Text |
| 2006-08-08 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | A. SEPARATE GAS PERMIT REQUIRED AND |
| | SHALL BE SUBMITTED WITH GENERATOR |
| | APPLICATION. |
| | |
| | B. THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR GAS PLAN REVIEW: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - IF ADDING TO AN |
| | EXISTING SYSTEM, PLEASE INDICATE ALL |
| | PIPE SIZES AND SHOW REQUIREMENTS FROM |
| | REQUIREMENTS 2, 4, & 5 BELOW. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | 3. NOT USED |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). (THIS |
| | INCLUDES EXISTING SYSTEM IF APPLICABLE). |
| | |
| | 6. NOT USED |
| | |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | 8. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | (INFORMATION SUBMITTED DOES NOT SHOW |
| | INSTALLATION INSTRUCTIONS AS FAR AS |
| | MINIMUM DISTANCE FROM STRUCTURES |
| | REQUIRED FOR SERVICING ETC.). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |