| 2006-08-15 00:00:00 | ******** UNSAT ******** |
| | |
| | 1) NOTE: PLEASE SUBMIT INFORMATION ON |
| | LOAD OF EXISTING SERVICE WITH NEW LOADS |
| | BEING ADDED.220.31B |
| | PLEASE SHOW AND INDICATE THE EXSTING |
| | FEEDERS AND OCP FROM THE EXISTING 300A |
| | PANEL. |
| | PLEASE CORRELATE PANEL SCHEDULE(S) AND |
| | RISER DIAGRAM. PLEASE SEE RISER SHOWS |
| | 150A PANEL AND 150A MAIN, YET, PLEASE |
| | SEE PANEL SHOWS 200A MAIN ON A 150A BUS. |
| | PLEASE ALSO SEE EXISTING PANEL SCHEDULE. |
| | 240.4,310.16, 215.5, ETC. |
| | |
| | 2) NOTE: PLEASE SEE MEANS EGRESS LT |
| | CONTROLL SHOUDL BE IN THE IMMEDIATE AREA |
| | LEADING TO THE FLR ABOVE. |
| | 210.70, LS 101 7.8 |
| | |
| | 3) NOTE: PLEASE SEE MISSING CONTROL |
| | EXITING FROM FIRST FLR TO OUTSIDE. |
| | MENTIONS "LANSCAPE LTS, HOWEVER PLEASE |
| | KNOW, THERE SHOULD BE A LT IN THE AREA |
| | TO LT UP EGRESS. |
| | 210.70 |
| | |
| | 4) NOTE: PLEASE SEE MISSING SD'S INSIDE |
| | AND OUTSIDE ALL SLEEPING ROOMS OR |
| | ADAPTABLE SLEEPING ROOMS. |
| | PLEASE SEE THE EXERCISE RM IS CONSIDERED |
| | AN ADAPTBALE SLEEPING RM. PLEASE SEE |
| | REDLINED PLANS. |
| | NFPA-72 11.5.1.1,11.8.3 |
| | |
| | 5) NOTE: PLEASE SEE CIRCUITING FOR ALL |
| | "OUTLETS" IN SLEEPING ROOMS OR ADAPTABLE |
| | SLEEPIGN RMS ARE REQUIED TO HAVE ARC |
| | FAULT PROTECTION. THIS WOULD BE THE |
| | UPSTAIRS BEDRM AND THE "EXCERCISE RM. |
| | PLEASE SEE 2002 NEC210.12B AS SD'S, |
| | LTS, FANS ETC ARE REQUIRED TO BE |
| | PROTECTED. PLEASE BE SURE TO ADJUST |
| | CIRCUTING ON PANEL SCHEDULE AND IDENTIFY |
| | EACH. |
| | |
| | 6) NOTE: PLEASE SEE |
| | 210.52B1,210.11C1,220.16 AS THESE |
| | REQUIRE A MIN OF TWO SAMLL APPLIANCE |
| | CIRCUITS. PLEASE SEE THE IS CONSIDERED A |
| | DWELLING AND A KITCHEN BY DEFINITION. |
| | PLEASE ADJUST PANEL SCHEDULE AND LOAD |
| | CALCS. |
| | |
| | 7) NOTE: PLEASE SEE 210.52B1 FOR DINING |
| | AREAS AND AREAS OF THE LIKE REQUIRING |
| | THOSE RECEPTS TO BE ON ONE OR MORE OF |
| | THE SMALL APPLIANCE CIRCUITS. THIS MAY |
| | BE MORE THAN THE TWO MIN. |
| | PLEASE SEE MISSING RECEPT(S) PER 210.52, |
| | REDLINED. |
| | PLEASE ALSO SEE REDLINED MISSING RECEPT |
| | ON 2' OR MORE OF WALL. |
| | |
| | 8) NOTE: PLEASE SEE RISER MENTIONS TO |
| | CONNECT THE GROUDING ELECTRODE CONDUCTOR |
| | TO THE EXSITING FOOTER STEEL. PLEASE |
| | KNOW IN AN EXISTING STRUCTURE OF THE |
| | AGE, THERE IS A GOOD CHANCE THERE IS NO |
| | FOOTER STEEL AND THERE WOULD BE MORE |
| | HARM DONE AFFECTING THE STRUCTURAL |
| | INTEGRITY OF THE EXSITING FOOTER TRYING |
| | TO FIND STEEL WHICH MAY NOT BE THERE. |
| | PLEASE KNOW, THIS MAY BE DONW, HOWEVER |
| | NOT REQUIRED IN EXISTING BUILDINGS. |
| | PLEASE REVISE RISER OR IF NOTE STAYS |
| | THEN THIS WILL BE REQUIRED. |
| | |
| | 9) NOTE: PLEASE SEE THERE ARE TWO BATH |
| | #1 CIRCUITS. PLEASE SEE 210.52D, |
| | 210.11C3 AS NO MORE THAN ONE BATHRM MAY |
| | BE FED. |
| | |
| | 10) NOTE: PLEASE SEE FIRST FLR BATH, AS |
| | THERE IS A WALL LT AND RECEPTHOWEVER |
| | THIS IS NOT CIRCUITED NOR DOES IT SEEM |
| | IT BELONGN LOCATED THERE NEXT TO THE |
| | WATER CLOSET. |
| | PLEASE CLARIFY. |
| | |
| | 11) NOTE: PLEASE SEE CIRCUITING FOR #14 |
| | MENTIONS OUTSIDE , YET PLANS SHOW THIS |
| | BEING CIRCUITED INSIDE?? |
| | PLEASE CORRELATE. |
| | |
| | 12) NOTE: PLEASE SEE MISSING GFI |
| | RECEPT(S) FRONT AND REAR OF DWELLING AND |
| | PLEASE SEE MISSING GFI FOR CU. |
| | 210.52E,210.63, 210.8A |
| | |
| | 13) NOTE: PLEASE VERIFY THE OCP ETC FOR |
| | THE AHU #1, AS THE 2-POLE 45 SEEMS HIGH |
| | FOR A 5KW HEAT STRIP. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |