| Notes |
| Date |
Text |
| 2006-07-06 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. INDICATE AIC FOR | | | THE ATS. | | | | | | 2} THE PERSON TAKING RESPONSIBILITY FOR | | | THE DESIGN MUST PRINT AND SIGN THEIR | | | NAME TO SAME PER 106.3.4.2. | | | | | | 3} 110.3(B) INSTALLATION AND USE. LISTED | | | OR LABELED EQUIPMENT SHALL BE INSTALLED | | | AND USED IN ACCORDANCE WITH ANY | | | INSTRUCTIONS INCLUDED IN THE LISTING OR | | | LABELING. SUBMIT SPECIFICATIONS | | | INDICATING CLEARANCES. | | | | | | 4} THE TRANSFER SWITCH MAY NOT BE ON THE | | | LOAD SIDE OF THE SERVICE, SEE 230.82. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|