2007-02-23 09:00:36*** DENIED ***
 1) PLANS PAGE A-4 SHOWS THE WALLS FOR THE MAIN LAB AND
 PORCELAIN ROOM TO BE ONE HOUR FIRE RATED, SEE PAGE AC-1
 ALL THE A/C DUCTS THAT PENETRATE THE FIRE RATED WALLS
 NEED TO COMPLY WITH 2004 FBC/M 607, PLEASE CORRECT.
  
 2) SEE PAGE AC-1 MECHANICAL ROOM THE 62X12 SUPPLY AIR
 DUCT PENETRATING THE FIRE RATED WALL WILL NEED A FIRE
 DAMPER, SEE 2004 FBC/M 607.5.1,PLEASE CORRECT.
  
 3) SEE PAGES A-3 AND A-4 (ARCHITECT'S SEAL) THE
 ARCHITECT NEED TO PUT THE DATE WHEN HE SIGNED AND
 SEALED THE PLANS, SEE FAC 61G1-16.003.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.