| 2006-12-08 09:53:01 | BUILDING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561)###-#### |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 3RD |
| | ACTION: DENIED |
| | |
| | 1)FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 2) SHEET A-3 FBC. 11-4.13.6.MINIMUM MANEUVERING |
| | CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN FIGURE 11-25. THE |
| | MINIMUM CLERANCE ON THE PULL SIDE IS 18 INCHES AND 12 |
| | INCHES ON THE PUSH SIDE. AGAIN SEE FIG. 25 IN CH. 11. |
| | |
| | 3)AS REQUESTED PREVIOUSLY, SUBMIT A DETAIL ELEVATION |
| | DRAWING OF THE RECEPTION COUNTER SHOWING HOW IT WILL |
| | MEET THE REQUIREMENTS OF 11-7 (2) WHICH STATES; "OTHER |
| | COUNTERS THAT MAY "NOT" HAVE CASH REGISTER BUT AT WHICH |
| | GOODS OR SERVICES ARE SOLD OR DISTRIBUTED, EITHER ETC. |
| | THE COUNTER SHALL MEET ONE OF THE REQUIREMENTS OF THIS |
| | SECTION. |
| | |
| | 4)AGAIN, THE ENGINEERING INFORMATIONFOR THE |
| | RREMOVAL OF THE STAIRS REQUIRES AN INDEX SHEET |
| | REFERENCING ALL TO OTHER PAGES OF THE REPORT OR EACH |
| | SHEET SHALL HAVE THE ORIGINAL SEAL,SIGNATURE AND DATE |
| | OF THE ENGINEER, PHOTO COPIES ARE NOT ACCEPTABLE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |
| | |