2006-12-08 09:53:01BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 1)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) SHEET A-3 FBC. 11-4.13.6.MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN FIGURE 11-25. THE
 MINIMUM CLERANCE ON THE PULL SIDE IS 18 INCHES AND 12
 INCHES ON THE PUSH SIDE. AGAIN SEE FIG. 25 IN CH. 11.
  
 3)AS REQUESTED PREVIOUSLY, SUBMIT A DETAIL ELEVATION
 DRAWING OF THE RECEPTION COUNTER SHOWING HOW IT WILL
 MEET THE REQUIREMENTS OF 11-7 (2) WHICH STATES; "OTHER
 COUNTERS THAT MAY "NOT" HAVE CASH REGISTER BUT AT WHICH
 GOODS OR SERVICES ARE SOLD OR DISTRIBUTED, EITHER ETC.
 THE COUNTER SHALL MEET ONE OF THE REQUIREMENTS OF THIS
 SECTION.
  
 4)AGAIN, THE ENGINEERING INFORMATIONFOR THE
 RREMOVAL OF THE STAIRS REQUIRES AN INDEX SHEET
 REFERENCING ALL TO OTHER PAGES OF THE REPORT OR EACH
 SHEET SHALL HAVE THE ORIGINAL SEAL,SIGNATURE AND DATE
 OF THE ENGINEER, PHOTO COPIES ARE NOT ACCEPTABLE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  