| Plan Review Notes For Permit 06061406 |
| Permit Number |
06061406 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-27 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)THE ASSEMLY INDICATED ON PAGE 18 | | | CONFLICTS WITH THE WRITTEN SPECIFICATION | | | YOU HAVE PROVIDED.FOR INSTANCE, FOR | | | PRESSURE YOU GIVE AN ASSEMBLY DESIGN | | | PRESSURE OF -60, 1 1/4 RING SHANK NAILS | | | WITH TIN CAPS FOR FASTENERS.ON PAGE | | | 18, THE APPROVED ASSEMBLY YOU HAVE | | | PROVIDED, THE TWO DIFFERENT OPTIONS WITH | | | A DESIGN PRESSURE OF -60 DO NOT USE THIS | | | FASTENER.IT IS UNCLEAR WHICH ASSEMBLY | | | YOU ARE USING.YOU MAY CIRCLE IT ON THE | | | PRODUCT APPROVAL AND WRITE THE SPEC FOR | | | THE FASTENING FOR CORNER AND PERIMETER | | | ZONES ON THAT SHEET, ELIMINATING THE | | | HVHZ APPLICATION FORM. |
|