Plan Review Notes
Plan Review Notes For Permit 06061338
Permit Number 06061338
Review Stop B
Sequence Number 1
Notes
Date Text
2006-07-10 00:00:00 
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) 61G15-23.002 SEAL, SIGNATURE AND DATE
 SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL
 PLANS, SPECIFICATIONS, REPORTS, FINAL
 BID DOCUMENTS PROVIDED TO THE OWNER OR
 THE OWNER'S REPRESENTATIVE, OR OTHER
 DOCUMENTS PREPARED OR ISSUED BY SAID
 REGISTRANT AND BEING FILED FOR
 PUBLIC RECORD. THE DATE THAT THE
 SIGNATURE AND SEAL IS AFFIXED AS
 PROVIDED HEREIN SHALL BE ENTERED ON SAID
 PLANS, SPECIFICATIONS,
 REPORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER.
 (2) EACH SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE
 PROVISIONS OF CHAPTER 471, F.S., SHALL
 BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE
 CHARGE. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET.
  
 3) NFPA 99C5.1.3.3.2
 DESIGN AND CONSTRUCTION. LOCATIONS FOR
 CENTRAL SUPPLY SYSTEMS AND THE STORAGE
 OF POSITIVE PRESSURE GASES SHALL MEET
 THE FOLLOWING REQUIREMENTS:
 (1)BE CONSTRUCTED WITH ACCESS TO
 MOVE CYLINDERS, EQUIPMENT, AND SO FORTH,
 IN AND OUT OF THE LOCATION ON HAND
 TRUCKS COMPLYING WITH 9.5.3.1.1
 (2)BE SECURED WITH LOCKABLE DOORS OR
 GATES OR OTHERWISE SECURED
 (3)IF OUTDOORS, BE PROVIDED WITH AN
 ENCLOSURE (WALL OR FENCING) CONSTRUCTED
 OF NONCOMBUSTIBLE MATERIALS
 (4)IF INDOORS, BE CONSTRUCTED AND
 USE INTERIOR FINISHES OF NONCOMBUSTIBLE
 OR LIMITED-COMBUSTIBLE MATERIALS SUCH
 THAT ALL WALLS, FLOORS, CEILINGS AND
 DOORS ARE OF A MINIMUM 1-HOUR FIRE
 RESISTANCE RATING
  
 4) CONSTRUCTION. CARTS AND HAND TRUCKS
 FOR CYLINDERS AND CONTAINERS SHALL BE
 APPROPRIATE CONSTRUCTED FOR THE INTENDED
 PURPOSE, BE SELF-SUPPORTING, AND BE
 PROVIDED WITH 9.5.3.1.1 CHAINS OR STAYS
 TO RETAIN CYLINDERS OR CONTAINERS
  
 5) A.5.1.3.3.2 ELECTRIC WIRING AND
 EQUIPMENT IN STORAGE ROOMS FOR OXYGEN
 AND NITROUS OXIDE ARE NOT REQUIRED TO BE
 EXPLOSION PROOF.
  
 6) A.5.1.3.4 SEE FIGURE A.5.1.3.4. A
 FOUR-VALVE BYPASS ARRANGEMENT IS
 ILLUSTRATED. THREE-WAY VALVES ARE
 PERMITTED IN LIEU OF THE FOUR VALVES
 SHOWN.
  
 7) 11-7.2 SALES AND SERVICE COUNTERS ,
 TELLER WINDOWS, INFORMATION COUNTERS.
 (2) AT TICKETING COUNTERS , TELLER
 STATIONS IN A BANK, REGISTRATION
 COUNTERS IN HOTELS AND MOTELS, BOX
 OFFICE TICKET COUNTERS , AND OTHER
 COUNTERS THAT MAY NOT HAVE A CASH
 REGISTER BUT AT WHICH GOODS OR SERVICES
 ARE SOLD OR DISTRIBUTED, EITHER:
 (I) A PORTION OF THE MAIN COUNTER WHICH
 IS A MINIMUM OF 36 INCHES (915 MM) IN
 LENGTH SHALL BE PROVIDED WITH A MAXIMUM
 HEIGHT OF 36 INCHES (915 MM);
  
 8)2004 EXISTING BUILDING CODE 605.2 THE
 MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF THIS SECTION.
 EXCEPTIONS:
 1. WHERE THE WORK AREA AND THE MEANS OF
 EGRESS SERVING IT COMPLIES WITH THE
 FLORIDA FIRE PREVENTION CODE .
 2. MEANS OF EGRESS CONFORMING TO THE
 REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING AND THE FLORIDA FIRE
 PREVENTION CODE UNDER WHICH THE BUILDING
 WAS CONSTRUCTED SHALL BE CONSIDERED
 COMPLIANT MEANS OF EGRESS IF, IN THE
 OPINION OF THE CODE OFFICIAL, THEY DO
 NOT CONSTITUTE A DISTINCT HAZARD TO
 LIFE. {EXIT
 STAIRWAYS,CHUTES,JANITORCLOSETS, GUEST
 ROOMS, SERVICE ROOMS, ETC., SHALL NOT
 OPEN INTO THE ELEVATOR LOBBY.1982
 STANDARD BUILDING CODE SEC.506.6 (1)}
  
 9)11-4.13.6 MANEUVERING CLEARANCES AT
 DOORS . MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIGURE 11-25 . THE FLOOR OR GROUND AREA
 WITHIN THE REQUIRED CLEARANCES SHALL BE
 LEVEL AND CLEAR. SEE SHEET A-3 WHERE
 CABINETS ARE INCROUCHING ON THE MINIMUM
 OF 18" ON THE PULL-SIDE OF THE DOORS.
  
 10) SEE FBC SEC.435.3/435.4 AND 435.5
 FOR THE REQUIREMENTS OF RADIATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  