2006-08-11 00:00:00 
  
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) 61G15-23.002 SEAL, SIGNATURE AND DATE
 SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL
 PLANS, SPECIFICATIONS, REPORTS, FINAL
 BID DOCUMENTS PROVIDED TO THE OWNER OR
 THE OWNER'S REPRESENTATIVE, OR OTHER
 DOCUMENTS PREPARED OR ISSUED BY SAID
 REGISTRANT AND BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND
 SEAL IS AFFIXED AS PROVIDED HEREIN SHALL
 BE ENTERED ON SAID PLANS,
 SPECIFICATIONS,REPORTS, OR OTHER
 DOCUMENTS IMMEDIATELY UNDER THE
 SIGNATURE OF THE PROFESSIONAL ENGINEER.
 (2) EACH SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE
 PROVISIONS OF CHAPTER 471, F.S., SHALL
 BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE
 CHARGE. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET.
 (SEE SHEET A-3)
  
 3) OK.
  
 4) OK. PER SHEET P-4
  
 5) OK.
  
 6) OK.
  
 7) 11-7.2 SALES AND SERVICE COUNTERS ,
 TELLER WINDOWS, INFORMATION COUNTERS.
 (2) AT TICKETING COUNTERS , TELLER
 STATIONS IN A BANK, REGISTRATION
 COUNTERS IN HOTELS AND MOTELS, BOX
 OFFICE TICKET COUNTERS , AND OTHER
 COUNTERS THAT MAY NOT HAVE A CASH
 REGISTER BUT AT WHICH GOODS OR SERVICES
 ARE SOLD OR DISTRIBUTED, EITHER:
 (I) A PORTION OF THE MAIN COUNTER WHICH
 IS A MINIMUM OF 36 INCHES (915 MM) IN
 LENGTH SHALL BE PROVIDED WITH A MAXIMUM
 HEIGHT OF 36 INCHES (915 MM);OR
 (II) AN AUXILIARY COUNTER WITH A
 MIXIMUM HEIGHT OF 36" IN CLOSE PROXIMITY
 TO THE MAIN COUNTER SHALL BE
 PROVIDED.SUBMIT A DETAIL ELEVATION
 DRAWING OF THE RECEPTION COUNTER SHOWING
 HOW THE ACCESSIBILITY REQUIREMENTS WILL
 BE MET. ALL BUSINESS AND SHALL MEET THE
 REQUIREMENTS OFSECTION 11-7.
 SUBMIT A DETAIL ELEVATION DRAWING OF THE
 RECEPTION COUNTER SHOWING HOW THE
 COUNTER WILL MEET THE ACCESSIBILITY
 REQUIREMENTS WITHOUT GOING INTO THE WORK
 AREA OF THE RECEPTIONIST.
  
 8)2004 EXISTING BUILDING CODE 605.2 THE
 MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF THIS SECTION.
 EXCEPTIONS:
 1. WHERE THE WORK AREA AND THE MEANS OF
 EGRESS SERVING IT COMPLIES WITH THE
 FLORIDA FIRE PREVENTION CODE .
 2. MEANS OF EGRESS CONFORMING TO THE
 REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING AND THE FLORIDA FIRE
 PREVENTION CODE UNDER WHICH THE BUILDING
 WAS CONSTRUCTED SHALL BE CONSIDERED
 COMPLIANT MEANS OF EGRESS IF, IN THE
 OPINION OF THE CODE OFFICIAL, THEY DO
 NOT CONSTITUTE A DISTINCT HAZARD TO
 LIFE. {EXIT
 STAIRWAYS,CHUTES,JANITORCLOSETS, GUEST
 ROOMS, SERVICE ROOMS, ETC., SHALL NOT
 OPEN INTO THE ELEVATOR LOBBY.[1982
 STANDARD BUILDING CODE SEC.506.6 (1)}
 NOTE: THE MECH.ROOM AND BOTH EXIT
 STAIRWAYS OPEN INTO THE ELEVATOR LOBBY.
 NOTE: THIS BUILDING WAS CONSTRUCTED
 DURING THE 1982 BUILDING CODE PERIOD.
  
 9) OK.
  
 10) OK.
  
 11) THE ENGINEERING INFORMATION FOR THE
 REMOVAL OF THE STAIRS REQUIRES AN INDEX
 SHEET REFERING TO PAGES INCLUDED IN THE
 PACKAGE, OR EACH SHEET SHALL HAVE THE
 ORIGINAL SEAL, SIGNATURE AND DATE OF THE
 ENGINEER. PHOTO COPIES ARE NOT
 ACCEPTABLE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  