Plan Review Notes
Plan Review Notes For Permit 06061453
Permit Number 06061453
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-07-11 00:00:001. PRODUCT DATA INDICATES THAT THE
 GENERATOR IS PLANNED TO BE NATURAL GAS
 ALTHOUGH THE PLANS ONLY DISPLAYS THE
 GENRATOR NEXT TO BUILDING.
  
 2. HOW IS THE PROPOSED GENRATOR FED WITH
 A GAS SUPPLY AS NONE IS SHOWN ON THE
 SITE PLAN.
  
 3. PLEASE INDICATE ON THE PLANS WHERE
 DOORS, WINDOWS, OR ANY OTHER BUILDING
 OPENINGS ARE PRESENT ON THE ELEVATION
 WHERE THE GENERATOR IS BEING PROPOSED TO
 BE INSTALLED.
  
 4. PLEASE PROVIDE A SURVEY TO DETERMINE
 THE DISTANCE FROM THE GERATOR TO THE
 ADJACENT PROPERTY LINES.
  
 5. THE PLUMBING INSPECTOR WILL NEED TO
 SEE A PIPING LAYOUT AND AND OTHER
 DETAILS ASSOCIATED WITH THE
 INSTALLATION.
  
 6. THE GENERATOR IS TO PROVIDE BACK-UP
 POWER TO WHAT DEVICES OR SYSTEMS. IS THE
 GENERATOR TO SUPPLY BACK-UP POWER TO THE
 RETAIL STORE AND THE FUEL DISPENSING
 PUMPS OR JUST THE FUEL PUMPS. PLEASE
 IDENTIFY EQUIPMENT OR DEVICES.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709