Plan Review Notes
Plan Review Notes For Permit 06061341
Permit Number 06061341
Review Stop M
Sequence Number 2
Notes
Date Text
2006-07-27 00:00:00*** DENIED ***
 1) AS NOTED IN LAST REVIEW 6-26-06 NOTE
 #1. THE ENGINEER'S LICENSE NUMBER MUST
 APPEAR IN THE TITLE BLOCK OF EACH PAGE
 OF THE PLANS, PER FAC 61G15-23.002 .
  
 2) EXHAUST FAN IS 2250 CFM'S, SEE 2004
 FBC/M 507.13.2, WHICH WOULD REQUIRE
 3,600 CFM'S EXHAUST, PLEASE CORRECT.
  
 3) SHOW DETAIL OF HOW ANGLE IRON
 SUPPORTS ARE TO BE ANCHORED TO WALL AND
 WILL COMPLY WITH 2004 FBC/M 301.13 WIND
 RESISTANCE 140 MPH.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.