Plan Review Notes
Plan Review Notes For Permit 06061453
Permit Number 06061453
Review Stop G
Sequence Number 1
Notes
Date Text
2006-08-08 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. SEPARATE GAS PERMIT REQUIRED AND
 SHALL BE SUBMITTED WITH GENERATOR
 APPLICATION.
  
 B. THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - IF ADDING TO AN
 EXISTING SYSTEM, PLEASE INDICATE ALL
 PIPE SIZES AND SHOW REQUIREMENTS FROM
 REQUIREMENTS 2, 4, & 5 BELOW.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. NOT USED
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (THIS
 INCLUDES EXISTING SYSTEM IF APPLICABLE).
  
 6. NOT USED
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 (INFORMATION SUBMITTED DOES NOT SHOW
 INSTALLATION INSTRUCTIONS AS FAR AS
 MINIMUM DISTANCE FROM STRUCTURES
 REQUIRED FOR SERVICING ETC.).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]