Plan Review Notes
Plan Review Notes For Permit 06061461
Permit Number 06061461
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-30 00:00:00****** UNSAT ********
  
 1) NOTE: PLEASE BE SURE TO COMPLETELY
 REMOVED ANY OF THE OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT THE NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 THIS WILL HELP TO AVOID ANY DELAYS IN
 PROCESSING PROJECT.
 ** ONE COPY OF ANY OLD/VOIDED REMOVED
 SHEETS SHOULD BE SUBMITTED SEPARATELY
 FOR REFERENCE.
  
 2) NOTE: PLEASE SEE CIRCUITING FOR
 BUTLERS PANTRY IS SHOWN ALSO FEEDING
 OUTSIDE GFI(S).
 PLEASE SEE 210.52B1 WHICH SPEAKS OF
 KITCHEN SM APPL AND AREAS OF THE LIKE.
 BUTLERS PANTRY SHALL BE CIRCUITED TO ONE
 OR MORE OF THE SMALL APPLICANCE
 CIRCUITS.
 LOADS SHALL BE FIGURED AT 1.5KW PER CIR.
 PLEASE ALSO OTHER CIRCUITS IN KITCHEN
 WHICH AARE NOT BEING SHOWN WITH LOADS
 ETC AT 1.5, VA OR ON ON ONE OR MORE OF
 THE SM APPL CIRCUITS.
 PLEASE KNOW, ALL CIRCUITS ABOVE THE TWO
 MIN SM APPL, SHALL ALL BE FIGURED AND
 SHOWN AT 1.5KW FOR EACH. IE; 4-CIRCUITS,
 6KW.
 210.11C1,210.52B1,220.16
  
 3) NOTE: PLEASE SEE PLANS SHALL
 REFERENCE THE CURRENT CODES IN EFFECT.
 PLEASE SEE PLANS NOW INDICATE THE
 "LATEST CODES". WE ARE NOT CURRENTLY
 UNDER THE LATEST CODES AS THEY HAVE NOT
 YET BEEN ADOPTED BY THE STATE OF
 FLORIDA.
 PLEASE SEE THE FOLLOWING AT A MIN SHOULD
 BEON PLANS. 2002 NFPA-70, 2003 NFPA-101,
 2002 NFPA-72.
  
 4) NOTE: PLEASE SEE MORE THAN ONE
 ENGINEERING TITLE BLOCK IS BEING SHOWN
 ON PLANS.???
 PLEASE KNOW, ONE SHALL BE THE
 RESPONSIBLE FIRM. ANY OTHER CONSULTING
 FIRMS ETC SHALL ALL INDICATE THEIR
 REQUIRED INFORMATION ON SAID TITLE
 BLOCKS. FAC 61G15-23.002, FAC
 61G1-16.004, FS 471.023, FS 481.219
  
 5) NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING CONTROLS IN MANY LOCATIONS.
 PLEASE SEE ALL RMS IN HOUSE WHICH
 INDICATE A SW FOR A FAN AND A
 FAN J-BOX ONLY??
 PLEASE KNOW, A LT FIXTURE WILL BE
 REQUIRED OR 1/2 SWITCHED RECEPT.
 PLEASE SEE OTHER LOCATIONS IN MAIN HOUSE
 FOR LOCATIONS OF MEANS OF EGRESS AND
 WHERE A LT FIXTURE OF SOME SORT WILL BE
 REQUIRED. PLEASE SEE RMS( BEDRM #1)
 WHERE ALL THE RECEPTS ARE SHOWN BEING
 SWITCHED? (AS SHOWN) IF THIS IS INDEED
 THE CASE, THEN PLEASE ALSO PROVIDE
 RECEPTS WHICH ARE NOT SWITCHED OR 1/2
 SWITCHED TO MEET 210.52
 (THIS APPEARS TO BE A MISPRINT).
 PLEASE SEE EGRESS TO UPPER TOWER FLR
 DOES NOT INDICATE A "S"3/ LEADING TO THE
 FLR ABOVE AND UPPER TOWER ONLY SHOWS A
 "S" FOR LT.
  
 6) NOTE: PLEASE SEE SD'S ARE NOTALL
 SHOWN WITH CIRCUITING? PLEASE SEE SD'S
 ARE BEING SHOWN CIRCUITED TO MORE THAN
 ONE CIRCUIT ON PANELS.
 PLEASE KNOW, THE SD'S IN DWELLING CAN
 BE CIRCUITED TO ONE OF THE ARC FAULT
 PROTECTED BEDRM LIGHTING/RECEPT
 CIRCUITS. THIS WILL ALLEAVIATE THE
 TURNING OFF OF THIS CIRCUIT AND LEAVING
 THE ENTIRE DWELLING WITH OUT SD
 PROTECTION. ( THIS WOULD ALSO ALLEAVIATE
 THE ADDITIONAL AFCI BRKR)
 215.5 NFPA-72 11.8.3
 ** PLEASE SEE 11.8.3 AS STATED ABOVE,
 MISSING SD WHICH IS REQUIRED INSIDE ALL
 SLEEPING ROOMS. PLEASE KNOW SD IN BEDRM
 #1 SHALL BE "IN" THE BEDRM AREA. PLEASE
 KNOW, SD'S SHALL BE INSTALLED WITH IN 3'
 OF THE PEAK ON A SLOPED CEILING.
 PLEASE SEE IF UPPER TOWER/FLR IS CLOSED
 IN, THEN A SD AT THAT LEVEL WILL BE
 REQUIRED.
 PLEASE SEE NO DOORS ARE SHOWN LEADING TO
 THE FLR BELOW AND IT SEEMS THAT THIS
 SPACE IS ENCLOSED.
  
 7) NOTE: PLEASE SEE IT IS KNOWN THAT THE
 RANGE, WH ETC MAY BE GAS , HOWEVER NO
 ELECTRICAL IS BEING SHOWN TO THESE UNITS
 FOR IGNITER'S, ETC.??
  
 8) NOTE:PLEASE SEE LOAD CALCULATIONS
 SHALL INCLUDE ALL LOADS ON PANEL "B" AND
 "C". PLEASE SEE LOADS SHOWN FOR PANEL
 "C" IS ONLY SHOWN AT 5.9KW, YET THE
 LOADS ON PANEL "C" WAY EXCEED THIS.
 PLEASE SHOW LOADS ON EACH PANEL, AND
 INDICATE INDICATE THIS BREAK DOWN FOR
 EACH IN LOAD CALCUALTIONS.
 215.5, 220
  
 9) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52 MANY OF THESE ARE REDLINED ON ONE
 OF THE SETS OF PLANS.
 PLEASE SEE 3RD FLR, IF THIS AREA IS
 INCLOSED, RECEPTS WILL BE REQUIRED.
 PLEASE ALSO SEE BUILDING COMMENTS IF 3
 FLRS OF HABITABLE SPACE.
  
 10) NOTE: PLEASE SEE SOME CIRCUITS ARE
 NOTED SHOWING GFI RECEPTS AND ALSO GFI
 BREAKERS IN PANELS??
 THIS IS OK, HOWEVER IF SHOWN THIS WAY,
 THEN THIS WILL BE REQUIRED.
 **THIS IS ONLY A NOTE;
  
 11) NOTE: PLEASE CORRELATE FEEDER TO
 PANEL "C" WITH PANEL "A" SCHEDULE. 310.16,240.4,215.5
  
 12) NOTE: PLEASE SEE 408.4 WHERE THE
 PANEL SCHEDULE SHALL BE SPECIFIC FOR
 ROOMS AND ALL AREAS. MOST ARE DONE.
 IE: BEDRM #3 RECEPTS , LIV RM LTS ETC
 ** IT IS KNOWN, THAT DURING CONSTRUCTION
 THESE CIRCUITS MAY CHANGE AND CAN BE
 REVISED AT A LATER DATE.
 PLEASE SEE SOME ARE ONLY SHOWN AS GFI,
 ETC. WHEREAS THE SM APPL CIRCUITS ETC
 SHALL BE SPECIFIC.
  
 13) NOTE: PLEASE INDICATE TH GFI
 PROTECTION FOR THE JACUZZI TUB.
 210.8,680.71
  
 14) NOTE: PLEASE INDICATE TH RM WHERE
 THE AHU #2 AS MECH/ELEC RM. NO STORAGE
 PERMITTED.
 110.26,408.7,240.24
  
 15) NOTE: PLEASE SEE ARC FAULT
 PROTECTION IS REQUIRED FOR ALL CIRCUITS
 IN BEDRMS , NOT ONLY RECEPTS. THIS
 REQUIREMRNT WAS CHANGED FROM THE 1999
 NEC. THE 2002 NEC 210.12B REQUIRES ALL
 "OUTLETS" TO BE PROTECTED ON THAT BRANCH
 CIRCUIT. THIS INCLUDES, LTS, RECEPTS,
 SD'S, FANS ETC.
  
 16)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 17) NOTE: PLEASE SEE RISER IS SHOWING
 "EQUIPMENT GROUNDING CONDUCTORS" FROM
 METER TO MAINS. PLEASE SEE THE EQP GRNDS
 ARE ONLY INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
 250.6,250.24B
  
 18) NOTE: PLEASE SEE 250.50 FOR MIN
 GROUNDING ELECTRODE SYSTEM AT MAIN
 HOUSE. NEW FOOTER STEEL, CWP, GRND ROD
 WILL BE REQUIRED.
  
 19) NOTE: PLEASE SEE NO HAND DRAWN
 CHANGES AREPERMITTED ON PLANS WHICH
 ARE SIGNED, DATED AND SEALED BY THE
 ARCHITECT OR ENGINEER.
 FS 481.221, 471.025
 PLEASE KNOW, "IF" SOME VERY MINOR ITEMS
 ARE ADDED, THEN EACH ITEM MAY BE DONE
 WITH THE DESIGN PROFESSIONAL OF RECORD
 SIGNING AND DATING EACH ITEM.
  
 20) NOTE: PLEASE SEE SOME ITEMS/RECEPTS
 ARE MISSING CIRCUITING ON PLANS. THESE
 ARE MINOR AND HAVE BEEN REDLINED, ALONG
 WITH SD'S.
 FBC ADMIN SECT 106.1.2
  
 21) NOTE: PLEASE SEE THE DINING RM
 RECEPTS SHALL BE EITHER ON ONE OR MORE
 OF THE REQUIRED DEDICATED SMA PPL
 CIRCUITS OR ON THEIR OWN. 210.11C1,220.16,210.52B1
  
 22) NOTE: PLEASE GO THROUGH ALL SWITCHES
 ON PLANS AS SOME ARE SHOWN AS SINGLE
 POLE SWITCHES, YET THEY SHOULD BEBUT
 NOT GOING TO ANYTHING, OTHERS SHOULD BE
 3-WAY, BUT NOT CLEAR? SEE NOTE ABOVE.
  
 23) NOTE: PLEASE CORRLELATE ALL A/C
 SYSTEMS, OCP AND LOADS, AS THESE SHOWN
 ON ELECTRICAL PANEL SCHEDULE DO NOT
 MATCH WITH THOSE AS SHOWN ON MECH
 SHEETS.
  
 24) NOTE: PLEASE CLARIFY GDO AS THESE
 LOCATIONS ARE SHOWING "J" BOXES AND NOT
 RECEPTS. PLEASE KNOW, IF THE GDO'S ARE
 PLUG-IN TYPE, THEN RECEPTS SHOULD BE
 SHOWN.
 106.1.2
  
 ** PLEASE KNOW,MANY OF THE ABOVE ITEMS
 ARE REDLINED ON ONE OF THE SETS OF
 PLANS, HOWEVER IS IN NO WAY ALL
 LOCATIONS AS NOTED ABOVE.
  
 ** PLEASE SUBMIT THE ABOVE FOR REVIEW
 AND IF THERE ARE ANY QUESTIONS OR
 COMMENTS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  