2007-03-13 11:41:51*** DENIED ***
 1) PLANS PAGE A-4 SHOWS THE WALLS FOR THE CORRIDOR,
 MAIN LAB AND PORCELAIN ROOM TO BE ONE HOUR FIRE RATED
 (WALL SYMBOL LEGEND), SEE PAGE AC-1 ALL THE A/C DUCTS
 THAT PENETRATE THE FIRE RATED WALLS NEED TO COMPLY WITH
 2004 FBC/M 607, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.