Plan Review Notes
Plan Review Notes For Permit 06061338
Permit Number 06061338
Review Stop E
Sequence Number 3
Notes
Date Text
2006-11-20 19:59:13****** UNSAT 3RD REVIEW *******
  
 ** PLEASE SEE SOME NOTE FROM PREVIOUS REVIEWS WHICH
 STILL NEED TO BE ADDRESSED.
  
 ** PLEASE SEE NO RESPONSE LETTERS WERE SUBMITTED IN
 SETS.
  
  
 1) NOTE:NO, PLEASE SEE NO COMPLIANCE WITH FBC CHAPTER
 13 HAS BEEN ADDRESSED. PLEASE SEE THIS IS A TENANT
 BUILD OUT IN A BUILDING GREATER THAN 5000 SQ FT. THIS
 IS NOT FOR THE REST OF THE BUILDING; IT IS FOR THIS
 TENANT SPACE.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1,
 TABLES 415.2.C.1, OR 415.2.B.1.
 NO ENERGY CALCULATIONS, NO PERFORMANCE CALCULATIONS,
 LIGHTING CONTROLS ETC.
 PLEASE SEE THE 2004 FBC. THIS IS NOT UNDER THE 2001
 FBC.
  
  
 ** PREVIOUS REVIEW NOTES FROM REVIEW ONE AND TWO. **
 PLEASE SEE PLANS ARE NOTED AS MEETING THE NEW FLORIDA
 ENERGY CODE; HOWEVER NO ITEMS COULD BE LOCATED ON PLANS
 TO VERIFY THIS.
 PLEASE SEE 2004 FBC
 13-415.1.ABC.1.1,.1.2,.1.3.
 PLEASE SEE 13-415.1.AB.1,
 13-415.2.ABC.1.
 PLEASE SEE EXCEPTIONS FOR MEDICAL AREAS FOR PROCEDURES
 ETC.
  
 PLEASE PROVIDE THE TIME OF DAY SCHEDULING, DEVICES,
 DEVICE LOCATIONS, OVER-RIDES AND LOCATIONS. PLEASE
 SPECIFY THE AMOUNT OF TIME (MAX) ON DEVICE(S) USED FOR
 OVER RIDES IN SPACES ETC.
 **PLEASE KNOW THE DEVICE(S) CAN BE LISTED ON THE
 ELECTRICAL DEVICE LEGEND AND NOTED ACCORDINGLY.
  
 2) NOTE: PLEASE SEE SECTION #2/PANEL "B" IS SHOWN AS
 100A'S ON SCHEDULE AND 225A ON RISER. THIS WAS IN
 PREVIOUS REVIEWS HOWEVER PART OF THE CHANGES WERE DONE
 WITH WHITE-OUT ON PLANS. PLEASE KNOW, UNDER NO
 CIRCUMSTANCES MAY WHITE OUT BE PLACED ON PLANS,
 ESPECIALLY PLANS SIGNED, DATED AND SEALED BY AN
 ARCHITECT OR ENGINEER.
  
 3) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH
 "INITIALS", IF INDEED THIS IS THE LEGAL SIGNATURE OF
 THE ENGINEER OF RECORD, PLEASE SUBMIT A SIGNED, DATED,
 SEALED AND NOTARIZED LETTER FOR SIGNATURE VERIFICATION.
 THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY
 FUTURE REFERENCE. PLEASE BE SURE THE LETTER IS PROPERLY
 NOTARIZED AS REQUIRED PER FLORIDA STATUTES 117.05.
  
 4) NOTE: PLEASE KNOW A 4X FEE HAS NOW BEEN ASSESSED FOR
 THIS SAID PLAN REVIEW AS REQUIRED UNDER THE FS AS
 NOTED. )PLEASE SEE PREVIOUS NOTES GAVE A NOTICE TO
 FLORIDA STATUTES 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW AT THIS TIME A FEE OF $7,200.00 WILL BE DUE
 BEFORE PLANS CAN BE RESUBMITTED FOR REVIEW. MAY NOT
 SUBMIT UNTIL THIS FEE IS PAID, THIS IS REQUIRED PER THE
 FLORIDA STATUTES AS NOTED. THIS FEE IS NOT TO THE
 CONTRACTOR OR OWNER.
 PLEASE KNOW AT THIS TIME ONE SET OF EACH SUBMITTED
 ELECTRICAL PLANS ARE BEING RETAINED BY THIS OFFICE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved