| Date |
Text |
| 2006-08-10 00:00:00 | ****** UNSAT 2ND REVIEW ******* |
| | |
| | ** PLEASE SEE SOME NOTE FROM PREVIOUS |
| | REVIEW WHICH STILL NEED TO BE ADDRESSED. |
| | PLEASE SEE NOTE BELOW ARE TAKEN DIRECTLY |
| | FROM THE PREVIOUS REVIEW. |
| | PLEASE SEE NEW NOTES BELOW ADDED TO THE |
| | BOTTOM. |
| | |
| | 1) NOTE: OK, HOWEVER PLEASE SEE NEW |
| | ENGINEER WHICH IS SIGNED AND SEALED ON |
| | PLANS IS REQUIRED TO HAVE TITLE BLOCKS |
| | ON SAID PLANS WITH ALL INFORMATION AS |
| | SET-FORTH UNDER FLORIDA ADMINISTRATIVE |
| | CODE 61G15-23.002, FS 471.025. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY SERVICE AS SHOWN |
| | AS SOME ITEMS ARE SHOWN AS EXISTING AND |
| | SOME OTHER ITEMS DO NOT INDICATE BEING |
| | EXISTING. IT IS BEING TAKEN THAT THESE |
| | ITEMS ARE NEW. |
| | PLEASE SEE NEW SYSTEMS INVOLVING |
| | 277/480V SYSTEMS SHALL BE SIGNED, DATED |
| | AND SEALED BY A PE. |
| | 471.003 (2)(H). |
| | |
| | 2) NOTE: NO, PLEASE SEE AS PLANS SHOWS |
| | THESE ARE STILL BEING TAPPED CONDUCTORS |
| | EXCEEDING PERMITTED LENGTHS PER 240.21. |
| | PLEASE REVISE RISER FOR CODE COMPLIANCE. |
| | (SUGG: ONE FEEDER TO PANEL W/FEED THRU |
| | LUGS>) THIS IS ONLY NOTED AS THERE ARE |
| | MANY SCENERIOS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE RISER SHOWS A GUTTER |
| | IN THE LOAD SIDE OF THE TRANSFORMER |
| | WHICH VIOLATES THE NEC 240.21. THIS IS |
| | SHOWING TAPPED CONDUCTORS BEING FED FROM |
| | OTHER TAPPED CONDUCTORS. THIS IS NOT |
| | PERMITTED , AND IF THIS IS EXISTING, |
| | THIS WILL BE REQUIRED TO BE CORRECTED. |
| | PLEASE KNOW, THE TAPPED CONDUCTORS ON |
| | THE SEC SIDE OF THE TRANSFORMER SHALL |
| | TERMINATE IN A SINGLE MEANS OF OCP WHEN |
| | USING THE 10FTRULE ETC. |
| | PLEASE ADJUST RISER. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: NO, PLEASE SEE THE TENANT BUILD |
| | OUT SPACE IS IN A BUIDLING WHICH IS |
| | LARGER THAN 5000 SQFT AND WILL REQUIRE |
| | CONTROLS IN THIS BUILD OUT SPACE. THIS |
| | COMMENT WAS NOT FOR UPDATING THE REST OF |
| | THE BUILDING. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS ARE NOTED AS |
| | MEETING THE NEW FLORIDA ENERGY CODE, |
| | HOWEVER NO ITEMS COULD BE LOCATED ON |
| | PLANS TO VERIFY THIS. |
| | PLEASE SEE 2004 FBC |
| | 13-415.1.ABC.1.1,.1.2,.1.3. |
| | PLEASE SEE 13-415.1.AB.1, |
| | 13-415.2.ABC.1. |
| | PLEASE SEE EXCEPTIONS FOR MEDICAL AREAS |
| | FOR PROCEDURES ETC. |
| | |
| | PLEASE PROVIDE THE TIME OF DAY |
| | SCHEDULING, DEVICES, DEVICE LOCATIONS, |
| | OVER-RIDES AND LOCATIONS. PLEASE SPECIFY |
| | THE AMOUNT OF TIME(MAX) ON DEVICE(S) |
| | USED FOR OVER RIDES IN SPACES ETC. |
| | **PLEASE KNOW THE DEVICE(S) CAN BE |
| | LISTED ON THE ELECTRICAL DEVICE LEGEND |
| | AND NOTED ACCORDINGLY. |
| | |
| | 8) NOTE: OK, HOWEVER THIS NOTE WILL |
| | REMAIN AS NEW EQUIPMENT AND LOCATIONS |
| | WILL MOST LIKELY CHANGE DUE TO ONE OF |
| | THE ABOVE COMMENTS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY LOCATIONS OF ALL |
| | ELECTRICAL EQUIPMENT, AS PANELS ARE |
| | SHOWN ON PLANS, HOWEVER NOT CLEAR WHERE TRANSFORMER AND |
| | TWO OTHER DISCONNECTS |
| | ARE ?? |
| | 215.5,110.26, ETC |
| | |
| | 9) NOTE: OK. |
| | |
| | ***NEW NOTES ** |
| | |
| | 10) NOTE: PLEASE SEE THE ADDRESSING |
| | REVIEWER HAS ADDED AND EXTENSION AND NEW |
| | SUITE # OF 702 FOR THIS SPACE. PLEASE |
| | ADJUST ADDRESS ON TITLE BLOCKS. |
| | |
| | 11) NOTE: PLEASE SEE FS 553.80(2)(B) |
| | WITH RESPECT TO THE DEISGN PROFESSIONALS |
| | AND REPEAT COMMENTS. |
| | |
| | ** IMPORTANT** |
| | WHEN AND BEFORE RESUBMITTING PLANS ONCE |
| | ALL REVIEWS ARE DONE. PLEASE COMPLETELY |
| | REMOVE ALL OLD/VOIDED SHEETS AND ONLY |
| | INSERT ANY OF THE NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE SUBMIT ONLY ONE COPY OF THE |
| | OLD/REMOVED VOIDED SHEETS FOR REFERENCE |
| | ONLY. THESE WILL BE SEPARATE FROM NEW |
| | SETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |