| Plan Review Notes For Permit 06061338 |
| Permit Number |
06061338 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-02-23 09:00:36 | *** DENIED *** | | | 1) PLANS PAGE A-4 SHOWS THE WALLS FOR THE MAIN LAB AND | | | PORCELAIN ROOM TO BE ONE HOUR FIRE RATED, SEE PAGE AC-1 | | | ALL THE A/C DUCTS THAT PENETRATE THE FIRE RATED WALLS | | | NEED TO COMPLY WITH 2004 FBC/M 607, PLEASE CORRECT. | | | | | | 2) SEE PAGE AC-1 MECHANICAL ROOM THE 62X12 SUPPLY AIR | | | DUCT PENETRATING THE FIRE RATED WALL WILL NEED A FIRE | | | DAMPER, SEE 2004 FBC/M 607.5.1,PLEASE CORRECT. | | | | | | 3) SEE PAGES A-3 AND A-4 (ARCHITECT'S SEAL) THE | | | ARCHITECT NEED TO PUT THE DATE WHEN HE SIGNED AND | | | SEALED THE PLANS, SEE FAC 61G1-16.003. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|