| Plan Review Notes For Permit 06061338 |
| Permit Number |
06061338 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-03 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE NOTE THAT ANY ELEVATION CHANGE | | | IN EXCESS OF 1/4" SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION SEC. 7.1.6.2. | | | | | | 2) PRESSURIZED GAS CYLINDERS SHALL BE | | | SECURED BY APPROVED MEANS. PLEASE SEE | | | LARGER CYLINDERS TO BE SECURED WITH | | | CHAINS. | | | | | | 3) FLORIDA FIRE PREVENTION CODE TO | | | COMPLY WITH 2004 EDITION. | | | | | | 4) PLEASE SEE MECHANICAL PROVISO. IN | | | ADDITION TO FAN SHUTDOWN, DUCT SMOKE | | | DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM WHEN TIED INTO A FIRE ALARM | | | SYSTEM. | | | | | | 5) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|