| Plan Review Notes For Permit 06061338 |
| Permit Number |
06061338 |
|
| Review Stop |
MEDGAS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-30 00:00:00 | DENIED; | | | 1.ADD TO NOTES; OXYGEN, COMPRESSED AIR , | | | AND VACUUM PIPING TO BE INSTALLED BY A | | | CERTIFIED MED-GAS CONTRACTOR. SEPARATE | | | PERMIT REQUIRED. | | | 2.PAGE P-3 OXYGEN PIPING DIAGRAM; SHOW | | | PIPE SIZE, MATERIAL, AND HOW JOINTS ARE | | | TO BE DONE. ALSO SHOW ALL SHUTOFF VALVES | | | AND ALARMS REQUIRED. | | | 3.SHOW DETAIL OR LIST EQUIPMENT TO BE | | | USED TO SECURE OXYGENT TANKS. | | | 4.LEVEL 3 VACUUM; SHOW CHECK VALVE | | | REQUIRED SEC. 5.3.3.6.3.2(1) AND A NOTE | | | REQUIRING A DEEP SEAL TRAP SEC. | | | 5.3.3.6.3.2(2). | | | 5 ADD TO PLANS, EXHAUST FROM VACUUM | | | SYSTEM TO BE SCREENED SEC. 5.3.3.6.4.6. | | | MED-GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|