| Plan Review Notes For Permit 06061461 |
| Permit Number |
06061461 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-30 00:00:00 | FOR PLAN REVIEW ONLY NOT FOR PERMIT. | | | *** DENIED *** | | | 1) PLEASE SUBMIT A COMPLETE MANUAL J | | | CALCULATION SHOWING EACH ZONE, PER 2004 | | | FBC 13-607.1.ABC.1 . | | | | | | 2) SHOW A/C SYSTEMS TOTAL, AND SENSIBLE | | | BTU'S ON MECHANICAL PLANS EQUIPMENT | | | LISTING. | | | | | | 3) PLEASE SUBMIT DETAILED MANUFACTURE'S | | | SPECIFICATION'S AND INSTALLATION | | | INSTRUCTIONS FOR GAS FIREPLACE & HEATER, | | | AND GAS BBQ GRILL & HOOD. | | | | | | 4) GUEST BEDROOM SHOWS A 10X10 SUPPLY | | | AIR DUCT WITCH MAKES THE 10" RETURN AIR | | | TRANSFER DUCT TO SMALL, PLEASE CORRECT. | | | | | | 5) 12" RETURN AIR TRANSFER DUCT IN | | | MASTER BEDROOM SUITE NEEDS TO BE 14", | | | PLEASE SEE 2004 FBC/R M1602.4 . | | | | | | 6) AHU #2 14X12 RETURN AIR DUCT NEEDS TO | | | BE 26X12, AS IT IS ACTING AS A TRANSFER | | | DUCT, SEE 2004 FBC/R M1602.4 . | | | | | | 7) AHU #2 10X10 RETURN AIR DUCT NEEDS TO | | | BE 16X10 FOR SAME REASON AS NOTE #6. | | | | | | 8) PLEASE SEE ELECTRICAL REWIEW NOTES | | | #3, 4, AND 23. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|