Plan Review Notes
Plan Review Notes For Permit 06061461
Permit Number 06061461
Review Stop M
Sequence Number 1
Notes
Date Text
2006-06-30 00:00:00FOR PLAN REVIEW ONLY NOT FOR PERMIT.
 *** DENIED ***
 1) PLEASE SUBMIT A COMPLETE MANUAL J
 CALCULATION SHOWING EACH ZONE, PER 2004
 FBC 13-607.1.ABC.1 .
  
 2) SHOW A/C SYSTEMS TOTAL, AND SENSIBLE
 BTU'S ON MECHANICAL PLANS EQUIPMENT
 LISTING.
  
 3) PLEASE SUBMIT DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR GAS FIREPLACE & HEATER,
 AND GAS BBQ GRILL & HOOD.
  
 4) GUEST BEDROOM SHOWS A 10X10 SUPPLY
 AIR DUCT WITCH MAKES THE 10" RETURN AIR
 TRANSFER DUCT TO SMALL, PLEASE CORRECT.
  
 5) 12" RETURN AIR TRANSFER DUCT IN
 MASTER BEDROOM SUITE NEEDS TO BE 14",
 PLEASE SEE 2004 FBC/R M1602.4 .
  
 6) AHU #2 14X12 RETURN AIR DUCT NEEDS TO
 BE 26X12, AS IT IS ACTING AS A TRANSFER
 DUCT, SEE 2004 FBC/R M1602.4 .
  
 7) AHU #2 10X10 RETURN AIR DUCT NEEDS TO
 BE 16X10 FOR SAME REASON AS NOTE #6.
  
 8) PLEASE SEE ELECTRICAL REWIEW NOTES
 #3, 4, AND 23.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.