| Plan Review Notes For Permit 06061419 |
| Permit Number |
06061419 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-07 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE VALUE ON THE APPLICATION MUST | | | INCLUDE THE COST OF LABOR AND MATERIAL | | | FOR THE INSTALLATION OF ALL COMPONENTS | | | UNDER THE SCOPE OF THIS PERMIT. FBC | | | 108.3. | | | | | | 2}THE PERSON TAKING RESPONSIBILITY FOR | | | THE PLAN/DRAWINGS, SHALL PRINT AND SIGN | | | THEIR NAME ON THE SHEETS THEY DRAW. | | | PLEASE DO THIS PRIOR TO | | | RESUBMITTING.106.3.4.2 FBC. | | | | | | 3} PLEASE LOCATE ALL SERVICE EQUIPMENT | | | ON THE PLAN, METER ENCLOSURE, GENERATOR, | | | TRANSFER SWITCH, DISCONNECTS AND PANELS, | | | SO THAT COMPLIANCE WITH ARTICLES 225 AND | | | 230 CAN BE REVIEWED. | | | | | | 4} PROVIDE SPECIFICATIONS FOR THE | | | TRANSFER SWITCH. | | | | | | 5} PROVIDE A PANEL SCHEDULE PER 408.4. | | | FR THE PANEL BEING FED FROM THE | | | GENERATOR. | | | | | | 6} PROVIDE MANUFACTURERS SPECIFICATIONS/RECOMMENDATION, | | | REGARDING CLEARANCES. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561) 805-6718 | | | |
|