| 2006-06-30 00:00:00 | ****** UNSAT ******** |
| | |
| | 1) NOTE: PLEASE BE SURE TO COMPLETELY |
| | REMOVED ANY OF THE OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT THE NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | THIS WILL HELP TO AVOID ANY DELAYS IN |
| | PROCESSING PROJECT. |
| | ** ONE COPY OF ANY OLD/VOIDED REMOVED |
| | SHEETS SHOULD BE SUBMITTED SEPARATELY |
| | FOR REFERENCE. |
| | |
| | 2) NOTE: PLEASE SEE CIRCUITING FOR |
| | BUTLERS PANTRY IS SHOWN ALSO FEEDING |
| | OUTSIDE GFI(S). |
| | PLEASE SEE 210.52B1 WHICH SPEAKS OF |
| | KITCHEN SM APPL AND AREAS OF THE LIKE. |
| | BUTLERS PANTRY SHALL BE CIRCUITED TO ONE |
| | OR MORE OF THE SMALL APPLICANCE |
| | CIRCUITS. |
| | LOADS SHALL BE FIGURED AT 1.5KW PER CIR. |
| | PLEASE ALSO OTHER CIRCUITS IN KITCHEN |
| | WHICH AARE NOT BEING SHOWN WITH LOADS |
| | ETC AT 1.5, VA OR ON ON ONE OR MORE OF |
| | THE SM APPL CIRCUITS. |
| | PLEASE KNOW, ALL CIRCUITS ABOVE THE TWO |
| | MIN SM APPL, SHALL ALL BE FIGURED AND |
| | SHOWN AT 1.5KW FOR EACH. IE; 4-CIRCUITS, |
| | 6KW. |
| | 210.11C1,210.52B1,220.16 |
| | |
| | 3) NOTE: PLEASE SEE PLANS SHALL |
| | REFERENCE THE CURRENT CODES IN EFFECT. |
| | PLEASE SEE PLANS NOW INDICATE THE |
| | "LATEST CODES". WE ARE NOT CURRENTLY |
| | UNDER THE LATEST CODES AS THEY HAVE NOT |
| | YET BEEN ADOPTED BY THE STATE OF |
| | FLORIDA. |
| | PLEASE SEE THE FOLLOWING AT A MIN SHOULD |
| | BEON PLANS. 2002 NFPA-70, 2003 NFPA-101, |
| | 2002 NFPA-72. |
| | |
| | 4) NOTE: PLEASE SEE MORE THAN ONE |
| | ENGINEERING TITLE BLOCK IS BEING SHOWN |
| | ON PLANS.??? |
| | PLEASE KNOW, ONE SHALL BE THE |
| | RESPONSIBLE FIRM. ANY OTHER CONSULTING |
| | FIRMS ETC SHALL ALL INDICATE THEIR |
| | REQUIRED INFORMATION ON SAID TITLE |
| | BLOCKS. FAC 61G15-23.002, FAC |
| | 61G1-16.004, FS 471.023, FS 481.219 |
| | |
| | 5) NOTE: PLEASE SEE MISSING EGRESS |
| | LIGHTING CONTROLS IN MANY LOCATIONS. |
| | PLEASE SEE ALL RMS IN HOUSE WHICH |
| | INDICATE A SW FOR A FAN AND A |
| | FAN J-BOX ONLY?? |
| | PLEASE KNOW, A LT FIXTURE WILL BE |
| | REQUIRED OR 1/2 SWITCHED RECEPT. |
| | PLEASE SEE OTHER LOCATIONS IN MAIN HOUSE |
| | FOR LOCATIONS OF MEANS OF EGRESS AND |
| | WHERE A LT FIXTURE OF SOME SORT WILL BE |
| | REQUIRED. PLEASE SEE RMS( BEDRM #1) |
| | WHERE ALL THE RECEPTS ARE SHOWN BEING |
| | SWITCHED? (AS SHOWN) IF THIS IS INDEED |
| | THE CASE, THEN PLEASE ALSO PROVIDE |
| | RECEPTS WHICH ARE NOT SWITCHED OR 1/2 |
| | SWITCHED TO MEET 210.52 |
| | (THIS APPEARS TO BE A MISPRINT). |
| | PLEASE SEE EGRESS TO UPPER TOWER FLR |
| | DOES NOT INDICATE A "S"3/ LEADING TO THE |
| | FLR ABOVE AND UPPER TOWER ONLY SHOWS A |
| | "S" FOR LT. |
| | |
| | 6) NOTE: PLEASE SEE SD'S ARE NOTALL |
| | SHOWN WITH CIRCUITING? PLEASE SEE SD'S |
| | ARE BEING SHOWN CIRCUITED TO MORE THAN |
| | ONE CIRCUIT ON PANELS. |
| | PLEASE KNOW, THE SD'S IN DWELLING CAN |
| | BE CIRCUITED TO ONE OF THE ARC FAULT |
| | PROTECTED BEDRM LIGHTING/RECEPT |
| | CIRCUITS. THIS WILL ALLEAVIATE THE |
| | TURNING OFF OF THIS CIRCUIT AND LEAVING |
| | THE ENTIRE DWELLING WITH OUT SD |
| | PROTECTION. ( THIS WOULD ALSO ALLEAVIATE |
| | THE ADDITIONAL AFCI BRKR) |
| | 215.5 NFPA-72 11.8.3 |
| | ** PLEASE SEE 11.8.3 AS STATED ABOVE, |
| | MISSING SD WHICH IS REQUIRED INSIDE ALL |
| | SLEEPING ROOMS. PLEASE KNOW SD IN BEDRM |
| | #1 SHALL BE "IN" THE BEDRM AREA. PLEASE |
| | KNOW, SD'S SHALL BE INSTALLED WITH IN 3' |
| | OF THE PEAK ON A SLOPED CEILING. |
| | PLEASE SEE IF UPPER TOWER/FLR IS CLOSED |
| | IN, THEN A SD AT THAT LEVEL WILL BE |
| | REQUIRED. |
| | PLEASE SEE NO DOORS ARE SHOWN LEADING TO |
| | THE FLR BELOW AND IT SEEMS THAT THIS |
| | SPACE IS ENCLOSED. |
| | |
| | 7) NOTE: PLEASE SEE IT IS KNOWN THAT THE |
| | RANGE, WH ETC MAY BE GAS , HOWEVER NO |
| | ELECTRICAL IS BEING SHOWN TO THESE UNITS |
| | FOR IGNITER'S, ETC.?? |
| | |
| | 8) NOTE:PLEASE SEE LOAD CALCULATIONS |
| | SHALL INCLUDE ALL LOADS ON PANEL "B" AND |
| | "C". PLEASE SEE LOADS SHOWN FOR PANEL |
| | "C" IS ONLY SHOWN AT 5.9KW, YET THE |
| | LOADS ON PANEL "C" WAY EXCEED THIS. |
| | PLEASE SHOW LOADS ON EACH PANEL, AND |
| | INDICATE INDICATE THIS BREAK DOWN FOR |
| | EACH IN LOAD CALCUALTIONS. |
| | 215.5, 220 |
| | |
| | 9) NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 MANY OF THESE ARE REDLINED ON ONE |
| | OF THE SETS OF PLANS. |
| | PLEASE SEE 3RD FLR, IF THIS AREA IS |
| | INCLOSED, RECEPTS WILL BE REQUIRED. |
| | PLEASE ALSO SEE BUILDING COMMENTS IF 3 |
| | FLRS OF HABITABLE SPACE. |
| | |
| | 10) NOTE: PLEASE SEE SOME CIRCUITS ARE |
| | NOTED SHOWING GFI RECEPTS AND ALSO GFI |
| | BREAKERS IN PANELS?? |
| | THIS IS OK, HOWEVER IF SHOWN THIS WAY, |
| | THEN THIS WILL BE REQUIRED. |
| | **THIS IS ONLY A NOTE; |
| | |
| | 11) NOTE: PLEASE CORRELATE FEEDER TO |
| | PANEL "C" WITH PANEL "A" SCHEDULE. 310.16,240.4,215.5 |
| | |
| | 12) NOTE: PLEASE SEE 408.4 WHERE THE |
| | PANEL SCHEDULE SHALL BE SPECIFIC FOR |
| | ROOMS AND ALL AREAS. MOST ARE DONE. |
| | IE: BEDRM #3 RECEPTS , LIV RM LTS ETC |
| | ** IT IS KNOWN, THAT DURING CONSTRUCTION |
| | THESE CIRCUITS MAY CHANGE AND CAN BE |
| | REVISED AT A LATER DATE. |
| | PLEASE SEE SOME ARE ONLY SHOWN AS GFI, |
| | ETC. WHEREAS THE SM APPL CIRCUITS ETC |
| | SHALL BE SPECIFIC. |
| | |
