| 2006-06-29 00:00:00 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION. | | | | | | 2) PLEASE INDICATE THE MINIMUM INTERIOR | | | FINISH FOR WALLS AND CEILINGS IN TERMS | | | OF CLASS A, B, OR C. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | 4) IF DUCT SMOKE DETECTOR INSTALLATION | | | IS PART OF THE SCOPE OF THIS WORK, THEY | | | SHALL INITIATE A GENERAL FIRE ALARM IN | | | ACCORDANCE WITH LOCAL REQUIREMENTS. SHT | | | E0.1, NOTE (17). | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|