| 2006-09-08 00:00:00 | ******** UNSAT 3RD REVIEW ******** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED ALONG |
| | WITH SOME NEW COMMENTS DUE TO CHANGES IN |
| | PLANS. |
| | ** PLEASE SEE NOTE BELOW ARE TAKEN |
| | DRIRECTLY FROM PREVIOUS REVIEW WITH NEW |
| | NOTES ADDED AT THE BOTTOM OF NOTES. |
| | |
| | |
| | 1) NOTE: NO, PLEASE SEE NOT OF THIS |
| | PREVIOUS NOTE WAS ADDRESSED. PLEASE SEE |
| | NUMEROUS ITEMS ON PANEL SCHEDULE WHICH |
| | IS NOT IN LOAD CALCULATIONS, PLEASE SEE |
| | NO LOAD CALCULATION WAS SUBMITTEF RO |
| | EXISTING LOAD AND NEW INCREASED LOAD ON |
| | EXISTING SERVICE. |
| | PLEASE CORRELATE AND ADJUST ALL. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | |
| | PLEASE SUBMIT INFORMATION ON |
| | LOAD OF EXISTING SERVICE WITH NEW LOADS |
| | BEING ADDED.220.31B |
| | PLEASE SHOW AND INDICATE THE EXSTING |
| | FEEDERS AND OCP FROM THE EXISTING 300A |
| | PANEL. |
| | PLEASE CORRELATE PANEL SCHEDULE(S) AND |
| | RISER DIAGRAM. PLEASE SEE RISER SHOWS |
| | 150A PANEL AND 150A MAIN, YET, PLEASE |
| | SEE PANEL SHOWS 200A MAIN ON A 150A BUS. |
| | PLEASE ALSO SEE EXISTING PANEL SCHEDULE. |
| | 240.4,310.16, 215.5, ETC. |
| | |
| | 2) NOTE: NO, PLEASE SEE NO SWITCH IS |
| | BEING INDICATED AT THE STAIRS LEADING TO |
| | FLR ABOVE AS PERVIOUSLY NOTED. PLEASE |
| | SEE A 4-WAY SWITCH IS BEING SHOWN, |
| | HOWEVER SWITCHING IS ONLY BEING SHOWN |
| | FROM TWO LOCATIONS, THER-FORE THIS |
| | WOULD BE TWO 3-WAYS SWITHCES. |
| | |
| | ** PREVIIOUS REVIEW NOTE ** |
| | PLEASE SEE MEANS EGRESS LT |
| | CONTROL SHOULD BE IN THE IMMEDIATE AREA |
| | LEADING TO THE FLR ABOVE. |
| | 210.70, LS 101 7.8 |
| | |
| | 3) NOTE: NO, PLEASE SEE THIS IS THE SAME |
| | ALSO. MAY NOT USE LANSCAPE LTS AS THEY |
| | ARE NOT ON PLANS SHOWING THE TYPE AND |
| | LOCATIONS OF FIXTURES. THE LANSCAPE LTS |
| | ARE NOT INCLUDE IN THE PLANS SUBMITTED. |
| | A CONTROL AS REQUIRED BY 210.70, LS101 |
| | 7.8 IS REQUIRED TO CONTROL A LT LOCATED |
| | IN THE AREA OF EGRESS. (PORCH, DOOR, |
| | SCONCE) ETC IN ORDER TO ILLUMINATE |
| | OUTSIDE THIS DOOR. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING CONTROL |
| | EXITING FROM FIRST FLR TO OUTSIDE. |
| | MENTIONS "LANSCAPE LTS, HOWEVER PLEASE |
| | KNOW, THERE SHOULD BE A LT IN THE AREA |
| | TO LT UP EGRESS. |
| | 210.70 |
| | |
| | 4) NOTE: OK, HOWEVER PLEASE SEE NOW TWO |
| | SD'S ARE BEING ADDED TO PLANS AT LOWER |
| | LEVEL IN THE SAME VICINITY WITH |
| | EACHOTHER?? PLEASE ALSO SEE CIRCUITING |
| | IS MISSING FOR THESE. PLEASE KNOW, THESE |
| | WOULD BE REQUIRED TO BE ON AN ARC FAULT |
| | PROTECTED CIRCUIT PER 210.12. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING SD'S INSIDE |
| | AND OUTSIDE ALL SLEEPING ROOMS OR |
| | ADAPTABLE SLEEPING ROOMS. |
| | PLEASE SEE THE EXERCISE RM IS CONSIDERED |
| | AN ADAPTBALE SLEEPING RM. PLEASE SEE |
| | REDLINED PLANS. |
| | NFPA-72 11.5.1.1,11.8.3 |
| | |
| | 5) NOTE: OK, SEE NOTE ABOVE FOR SD'S. |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: NO, PLEASE SEE C-17 AS THIS IS |
| | AN AREA DETERMINED BY THE NEC IN |
| | 210.52B1 REQUIRED TO BE ON ONE OR MORE |
| | OF THE SMALL APPLIANCE CIRCUITS OR |
| | DEDICATED DINING/BRKFAST AREA(S). PLEASE |
| | SEE THIS AREA REDLINED WOULD REQUIRED |
| | 20A #12. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 210.52B1 FOR DINING |
| | AREAS AND AREAS OF THE LIKE REQUIRING |
| | THOSE RECEPTS TO BE ON ONE OR MORE OF |
| | THE SMALL APPLIANCE CIRCUITS. THIS MAY |
| | BE MORE THAN THE TWO MIN. |
| | PLEASE SEE MISSING RECEPT(S) PER 210.52, |
| | REDLINED. |
| | PLEASE ALSO SEE REDLINED MISSING RECEPT |
| | ON 2' OR MORE OF WALL. |
| | |
| | 8) NOTE: OK. |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: OK. |
| | |
| | 13) NOTE:NO, PLEASE SEE ONLY ONE SHOWS |
| | THE CORRECT OCP. (2-POLE 30A OCP. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE VERIFY THE OCP ETC FOR |
| | THE AHU #1, AS THE 2-POLE 45 SEEMS HIGH |
| | FOR A 5KW HEAT STRIP. |
| | |
| | ** NEW NOTE ** |
| | 14) NOTE: PLEASE SEE FS 553.80(2)(B) |
| | WITH RESPECT TO REPEAT CODE COMPLIANT |
| | COMMENTS FOR DESIGN PROFESSIONALS. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | 15) NOTE: PLEASE SEE THE FOLLOWING WAS |
| | NOT DONE. THIS MUST BE DONE OR PLANS MAY |
| | COME BACK FOR ONLY THIS COMMENT. |
| | THE PREVIOUS REVIEW REQUESTED THIS BE |
| | DONE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |