| 2006-08-11 00:00:00 | |
| | |
| | |
| | 1) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 2) 61G15-23.002 SEAL, SIGNATURE AND DATE |
| | SHALL BE AFFIXED. |
| | (1) A PROFESSIONAL ENGINEER SHALL SIGN |
| | HIS NAME AND AFFIX HIS SEAL TO ALL |
| | PLANS, SPECIFICATIONS, REPORTS, FINAL |
| | BID DOCUMENTS PROVIDED TO THE OWNER OR |
| | THE OWNER'S REPRESENTATIVE, OR OTHER |
| | DOCUMENTS PREPARED OR ISSUED BY SAID |
| | REGISTRANT AND BEING FILED FOR PUBLIC |
| | RECORD. THE DATE THAT THE SIGNATURE AND |
| | SEAL IS AFFIXED AS PROVIDED HEREIN SHALL |
| | BE ENTERED ON SAID PLANS, |
| | SPECIFICATIONS,REPORTS, OR OTHER |
| | DOCUMENTS IMMEDIATELY UNDER THE |
| | SIGNATURE OF THE PROFESSIONAL ENGINEER. |
| | (2) EACH SHEET OF PLANS AND PRINTS |
| | WHICH MUST BE SEALED UNDER THE |
| | PROVISIONS OF CHAPTER 471, F.S., SHALL |
| | BE SEALED, SIGNED AND DATED BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE |
| | CHARGE. ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME, ADDRESS, AND LICENSE NUMBER |
| | ON EACH SHEET. |
| | (SEE SHEET A-3) |
| | |
| | 3) OK. |
| | |
| | 4) OK. PER SHEET P-4 |
| | |
| | 5) OK. |
| | |
| | 6) OK. |
| | |
| | 7) 11-7.2 SALES AND SERVICE COUNTERS , |
| | TELLER WINDOWS, INFORMATION COUNTERS. |
| | (2) AT TICKETING COUNTERS , TELLER |
| | STATIONS IN A BANK, REGISTRATION |
| | COUNTERS IN HOTELS AND MOTELS, BOX |
| | OFFICE TICKET COUNTERS , AND OTHER |
| | COUNTERS THAT MAY NOT HAVE A CASH |
| | REGISTER BUT AT WHICH GOODS OR SERVICES |
| | ARE SOLD OR DISTRIBUTED, EITHER: |
| | (I) A PORTION OF THE MAIN COUNTER WHICH |
| | IS A MINIMUM OF 36 INCHES (915 MM) IN |
| | LENGTH SHALL BE PROVIDED WITH A MAXIMUM |
| | HEIGHT OF 36 INCHES (915 MM);OR |
| | (II) AN AUXILIARY COUNTER WITH A |
| | MIXIMUM HEIGHT OF 36" IN CLOSE PROXIMITY |
| | TO THE MAIN COUNTER SHALL BE |
| | PROVIDED.SUBMIT A DETAIL ELEVATION |
| | DRAWING OF THE RECEPTION COUNTER SHOWING |
| | HOW THE ACCESSIBILITY REQUIREMENTS WILL |
| | BE MET. ALL BUSINESS AND SHALL MEET THE |
| | REQUIREMENTS OFSECTION 11-7. |
| | SUBMIT A DETAIL ELEVATION DRAWING OF THE |
| | RECEPTION COUNTER SHOWING HOW THE |
| | COUNTER WILL MEET THE ACCESSIBILITY |
| | REQUIREMENTS WITHOUT GOING INTO THE WORK |
| | AREA OF THE RECEPTIONIST. |
| | |
| | 8)2004 EXISTING BUILDING CODE 605.2 THE |
| | MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THIS SECTION. |
| | EXCEPTIONS: |
| | 1. WHERE THE WORK AREA AND THE MEANS OF |
| | EGRESS SERVING IT COMPLIES WITH THE |
| | FLORIDA FIRE PREVENTION CODE . |
| | 2. MEANS OF EGRESS CONFORMING TO THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING |
| | CODE, BUILDING AND THE FLORIDA FIRE |
| | PREVENTION CODE UNDER WHICH THE BUILDING |
| | WAS CONSTRUCTED SHALL BE CONSIDERED |
| | COMPLIANT MEANS OF EGRESS IF, IN THE |
| | OPINION OF THE CODE OFFICIAL, THEY DO |
| | NOT CONSTITUTE A DISTINCT HAZARD TO |
| | LIFE. {EXIT |
| | STAIRWAYS,CHUTES,JANITORCLOSETS, GUEST |
| | ROOMS, SERVICE ROOMS, ETC., SHALL NOT |
| | OPEN INTO THE ELEVATOR LOBBY.[1982 |
| | STANDARD BUILDING CODE SEC.506.6 (1)} |
| | NOTE: THE MECH.ROOM AND BOTH EXIT |
| | STAIRWAYS OPEN INTO THE ELEVATOR LOBBY. |
| | NOTE: THIS BUILDING WAS CONSTRUCTED |
| | DURING THE 1982 BUILDING CODE PERIOD. |
| | |
| | 9) OK. |
| | |
| | 10) OK. |
| | |
| | 11) THE ENGINEERING INFORMATION FOR THE |
| | REMOVAL OF THE STAIRS REQUIRES AN INDEX |
| | SHEET REFERING TO PAGES INCLUDED IN THE |
| | PACKAGE, OR EACH SHEET SHALL HAVE THE |
| | ORIGINAL SEAL, SIGNATURE AND DATE OF THE |
| | ENGINEER. PHOTO COPIES ARE NOT |
| | ACCEPTABLE. |
| | |