| Date |
Text |
| 2006-06-28 00:00:00 | ****** UNSAT ******* |
| | |
| | 1) NOTE: PLEASE CLARIFY SERVICE AS SHOWN |
| | AS SOME ITEMS ARE SHOWN AS EXISTING AND |
| | SOME OTHER ITEMS DO NOT INDICATE BEING |
| | EXISTING. IT IS BEING TAKEN THAT THESE |
| | ITEMS ARE NEW. |
| | PLEASE SEE NEW SYSTEMS INVOLVING |
| | 277/480V SYSTEMS SHALL BE SIGNED, DATED |
| | AND SEALED BY A PE. |
| | 471.003 (2)(H). |
| | |
| | 2) NOTE: PLEASE SEE RISER SHOWS A GUTTER |
| | IN THE LOAD SIDE OF THE TRANSFORMER |
| | WHICH VIOLATES THE NEC 240.21. THIS IS |
| | SHOWING TAPPED CONDUCTORS BEING FED FROM |
| | OTHER TAPPED CONDUCTORS. THIS IS NOT |
| | PERMITTED , AND IF THIS IS EXISTING, |
| | THIS WILL BE REQUIRED TO BE CORRECTED. |
| | PLEASE KNOW, THE TAPPED CONDUCTORS ON |
| | THE SEC SIDE OF THE TRANSFORMER SHALL |
| | TERMINATE IN A SINGLE MEANS OF OCP WHEN |
| | USING THE 10FTRULE ETC. |
| | PLEASE ADJUST RISER. |
| | |
| | 3) NOTE: PLEASE INCLUDE ALL EQUIPMENT |
| | GROUNDING CONDUCTORS AS REQUIRED. |
| | 250.110,250.24B , 250.122 |
| | |
| | 4) NOTE: PLEASE INDICATE THE GROUNDING |
| | ATTACHEMENT FOR THE TRANSFORMER. |
| | 250.66,250.30, 250.50 |
| | |
| | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 6) NOTE: PLEASE SEE THAT ALL CURRENT |
| | CODES AS FOLLOWS SHALL BE STATED ON |
| | PLANS/DESIGN. |
| | NFPA-70,2002, NFPA-101 2003, NFPA-72 |
| | 2002. |
| | |
| | 7) NOTE: PLEASE SEE PLANS ARE NOTED AS |
| | MEETING THE NEW FLORIDA ENERGY CODE, |
| | HOWEVER NO ITEMS COULD BE LOCATED ON |
| | PLANS TO VERIFY THIS. |
| | PLEASE SEE 2004 FBC |
| | 13-415.1.ABC.1.1,.1.2,.1.3. |
| | PLEASE SEE 13-415.1.AB.1, |
| | 13-415.2.ABC.1. |
| | PLEASE SEE EXCEPTIONS FOR MEDICAL AREAS |
| | FOR PROCEDURES ETC. |
| | |
| | PLEASE PROVIDE THE TIME OF DAY |
| | SCHEDULING, DEVICES, DEVICE LOCATIONS, |
| | OVER-RIDES AND LOCATIONS. PLEASE SPECIFY |
| | THE AMOUNT OF TIME(MAX) ON DEVICE(S) |
| | USED FOR OVER RIDES IN SPACES ETC. |
| | **PLEASE KNOW THE DEVICE(S) CAN BE |
| | LISTED ON THE ELECTRICAL DEVICE LEGEND |
| | AND NOTED ACCORDINGLY. |
| | |
| | 8) NOTE: PLEASE CLARIFY LOCATIONS OF ALL |
| | ELECTRICAL EQUIPMENT, AS PANELS ARE |
| | SHOWN ON PLANS, HOWEVER NOT CLEAR WHERE |
| | TRANSFORMER AND TWO OTHER DISCONNECTS |
| | ARE ?? |
| | 215.5,110.26, ETC |
| | |
| | 9) NOTE: PLEASE CLARIFY TITLE BLOCKS ON |
| | PLANS, AS PLANS INDICATE THE FIRM, |
| | ARCHITECT ALONG WITH THE SAME FIRM AND |
| | ARCHITECTS LICENSE NUMBER AND CA #, |
| | HOWEVER PLEASE SEE TITLE BLOCKS ALSO |
| | INCLUDE WHAT APPEAR TO BE A NAME OF |
| | ANOTHER "ARCHITECTURAL FIRM". THESE ARE |
| | STATED AS "ALIEN ARCHITECTURE"?? |
| | PLEASE CLARIFY, AS THIS DOES NOT SEEM TO |
| | PART OF THE TITLE BLOCK FOR SAID FIRM |
| | LISTED?? |
| | FAC 61G1-16.004, FS 481.219 |
| | |
| | ** IMPORTANT** |
| | WHEN AND BEFORE RESUBMITTING PLANS ONCE |
| | ALL REVIEWS ARE DONE. PLEASE COMPLETELY |
| | REMOVE ALL OLD/VOIDED SHEETS AND ONLY |
| | INSERT ANY OF THE NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE SUBMIT ONLY ONE COPY OF THE |
| | OLD/REMOVED VOIDED SHEETS FOR REFERENCE |
| | ONLY. THESE WILL BE SEPARATE FROM NEW |
| | SETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |