| Date |
Text |
| 2006-11-20 19:59:13 | ****** UNSAT 3RD REVIEW ******* |
| | |
| | ** PLEASE SEE SOME NOTE FROM PREVIOUS REVIEWS WHICH |
| | STILL NEED TO BE ADDRESSED. |
| | |
| | ** PLEASE SEE NO RESPONSE LETTERS WERE SUBMITTED IN |
| | SETS. |
| | |
| | |
| | 1) NOTE:NO, PLEASE SEE NO COMPLIANCE WITH FBC CHAPTER |
| | 13 HAS BEEN ADDRESSED. PLEASE SEE THIS IS A TENANT |
| | BUILD OUT IN A BUILDING GREATER THAN 5000 SQ FT. THIS |
| | IS NOT FOR THE REST OF THE BUILDING; IT IS FOR THIS |
| | TENANT SPACE. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1, |
| | TABLES 415.2.C.1, OR 415.2.B.1. |
| | NO ENERGY CALCULATIONS, NO PERFORMANCE CALCULATIONS, |
| | LIGHTING CONTROLS ETC. |
| | PLEASE SEE THE 2004 FBC. THIS IS NOT UNDER THE 2001 |
| | FBC. |
| | |
| | |
| | ** PREVIOUS REVIEW NOTES FROM REVIEW ONE AND TWO. ** |
| | PLEASE SEE PLANS ARE NOTED AS MEETING THE NEW FLORIDA |
| | ENERGY CODE; HOWEVER NO ITEMS COULD BE LOCATED ON PLANS |
| | TO VERIFY THIS. |
| | PLEASE SEE 2004 FBC |
| | 13-415.1.ABC.1.1,.1.2,.1.3. |
| | PLEASE SEE 13-415.1.AB.1, |
| | 13-415.2.ABC.1. |
| | PLEASE SEE EXCEPTIONS FOR MEDICAL AREAS FOR PROCEDURES |
| | ETC. |
| | |
| | PLEASE PROVIDE THE TIME OF DAY SCHEDULING, DEVICES, |
| | DEVICE LOCATIONS, OVER-RIDES AND LOCATIONS. PLEASE |
| | SPECIFY THE AMOUNT OF TIME (MAX) ON DEVICE(S) USED FOR |
| | OVER RIDES IN SPACES ETC. |
| | **PLEASE KNOW THE DEVICE(S) CAN BE LISTED ON THE |
| | ELECTRICAL DEVICE LEGEND AND NOTED ACCORDINGLY. |
| | |
| | 2) NOTE: PLEASE SEE SECTION #2/PANEL "B" IS SHOWN AS |
| | 100A'S ON SCHEDULE AND 225A ON RISER. THIS WAS IN |
| | PREVIOUS REVIEWS HOWEVER PART OF THE CHANGES WERE DONE |
| | WITH WHITE-OUT ON PLANS. PLEASE KNOW, UNDER NO |
| | CIRCUMSTANCES MAY WHITE OUT BE PLACED ON PLANS, |
| | ESPECIALLY PLANS SIGNED, DATED AND SEALED BY AN |
| | ARCHITECT OR ENGINEER. |
| | |
| | 3) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH |
| | "INITIALS", IF INDEED THIS IS THE LEGAL SIGNATURE OF |
| | THE ENGINEER OF RECORD, PLEASE SUBMIT A SIGNED, DATED, |
| | SEALED AND NOTARIZED LETTER FOR SIGNATURE VERIFICATION. |
| | THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY |
| | FUTURE REFERENCE. PLEASE BE SURE THE LETTER IS PROPERLY |
| | NOTARIZED AS REQUIRED PER FLORIDA STATUTES 117.05. |
| | |
| | 4) NOTE: PLEASE KNOW A 4X FEE HAS NOW BEEN ASSESSED FOR |
| | THIS SAID PLAN REVIEW AS REQUIRED UNDER THE FS AS |
| | NOTED. )PLEASE SEE PREVIOUS NOTES GAVE A NOTICE TO |
| | FLORIDA STATUTES 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONALS AND REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE KNOW AT THIS TIME A FEE OF $7,200.00 WILL BE DUE |
| | BEFORE PLANS CAN BE RESUBMITTED FOR REVIEW. MAY NOT |
| | SUBMIT UNTIL THIS FEE IS PAID, THIS IS REQUIRED PER THE |
| | FLORIDA STATUTES AS NOTED. THIS FEE IS NOT TO THE |
| | CONTRACTOR OR OWNER. |
| | PLEASE KNOW AT THIS TIME ONE SET OF EACH SUBMITTED |
| | ELECTRICAL PLANS ARE BEING RETAINED BY THIS OFFICE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| | DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |