| Plan Review Notes For Permit 06061421 |
| Permit Number |
06061421 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-03-07 07:17:54 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE A LOAD CALCULATION FOR THE | | | LOAD INTENDED TO BE SERVED. 215.5. THE CALCULATIONS | | | SUBMITTED EXCEED THE GENERATOR OUTPUT, SEE 702.5 2005 | | | NEC. | | | | | | 2} PROVIDE A PANEL SCHEDULE FOR THE | | | GENERATOR PANEL. 106.3.5.4 FBC AS | | | AMMENDED. 215.5 NEC | | | | | | 3} THE RISER SHOWS A 25 KW GENERATOR, THE SPEC'S FOR A | | | 20 KW WERE SUBMITTED, PLEASE CORRELATE. | | | | | | 4} PLEASE HI-LITE THE TRANSFER SWITCH INTENDED FOR | | | INSTALLATION ON THE SPEC SHEET SUBMITTED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|