| | 13) NOTE: PLEASE INDICATE TH GFI |
| | PROTECTION FOR THE JACUZZI TUB. |
| | 210.8,680.71 |
| | |
| | 14) NOTE: PLEASE INDICATE TH RM WHERE |
| | THE AHU #2 AS MECH/ELEC RM. NO STORAGE |
| | PERMITTED. |
| | 110.26,408.7,240.24 |
| | |
| | 15) NOTE: PLEASE SEE ARC FAULT |
| | PROTECTION IS REQUIRED FOR ALL CIRCUITS |
| | IN BEDRMS , NOT ONLY RECEPTS. THIS |
| | REQUIREMRNT WAS CHANGED FROM THE 1999 |
| | NEC. THE 2002 NEC 210.12B REQUIRES ALL |
| | "OUTLETS" TO BE PROTECTED ON THAT BRANCH |
| | CIRCUIT. THIS INCLUDES, LTS, RECEPTS, |
| | SD'S, FANS ETC. |
| | |
| | 16)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 17) NOTE: PLEASE SEE RISER IS SHOWING |
| | "EQUIPMENT GROUNDING CONDUCTORS" FROM |
| | METER TO MAINS. PLEASE SEE THE EQP GRNDS |
| | ARE ONLY INSTALLED AFTER THE FIRST MEANS |
| | OF DISCONNECT. |
| | 250.6,250.24B |
| | |
| | 18) NOTE: PLEASE SEE 250.50 FOR MIN |
| | GROUNDING ELECTRODE SYSTEM AT MAIN |
| | HOUSE. NEW FOOTER STEEL, CWP, GRND ROD |
| | WILL BE REQUIRED. |
| | |
| | 19) NOTE: PLEASE SEE NO HAND DRAWN |
| | CHANGES AREPERMITTED ON PLANS WHICH |
| | ARE SIGNED, DATED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER. |
| | FS 481.221, 471.025 |
| | PLEASE KNOW, "IF" SOME VERY MINOR ITEMS |
| | ARE ADDED, THEN EACH ITEM MAY BE DONE |
| | WITH THE DESIGN PROFESSIONAL OF RECORD |
| | SIGNING AND DATING EACH ITEM. |
| | |
| | 20) NOTE: PLEASE SEE SOME ITEMS/RECEPTS |
| | ARE MISSING CIRCUITING ON PLANS. THESE |
| | ARE MINOR AND HAVE BEEN REDLINED, ALONG |
| | WITH SD'S. |
| | FBC ADMIN SECT 106.1.2 |
| | |
| | 21) NOTE: PLEASE SEE THE DINING RM |
| | RECEPTS SHALL BE EITHER ON ONE OR MORE |
| | OF THE REQUIRED DEDICATED SMA PPL |
| | CIRCUITS OR ON THEIR OWN. 210.11C1,220.16,210.52B1 |
| | |
| | 22) NOTE: PLEASE GO THROUGH ALL SWITCHES |
| | ON PLANS AS SOME ARE SHOWN AS SINGLE |
| | POLE SWITCHES, YET THEY SHOULD BEBUT |
| | NOT GOING TO ANYTHING, OTHERS SHOULD BE |
| | 3-WAY, BUT NOT CLEAR? SEE NOTE ABOVE. |
| | |
| | 23) NOTE: PLEASE CORRLELATE ALL A/C |
| | SYSTEMS, OCP AND LOADS, AS THESE SHOWN |
| | ON ELECTRICAL PANEL SCHEDULE DO NOT |
| | MATCH WITH THOSE AS SHOWN ON MECH |
| | SHEETS. |
| | |
| | 24) NOTE: PLEASE CLARIFY GDO AS THESE |
| | LOCATIONS ARE SHOWING "J" BOXES AND NOT |
| | RECEPTS. PLEASE KNOW, IF THE GDO'S ARE |
| | PLUG-IN TYPE, THEN RECEPTS SHOULD BE |
| | SHOWN. |
| | 106.1.2 |
| | |
| | ** PLEASE KNOW,MANY OF THE ABOVE ITEMS |
| | ARE REDLINED ON ONE OF THE SETS OF |
| | PLANS, HOWEVER IS IN NO WAY ALL |
| | LOCATIONS AS NOTED ABOVE. |
| | |
| | ** PLEASE SUBMIT THE ABOVE FOR REVIEW |
| | AND IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |