Plan Review Notes
Plan Review Notes For Permit 06061430
Permit Number 06061430
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-15 00:00:00******** UNSAT ********
  
 1) NOTE: PLEASE SUBMIT INFORMATION ON
 LOAD OF EXISTING SERVICE WITH NEW LOADS
 BEING ADDED.220.31B
 PLEASE SHOW AND INDICATE THE EXSTING
 FEEDERS AND OCP FROM THE EXISTING 300A
 PANEL.
 PLEASE CORRELATE PANEL SCHEDULE(S) AND
 RISER DIAGRAM. PLEASE SEE RISER SHOWS
 150A PANEL AND 150A MAIN, YET, PLEASE
 SEE PANEL SHOWS 200A MAIN ON A 150A BUS.
 PLEASE ALSO SEE EXISTING PANEL SCHEDULE.
 240.4,310.16, 215.5, ETC.
  
 2) NOTE: PLEASE SEE MEANS EGRESS LT
 CONTROLL SHOUDL BE IN THE IMMEDIATE AREA
 LEADING TO THE FLR ABOVE.
 210.70, LS 101 7.8
  
 3) NOTE: PLEASE SEE MISSING CONTROL
 EXITING FROM FIRST FLR TO OUTSIDE.
 MENTIONS "LANSCAPE LTS, HOWEVER PLEASE
 KNOW, THERE SHOULD BE A LT IN THE AREA
 TO LT UP EGRESS.
 210.70
  
 4) NOTE: PLEASE SEE MISSING SD'S INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS OR
 ADAPTABLE SLEEPING ROOMS.
 PLEASE SEE THE EXERCISE RM IS CONSIDERED
 AN ADAPTBALE SLEEPING RM. PLEASE SEE
 REDLINED PLANS.
 NFPA-72 11.5.1.1,11.8.3
  
 5) NOTE: PLEASE SEE CIRCUITING FOR ALL
 "OUTLETS" IN SLEEPING ROOMS OR ADAPTABLE
 SLEEPIGN RMS ARE REQUIED TO HAVE ARC
 FAULT PROTECTION. THIS WOULD BE THE
 UPSTAIRS BEDRM AND THE "EXCERCISE RM.
 PLEASE SEE 2002 NEC210.12B AS SD'S,
 LTS, FANS ETC ARE REQUIRED TO BE
 PROTECTED. PLEASE BE SURE TO ADJUST
 CIRCUTING ON PANEL SCHEDULE AND IDENTIFY
 EACH.
  
 6) NOTE: PLEASE SEE
 210.52B1,210.11C1,220.16 AS THESE
 REQUIRE A MIN OF TWO SAMLL APPLIANCE
 CIRCUITS. PLEASE SEE THE IS CONSIDERED A
 DWELLING AND A KITCHEN BY DEFINITION.
 PLEASE ADJUST PANEL SCHEDULE AND LOAD
 CALCS.
  
 7) NOTE: PLEASE SEE 210.52B1 FOR DINING
 AREAS AND AREAS OF THE LIKE REQUIRING
 THOSE RECEPTS TO BE ON ONE OR MORE OF
 THE SMALL APPLIANCE CIRCUITS. THIS MAY
 BE MORE THAN THE TWO MIN.
 PLEASE SEE MISSING RECEPT(S) PER 210.52,
 REDLINED.
 PLEASE ALSO SEE REDLINED MISSING RECEPT
 ON 2' OR MORE OF WALL.
  
 8) NOTE: PLEASE SEE RISER MENTIONS TO
 CONNECT THE GROUDING ELECTRODE CONDUCTOR
 TO THE EXSITING FOOTER STEEL. PLEASE
 KNOW IN AN EXISTING STRUCTURE OF THE
 AGE, THERE IS A GOOD CHANCE THERE IS NO
 FOOTER STEEL AND THERE WOULD BE MORE
 HARM DONE AFFECTING THE STRUCTURAL
 INTEGRITY OF THE EXSITING FOOTER TRYING
 TO FIND STEEL WHICH MAY NOT BE THERE.
 PLEASE KNOW, THIS MAY BE DONW, HOWEVER
 NOT REQUIRED IN EXISTING BUILDINGS.
 PLEASE REVISE RISER OR IF NOTE STAYS
 THEN THIS WILL BE REQUIRED.
  
 9) NOTE: PLEASE SEE THERE ARE TWO BATH
 #1 CIRCUITS. PLEASE SEE 210.52D,
 210.11C3 AS NO MORE THAN ONE BATHRM MAY
 BE FED.
  
 10) NOTE: PLEASE SEE FIRST FLR BATH, AS
 THERE IS A WALL LT AND RECEPTHOWEVER
 THIS IS NOT CIRCUITED NOR DOES IT SEEM
 IT BELONGN LOCATED THERE NEXT TO THE
 WATER CLOSET.
 PLEASE CLARIFY.
  
 11) NOTE: PLEASE SEE CIRCUITING FOR #14
 MENTIONS OUTSIDE , YET PLANS SHOW THIS
 BEING CIRCUITED INSIDE??
 PLEASE CORRELATE.
  
 12) NOTE: PLEASE SEE MISSING GFI
 RECEPT(S) FRONT AND REAR OF DWELLING AND
 PLEASE SEE MISSING GFI FOR CU.
 210.52E,210.63, 210.8A
  
 13) NOTE: PLEASE VERIFY THE OCP ETC FOR
 THE AHU #1, AS THE 2-POLE 45 SEEMS HIGH
 FOR A 5KW HEAT STRIP.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  