2007-03-07 07:17:54 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A LOAD CALCULATION FOR THE
 LOAD INTENDED TO BE SERVED. 215.5. THE CALCULATIONS
 SUBMITTED EXCEED THE GENERATOR OUTPUT, SEE 702.5 2005
 NEC.
  
 2} PROVIDE A PANEL SCHEDULE FOR THE
 GENERATOR PANEL. 106.3.5.4 FBC AS
 AMMENDED. 215.5 NEC
  
 3} THE RISER SHOWS A 25 KW GENERATOR, THE SPEC'S FOR A
 20 KW WERE SUBMITTED, PLEASE CORRELATE.
  
 4} PLEASE HI-LITE THE TRANSFER SWITCH INTENDED FOR
 INSTALLATION ON THE SPEC SHEET SUBMITTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  