Plan Review Notes
Plan Review Notes For Permit 06061338
Permit Number 06061338
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-07-03 00:00:00***DENIED***
  
 1) PLEASE NOTE THAT ANY ELEVATION CHANGE
 IN EXCESS OF 1/4" SHALL COMPLY WITH NFPA
 101, 2003 EDITION SEC. 7.1.6.2.
  
 2) PRESSURIZED GAS CYLINDERS SHALL BE
 SECURED BY APPROVED MEANS. PLEASE SEE
 LARGER CYLINDERS TO BE SECURED WITH
 CHAINS.
  
 3) FLORIDA FIRE PREVENTION CODE TO
 COMPLY WITH 2004 EDITION.
  
 4) PLEASE SEE MECHANICAL PROVISO. IN
 ADDITION TO FAN SHUTDOWN, DUCT SMOKE
 DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM WHEN TIED INTO A FIRE ALARM
 SYSTEM.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722