| Date |
Text |
| 2006-07-15 00:00:00 | ****** UNSAT ******* |
| | |
| | 1) NOTE: PLEASE SEE VALUE SHALL BE BASED |
| | ON ALL LABOUR AND MATERIALS WHETHER OR |
| | NOT ANY MATERIALS ARE OWNER SUPPLIED. |
| | FBC ADMIN SECT 108.3 AS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. |
| | |
| | 2) NOTE: PLEASE SEE THAT PLANS ARE |
| | REQUIRED TO BE DONE BY A PE. |
| | FS 471.003. |
| | |
| | 3) NOTE: PLEASE PROVIDE INFORMATION ON |
| | WHAT TYPE OF RETAIL STORE THIS SYSTEM |
| | WILL BE SUPPLYING? IF THIS IS GAS |
| | STATION FURTHER CONSULTATION WILL BE |
| | REQUIRED AS AN ATS MAY NOT BE PERMITTED. |
| | PLEASE INDICAT OF ANY EM DEVICES WILL BE |
| | RE-FED FROM THIS GEN OR DOES ALL |
| | EXISTING EM DEVICES CONTAIN BATTERY BACK |
| | UP. |
| | |
| | 4) NOTE: PLEASE KNOW, THE A/C HEAT LOADS |
| | SHALL BE FIGURED AT 100%. PLEASE KNOW, |
| | LOAD SHEDDING AND TIMED DELAY STARTING |
| | OF UNITS WILL BE PERMITTED. |
| | PLEASE ALSO KNOW, ALL CONTINUOUS LOADS |
| | SHALL BE SHOWN AT 125%. 215.3,230.42 ETC |
| | 702.5, 220.31, 90.4 |
| | |
| | 5) NOTE: PLEASE KNOW, ALL PLANS SHALL |
| | CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF ALL PERSONS RESPONSIBLE FOR DESIGN |
| | ETC. |
| | FBC 106.1 |
| | |
| | 6) NOTE: PLEASE BE SURE ALL MANUFACTURES |
| | SPECS INCLUDE THE MIN CLEARENCES |
| | REQUIRED BY MANUFACTURE FOR EQUIPMENT. |
| | 110.26,110.3 ETC |
| | |
| | 7) NOTE: PLEASE INDICATE ON SITE PLAN |
| | WHERE THE NEW MAIN, ATS ETC WILL BE |
| | LOCATED. |
| | NEED TO VERIFY GROUPING OF DISCONNECTS |
| | PER 225.34,230.72 ETC. |
| | |
| | 8) NOTE: PLEASE CLARIFY WHICH DISCONNECT |
| | WILL FEED THE 400A ATS, AS BOTH 400A |
| | MAINS CAN NOT FEED ONE 400A ATS, AS THE |
| | ATS IS NOT RATED FOR 800A'S.PLEASE |
| | REVISE RISER, AS SHOWN IS NOT CLEAR WHAT |
| | IS TAKING PLACE. |
| | 310.16,240.4,215.5, 230.70 ETC. |
| | |
| | 9) NOTE: PLEASE SUBMIT MANUFACTURES |
| | SPECS/CUT SHEETS REQUIRED FOR ATS. |
| | 110.3,702.6 ETC. |
| | |
| | |
| | 10) NOTE: PLEASE INDICATE THE OCP AT THE |
| | GEN, AS THE VOLTAGE FOR SERVICE IS NOT |
| | SHOWN. |
| | PLEASE HIGH-LIGHT SPECS ALSO. |
| | 106.1.2 FBC ADMIN SECT, 445.13 ETC. |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES |
| | AS THEY WILL HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |