| 2006-10-24 12:00:01 | ****** UNSAT2ND REVIEW ******** |
| | |
| | ** PLEASE KNOW PLANS AHVE ONLY BEEN SUBMITTED FOR "PLAN |
| | REVIEW" ONLY AND EVEN IF PLANS PASS THEY CAN NOT BE |
| | STAMPED UNTIL SUCH TIME A PERMIT HAS BEEN APPLIED FOR |
| | . |
| | PLEASE SEE REVIEWS ARE BASED ON PLANS REVIEW FOR A |
| | "PROJECT" ONLY. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE THE |
| | SAME AND SEE NEW NOTE DUE TO A CHANGE AND INFORMATION |
| | FOUND IN THE CODE. |
| | PLEASE SEE NOTE BELOW ARE TAKEN DIRECTLY FROM PREVIOUS |
| | REVIEW WITH NEW NOTES ADDED. |
| | |
| | 1) NOTE:OK, HOWEVER PLEASE DO THE SAME WHEN |
| | RESUBMITTING PLANS FOR REVIEW ONCE AGAIN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE TO COMPLETELY |
| | REMOVE ANY OF THE OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT THE NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | THIS WILL HELP TO AVOID ANY DELAYS IN |
| | PROCESSING PROJECT. |
| | ** ONE COPY OF ANY OLD/VOIDED REMOVED |
| | SHEETS SHOULD BE SUBMITTED SEPARATELY |
| | FOR REFERENCE. |
| | |
| | 2) NOTE:NO, PLEASE SEE LOADS SHALL BE FIGURED FOR ONE |
| | OR MORE. PLEASE SEE TWO SM APPL CIRCUITS ARE REQUIRED |
| | FOR MIN, HOWEVER PLEASE SEE CODES GIVEN FOR OTHERS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE CIRCUITING FOR |
| | BUTLERS PANTRY IS SHOWN ALSO FEEDING |
| | OUTSIDE GFI(S). |
| | PLEASE SEE 210.52B1 WHICH SPEAKS OF |
| | KITCHEN SM APPL AND AREAS OF THE LIKE. |
| | BUTLERS PANTRY SHALL BE CIRCUITED TO ONE |
| | OR MORE OF THE SMALL APPLICANCE |
| | CIRCUITS. |
| | LOADS SHALL BE FIGURED AT 1.5KW PER CIR. |
| | PLEASE ALSO OTHER CIRCUITS IN KITCHEN |
| | WHICH AARE NOT BEING SHOWN WITH LOADS |
| | ETC AT 1.5, VA OR ON ON ONE OR MORE OF |
| | THE SM APPL CIRCUITS. |
| | PLEASE KNOW, ALL CIRCUITS ABOVE THE TWO |
| | MIN SM APPL, SHALL ALL BE FIGURED AND |
| | SHOWN AT 1.5KW FOR EACH. IE; 4-CIRCUITS, |
| | 6KW. |
| | 210.11C1,210.52B1,220.16 |
| | |
| | 3) NOTE:OK. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: OK, HOWEVER SEE NEW NOTE WITH RESPECT TO SD'S |
| | AND SA'S |
| | |
| | 7) NOTE: OK, NO ELECTRICAL SHOWN, IF THIS NEEDED, THESE |
| | ITEMS WILL BE REQUIRED TO BE REVISED AT A LATER DATE. |
| | PLEAS KNOW, MAY GAS APPLIANCES ARE REQUIRED TO HAVE AN |
| | ELECTRICAL FEED OF SOME KIND FOR ELECTRONICS ETC. THIS |
| | IS NOT ANYTHIGN THAT NEEDS TO BE CORRECTED ON PLANS. |
| | |
| | 8) NOTE: NO, PLEASE SEE LOAD CALCULATIONS STILL DO NOT |
| | INCLUDE ALL LOADS FOR DEDICATED EQUIPMENT. PLEASE SEE |
| | LOADS ON PANELS "B" AND "C" STILL DO NOT CORRELATE WITH |
| | PANEL "A". PLEASE SEE THERE ARE MANY IEMS WHICH ARE |
| | DEDICATED LAODS NOT FIGURED. |
| | PLEASE SEE NEC 220.31 AND SHOW ALL LOADS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE LOAD CALCULATIONS |
| | SHALL INCLUDE ALL LOADS ON PANEL "B" AND |
| | "C". PLEASE SEE LOADS SHOWN FOR PANEL |
| | "C" IS ONLY SHOWN AT 5.9KW, YET THE |
| | LOADS ON PANEL "C" WAY EXCEED THIS. |
| | PLEASE SHOW LOADS ON EACH PANEL, AND |
| | INDICATE INDICATE THIS BREAK DOWN FOR |
| | EACH IN LOAD CALCUALTIONS. |
| | 215.5, 220 |
| | |
| | 9) NOTE: NO, PLEASE SEE THERE ARE STILL SOME MISSING AS |
| | REQUIRED PER 210.52 |
| | |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING RECEPTS PER |
| | 210.52 MANY OF THESE ARE REDLINED ON ONE |
| | OF THE SETS OF PLANS. |
| | PLEASE SEE 3RD FLR, IF THIS AREA IS |
| | ENCLOSED, RECEPTS WILL BE REQUIRED. |
| | PLEASE ALSO SEE BUILDING COMMENTS IF 3 |
| | FLRS OF HABITABLE SPACE. |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: NO, PLEASE SEE GUEST RM, MISSING DESIGNATION |
| | ON ELECTRICAL PLANS, AND CIRCUITING FOR RECETPS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 408.4 WHERE THE |
| | PANEL SCHEDULE SHALL BE SPECIFIC FOR |
| | ROOMS AND ALL AREAS. MOST ARE DONE. |
| | IE: BEDRM #3 RECEPTS , LIV RM LTS ETC |
| | ** IT IS KNOWN, THAT DURING CONSTRUCTION |
| | THESE CIRCUITS MAY CHANGE AND CAN BE |
| | REVISED AT A LATER DATE. |
| | PLEASE SEE SOME ARE ONLY SHOWN AS GFI, |
| | ETC. WHEREAS THE SM APPL CIRCUITS ETC |
| | SHALL BE SPECIFIC. |
| | |
| | 13) NOTE: OK. |
| | |
| | 14) NOTE: OK. |
| | |
| | 15) NOTE:NO, PLEASE SEE NOT ALL CIRCUITS WHICH |
| | REQUIRE AFCI PROTECTION ARE SHOWN THIS WAY. PLEASE SEE |
| | A-31AND VERIFY ALL OTHERS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE ARC FAULT |
| | PROTECTION IS REQUIRED FOR ALL CIRCUITS |
| | IN BEDRMS , NOT ONLY RECEPTS. THIS |
| | REQUIREMRNT WAS CHANGED FROM THE 1999 |
| | NEC. THE 2002 NEC 210.12B REQUIRES ALL |
| | "OUTLETS" TO BE PROTECTED ON THAT BRANCH |
| | CIRCUIT. THIS INCLUDES, LTS, RECEPTS, |
| | SD'S, FANS ETC. |
| | |
| | 16)NOTE: OK, HOWEVER WITH THE AIC RATING BEING SHOWN |
| | AT 10K, PLEASE KNOW IF THE LOCATION CONTAINS AN OLDER |
| | TRANSFORMER, IT IS KNOWN TO THIS OFFICE THAT MANY OF |
| | THE OLDER TRANSFORMER ARE BEING CHNAGED OUT AND SOME |
| | CONSIDERATION FOR FUTURE KVA SIZE SHOULD BE GIVE. THIS |
| | IS ONLY NOTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 17) NOTE: OK. |
| | |
| | 18) NOTE:NO, PLEASE SEE MISSING REQUIRED FOOTER |
| | STEEL. SHOWS OTHERS, HOWEVER THE FOOTER STEEL IS |
| | REQUIRED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 250.50 FOR MIN |
| | GROUNDING ELECTRODE SYSTEM AT MAIN |
| | HOUSE. NEW FOOTER STEEL, CWP, GRND ROD |
| | WILL BE REQUIRED. |
| | |
| | 19) NOTE:OK. |
| | |
| | 20) NOTE:NO, AS NOTED ABOVE. PLEASE SEE SOME AREAS |
| | ARE MISSING SOME CIRCUITING. SEE REDLINED (GUEST RM). |
| | AND OTHER POSSIBLE LOCATIONS. |
| | NOT ALL AREAS AS REDLINED |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE SOME ITEMS/RECEPTS |
| | ARE MISSING CIRCUITING ON PLANS. THESE |
| | ARE MINOR AND HAVE BEEN REDLINED, ALONG |
| | WITH SD'S. |
| | FBC ADMIN SECT 106.1.2 |
| | |
| | 21) NOTE:NO, PLEASE SEE NOTE #2 ABOVE. PLEASE SEE |
| | LOADS, ECT REQUIRED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE DINING RM |
| | RECEPTS SHALL BE EITHER ON ONE OR MORE |
| | OF THE REQUIRED DEDICATED SMA PPL |
| | CIRCUITS OR ON THEIR OWN. 210.11C1,220.16,210.52B1 |
| | |
| | 22) NOTE: OK. |
| | |
| | 23) NOTE: OK. |
| | |
| | 24) NOTE: OK, HOWEVER PLEASE SEE BOTH GDO'S (GARAGE |
| | DOOR OPENERS) ARE BEING SHOWN ON ONE CIRCUIT WITH A |
| | LOAD OF 900A FOR BOTH. PLEASE VERIFY THIS AS THE |
| | TYPICAL SIZE OF A GDO IS LARGE ENOUGH WHERE EACH |
| | REQUIRES A DEDICATED CIRCUIT. PLEASE SEE 430.148 AND |
| | VERIFY AS THIS WOULD BE THE TIME TO REVISE IF NEEDED. |
| | PLEASE ALSO REVISED CALCULATIONS IF NEEDED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY GDO AS THESE |
| | LOCATIONS ARE SHOWING "J" BOXES AND NOT |
| | RECEPTS. PLEASE KNOW, IF THE GDO'S ARE |
| | PLUG-IN TYPE, THEN RECEPTS SHOULD BE |
| | SHOWN. |
| | 106.1.2 |
| | |
| | *** NEW NOTE *** |
| | |
| | 25) NOTE: PLEASE SEE NFPA-72 2002 DEFINITIONS OF SMOKE |
| | DETECTORS AND SMOKE ALARMS. PLEASE ADJUST SYMBOL |
| | DESIGNATIONS ON PLANS IF THESE ARE INDEED NOT ONLY |
| | DETECTION DEVICES ARE NOTPART OF A FA SYSTEM/SECURITY |
| | SYSTEM. IF THESE ARE DEVICES WHICH DETECT AND SOUND |
| | THESE ARE CONSIDERED SA'S SMOKE ALARMS. PLEASE KNOW THE |
| | CLARIFICATION FROM NFPA AND THE CODE PANELIST WAS GIVEN |
| | RECENTLY SINCE THE LAST REVIEW. |
| | PLEASE ADJUST PLANS. |
| | |
| | |
| | ** PLEASE KNOW,MANY OF THE ABOVE ITEMS |
| | ARE REDLINED ON ONE OF THE SETS OF |
| | PLANS, HOWEVER IS IN NO WAY ALL |
| | LOCATIONS AS NOTED ABOVE. |
| | |
| | ** PLEASE SUBMIT THE ABOVE FOR REVIEW |
| | AND IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2006-10-24 10:42:39 | RECEIVED FROM"INCOMING" ON 10/24/06, PLANS WERE NOT |
| | ROUTED ON 10/6 TO ELECTRICAL. |