Plan Review Notes
Plan Review Notes For Permit 06061430
Permit Number 06061430
Review Stop E
Sequence Number 3
Notes
Date Text
2006-09-08 00:00:00******** UNSAT 3RD REVIEW ********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED ALONG
 WITH SOME NEW COMMENTS DUE TO CHANGES IN
 PLANS.
 ** PLEASE SEE NOTE BELOW ARE TAKEN
 DRIRECTLY FROM PREVIOUS REVIEW WITH NEW
 NOTES ADDED AT THE BOTTOM OF NOTES.
  
  
 1) NOTE: NO, PLEASE SEE NOT OF THIS
 PREVIOUS NOTE WAS ADDRESSED. PLEASE SEE
 NUMEROUS ITEMS ON PANEL SCHEDULE WHICH
 IS NOT IN LOAD CALCULATIONS, PLEASE SEE
 NO LOAD CALCULATION WAS SUBMITTEF RO
 EXISTING LOAD AND NEW INCREASED LOAD ON
 EXISTING SERVICE.
 PLEASE CORRELATE AND ADJUST ALL.
  
 ** PREVIOUS REVIEW NOTE **
  
 PLEASE SUBMIT INFORMATION ON
 LOAD OF EXISTING SERVICE WITH NEW LOADS
 BEING ADDED.220.31B
 PLEASE SHOW AND INDICATE THE EXSTING
 FEEDERS AND OCP FROM THE EXISTING 300A
 PANEL.
 PLEASE CORRELATE PANEL SCHEDULE(S) AND
 RISER DIAGRAM. PLEASE SEE RISER SHOWS
 150A PANEL AND 150A MAIN, YET, PLEASE
 SEE PANEL SHOWS 200A MAIN ON A 150A BUS.
 PLEASE ALSO SEE EXISTING PANEL SCHEDULE.
 240.4,310.16, 215.5, ETC.
  
 2) NOTE: NO, PLEASE SEE NO SWITCH IS
 BEING INDICATED AT THE STAIRS LEADING TO
 FLR ABOVE AS PERVIOUSLY NOTED. PLEASE
 SEE A 4-WAY SWITCH IS BEING SHOWN,
 HOWEVER SWITCHING IS ONLY BEING SHOWN
 FROM TWO LOCATIONS, THER-FORE THIS
 WOULD BE TWO 3-WAYS SWITHCES.
  
 ** PREVIIOUS REVIEW NOTE **
 PLEASE SEE MEANS EGRESS LT
 CONTROL SHOULD BE IN THE IMMEDIATE AREA
 LEADING TO THE FLR ABOVE.
 210.70, LS 101 7.8
  
 3) NOTE: NO, PLEASE SEE THIS IS THE SAME
 ALSO. MAY NOT USE LANSCAPE LTS AS THEY
 ARE NOT ON PLANS SHOWING THE TYPE AND
 LOCATIONS OF FIXTURES. THE LANSCAPE LTS
 ARE NOT INCLUDE IN THE PLANS SUBMITTED.
 A CONTROL AS REQUIRED BY 210.70, LS101
 7.8 IS REQUIRED TO CONTROL A LT LOCATED
 IN THE AREA OF EGRESS. (PORCH, DOOR,
 SCONCE) ETC IN ORDER TO ILLUMINATE
 OUTSIDE THIS DOOR.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING CONTROL
 EXITING FROM FIRST FLR TO OUTSIDE.
 MENTIONS "LANSCAPE LTS, HOWEVER PLEASE
 KNOW, THERE SHOULD BE A LT IN THE AREA
 TO LT UP EGRESS.
 210.70
  
 4) NOTE: OK, HOWEVER PLEASE SEE NOW TWO
 SD'S ARE BEING ADDED TO PLANS AT LOWER
 LEVEL IN THE SAME VICINITY WITH
 EACHOTHER?? PLEASE ALSO SEE CIRCUITING
 IS MISSING FOR THESE. PLEASE KNOW, THESE
 WOULD BE REQUIRED TO BE ON AN ARC FAULT
 PROTECTED CIRCUIT PER 210.12.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING SD'S INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS OR
 ADAPTABLE SLEEPING ROOMS.
 PLEASE SEE THE EXERCISE RM IS CONSIDERED
 AN ADAPTBALE SLEEPING RM. PLEASE SEE
 REDLINED PLANS.
 NFPA-72 11.5.1.1,11.8.3
  
 5) NOTE: OK, SEE NOTE ABOVE FOR SD'S.
  
 6) NOTE: OK.
  
 7) NOTE: NO, PLEASE SEE C-17 AS THIS IS
 AN AREA DETERMINED BY THE NEC IN
 210.52B1 REQUIRED TO BE ON ONE OR MORE
 OF THE SMALL APPLIANCE CIRCUITS OR
 DEDICATED DINING/BRKFAST AREA(S). PLEASE
 SEE THIS AREA REDLINED WOULD REQUIRED
 20A #12.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.52B1 FOR DINING
 AREAS AND AREAS OF THE LIKE REQUIRING
 THOSE RECEPTS TO BE ON ONE OR MORE OF
 THE SMALL APPLIANCE CIRCUITS. THIS MAY
 BE MORE THAN THE TWO MIN.
 PLEASE SEE MISSING RECEPT(S) PER 210.52,
 REDLINED.
 PLEASE ALSO SEE REDLINED MISSING RECEPT
 ON 2' OR MORE OF WALL.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE:NO, PLEASE SEE ONLY ONE SHOWS
 THE CORRECT OCP. (2-POLE 30A OCP.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY THE OCP ETC FOR
 THE AHU #1, AS THE 2-POLE 45 SEEMS HIGH
 FOR A 5KW HEAT STRIP.
  
 ** NEW NOTE **
 14) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO REPEAT CODE COMPLIANT
 COMMENTS FOR DESIGN PROFESSIONALS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
 15) NOTE: PLEASE SEE THE FOLLOWING WAS
 NOT DONE. THIS MUST BE DONE OR PLANS MAY
 COME BACK FOR ONLY THIS COMMENT.
 THE PREVIOUS REVIEW REQUESTED THIS BE
 DONE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  