Plan Review Notes
Plan Review Notes For Permit 06061453
Permit Number 06061453
Review Stop Z
Sequence Number 1
Notes
Date Text
2006-07-31 00:00:00PLANNING AND ZONING DEPARTMENT:FAILED
  
 1. PROVIDE RESPONSES IN WRITING.
  
 2. A MINOR AMENDMENT TO THE IBIS PLANNED
 DEVELOPMENT, MASTER PLAN IS REQUIRED. AN
 APPLICATION WILL NEED TO BE FILED TO THE
 PLANNING AND ZONING DEPARTMENT AND
 APPROVED PRIOR TO SIGN-OFF OF BUILDING
 PERMIT.THE COMMENTS BELOW REFLECT THE
 INFORMATION NEEDED ON SITE PLAN, PRIOR
 TO SUBMITTAL OF THE MINOR AMENDMENT TO
 THE IBIS RESIDENTIAL PLANNED
 DEVELOPMENT.
  
 3. PROVIDE A BETTER DETAIL OF THE AREA
 WHERE THE GENERATOR IS PROPOSED, NOT AN
 ENLARGEMENT.THE SITE PLAN SHALL
 INCLUDE THE FOLLOWING:
  
 A. SCREENING AND ELEVATION OF
 WALL/HEDGES AROUND GENERATOR/ FUEL TANK,
 AND SETBACK DISTANCE FROM PROPERTY
 LINE.
  
 4.PURSUANT TO SECTION 94-444(B) OPEN
 SPACE STANDARDS:
 (B) FUEL OR OIL OR PROPANE
 TANKS, GENERATORS SHALL NOT BE PERMITTED
 UNLESS APPROPRIATE SCREENING IS
 PROVIDED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL.
  
 WALLS SHALL BE LANDSCAPED WITH SHRUBS
 AND HEDGES PLANTED AT TWO-FOOT
 INTERVALS.A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD
 AND STEEL, AN OBSCURING GATE IS REQUIRED
 AS A CONDITION FOR SITE PLAN APPROVAL.
  
 THE SCREENING SHALL ENCLOSE BOTH FUEL
 TANK INCLUDING ROOFTOP EXHAUST (TANK, IF
 APPLICABLE AND GENERATOR.
  
 5.PURSUANT TO SECTION 94-305(B)(4)
 SETBACKS
 (B)(4) SETBACK ENCROACHMENT:
 MECHANICAL EQUIPMENT SHALL NOT PROJECT
 MORE THAN 4 FEET INTO A SETBACK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT ME AT THE NUMBER BELOW.
  