| 2007-08-13 12:42:03 | ** REVISION DENIED ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE NEW SHEETS E 1-3 WHICH ARE NOW |
| | INDICATING SUBSTANTIAL REVISIONS TO THE BUILDING |
| | ELECTRICAL SERVICE RISER. |
| | AS THIS SCOPE OF WORK WAS NOT INCLUDED AND IS NOT PART |
| | OF THE BASE TENANT BUILD OUT, PLEASE SUBMIT THIS SCOPE |
| | OF WORK UNDER SEPARATE ELECTRICAL PERMIT FOR REVIEW. |
| | THIS RISER WAS NOT REVIEWED FOR CODE COMPLIANCE. |
| | FBC 106.1, 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE THE REVISED E-1 FOR TENANT BUILD |
| | OUT NEEDS TO INCLUDE ALL CIRCUITING FOR ALL THE NEW |
| | RECEPTACLES ETC SHOWN. THERE ARE A SUBSTANTIAL AMOUNT |
| | OF RECEPTACLES WHICH HAVE BEEN ADDED TO CIRCUITS. |
| | PLEASE SUBMIT REVISED PANEL SCHEDULES ALONG WITH |
| | REVISED LOAD CALCULATIONS FOR INCREASED LOADS. |
| | 408.4, 220.12, 220.14 ETC. |
| | |
| | 3) NOTE: PLEASE KNOW AS OF THIS REVIEW THE LOW VOLTAGE |
| | PERMIT FOR PHONE/DATA HAS BEEN PLACED ON HOLD AS FEES |
| | ARE OWED FOR INCREASED VALUE. THE VALUE AS STATED ON |
| | PERMIT APPLICATION DOES NOT ACCURATELY REFLECT THE |
| | SCOPE OF WORK OF LV CABLING ON PLANS. |
| | SPOKE TO CONTRACTOR/QUALIFIER AND HE WILL PAY THE FEES |
| | OWED. |
| | FBC 108.3 |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |