NOTE REQUIRED
 FOR TYPE OF RECESSED LIGHTING FIXTURES PER
 13-606.1.ABC.1.2.4
  
 3) NOTE: PLEASE SEE DUE TO THE SHEET E-2 BEING THE
 EXACT SAME SHEET SUBMITTED PREVIOUSLY WITH NO REVISIONS
 MADE, PLEASE BE SURE TO SEE ALL COMMENTS FROM PREVIOUS
 REVIEW(S) AND SEE REDLINED PLANS WHICH ARE STILL IN
 SETS FROM PREVIOUS REVIEW.
  
 4) NOTE: PLEASE SEE LOAD CALCULATIONS SHALL BE DONE AND
 CODES STATED PER 2005 NEC/ NFPA-70. PLEASE SEE ALL ARE
 REFLECTED FROM THE 2002 NEC.
  
 5) NOTE:PLEASE SEE DUE TO SOME SHEETS BEING THE SAME
 SHEETS FROM PREVIOUS REVIEW THIS COMMENT STANDS.
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 6) NOTE: PLEASE SEE PREVIOUS COMMENT WITH RESPECT TO
 THE NUMBER OF SMALL APPLIANCE CIRCUITS WHICH ARE
 REQUIRED TO BE FIGURED INTO THE LOAD CALCULATIONS PER
 210.52B1, 220.52, 210.11C1. THE ONLY SECTION WHICH WAS
 DIFFERENT ON PREVIOUS NOTES WAS 220.52 WHICH USED TO BE
 220.16. THIS IS THE SAME COMMENT MADE ON PREVIOUS
 REVIEWS. PLEASE BE SURE TO GO OVER ALL OF THESE TYPES
 OF CIRCUITS AND REVISE LOAD CALCULATIONS. (NOT ALL ARE
 INCLUDED AS SHOWN ON PLANS AND PANEL SCHEDULES).
  
 7) NOTE: PLEASE SEE PANEL *B* WHICH IS SHOWN AS 100AMPS
 AND 42 CIRCUIT. PLEASE VERIFY THIS AS 100AMPS PANELS
 ARE NOT MADE WITH 42CIRCUITS.
 PLEASE ALSO SEE PANEL *C* WHICH IS SHOWN AS 20 POLES
 AND 42 POLES?
 PLEASE CORRELATE EQUIPMENT. 110.3, 90.7.
 FBC 106.1.2 ADMIN SECTION.
  
 8) NOTE: PLEASE CLARIFY THE SECTION/DATE STATED ON
 PLANS WHICH LISTS THE LOAD CALCULATIONS PER A DATE OF
 9/25/1997? PLEASE SEE NOTES ABOVE WITH RESPECT TO THE
 CURRENT CODE OF 2005 NFPA-70.
  
 9) NOTE: PLEASE CORRELATE LOADS SHOWN FOR PANEL *C* ON
 PANEL *A* SCHEDULE WITH THAT OF THE LOAD SHOWN ON PANEL
 *C*.
 220.
 FBC 106.1.2
  
 10) NOTE: PLEASE CORRELATE ALL LOADS ON PANEL SCHEDULES
 WITH LOADS ON LOAD SUMMARY AND LOADS ON LOADS
 CALCULATIONS. PLEASE SEE THERE ARE SEVERAL WHICH DO NOT
 CORRELATE. PLEASE ALSO SEE THAT ALL LOADS ARE PERMITTED
 TO ROUND UP, BUT NOT PERMITTED TO ROUND DOWN.
 PLEASE SEE SOME LOADS ARE AS MUCH AS 800VA MORE ON
 PANEL SCHEDULE THAN IN LOAD CALCULATIONS ETC.
 PLEASE SEE 2005 NEC 220.
 FBC 106.1.2, 106.3.5.3.4
  
 11) NOTE: PLEASE SEE FS 489 PART I AS IT APPEARS PERMIT
 IS BEING APPLIED FOR AS OWNER/BUILDER YETHOMESTEAD
 AND RESISIDENCE IS ANOTHER LOCATION. PLEASE KNOW THAT
 DOCUMENTATION MAY BE REQUIREDFOR O/B IS MOVING INOT
 NEW RESIDENCE.
  
  
 ** PLEASE BE SURE TO SEE COMMENT S FROM PREVIOUS REVIEW
 AS SOME MAY STILL APPLY OR CORRELATE WITH THESE PLANS
 FOR SHEET E-2.
  
 ** PLEASE KNOW AS PLANS WERE ONLY SUBMITTED FOR **PLAN
 REVIEW** THE FIRST TWO TIMES, FS 553.80(2)(B) DOES NOT
 APPLY.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-02-25 07:53:592007-02-25 07:53:59