| 2006-07-10 00:00:00 | |
| | 1) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 2) 61G15-23.002 SEAL, SIGNATURE AND DATE |
| | SHALL BE AFFIXED. |
| | (1) A PROFESSIONAL ENGINEER SHALL SIGN |
| | HIS NAME AND AFFIX HIS SEAL TO ALL |
| | PLANS, SPECIFICATIONS, REPORTS, FINAL |
| | BID DOCUMENTS PROVIDED TO THE OWNER OR |
| | THE OWNER'S REPRESENTATIVE, OR OTHER |
| | DOCUMENTS PREPARED OR ISSUED BY SAID |
| | REGISTRANT AND BEING FILED FOR |
| | PUBLIC RECORD. THE DATE THAT THE |
| | SIGNATURE AND SEAL IS AFFIXED AS |
| | PROVIDED HEREIN SHALL BE ENTERED ON SAID |
| | PLANS, SPECIFICATIONS, |
| | REPORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL |
| | ENGINEER. |
| | (2) EACH SHEET OF PLANS AND PRINTS |
| | WHICH MUST BE SEALED UNDER THE |
| | PROVISIONS OF CHAPTER 471, F.S., SHALL |
| | BE SEALED, SIGNED AND DATED BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE |
| | CHARGE. ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME, ADDRESS, |
| | AND LICENSE NUMBER ON EACH SHEET. |
| | |
| | 3) NFPA 99C5.1.3.3.2 |
| | DESIGN AND CONSTRUCTION. LOCATIONS FOR |
| | CENTRAL SUPPLY SYSTEMS AND THE STORAGE |
| | OF POSITIVE PRESSURE GASES SHALL MEET |
| | THE FOLLOWING REQUIREMENTS: |
| | (1)BE CONSTRUCTED WITH ACCESS TO |
| | MOVE CYLINDERS, EQUIPMENT, AND SO FORTH, |
| | IN AND OUT OF THE LOCATION ON HAND |
| | TRUCKS COMPLYING WITH 9.5.3.1.1 |
| | (2)BE SECURED WITH LOCKABLE DOORS OR |
| | GATES OR OTHERWISE SECURED |
| | (3)IF OUTDOORS, BE PROVIDED WITH AN |
| | ENCLOSURE (WALL OR FENCING) CONSTRUCTED |
| | OF NONCOMBUSTIBLE MATERIALS |
| | (4)IF INDOORS, BE CONSTRUCTED AND |
| | USE INTERIOR FINISHES OF NONCOMBUSTIBLE |
| | OR LIMITED-COMBUSTIBLE MATERIALS SUCH |
| | THAT ALL WALLS, FLOORS, CEILINGS AND |
| | DOORS ARE OF A MINIMUM 1-HOUR FIRE |
| | RESISTANCE RATING |
| | |
| | 4) CONSTRUCTION. CARTS AND HAND TRUCKS |
| | FOR CYLINDERS AND CONTAINERS SHALL BE |
| | APPROPRIATE CONSTRUCTED FOR THE INTENDED |
| | PURPOSE, BE SELF-SUPPORTING, AND BE |
| | PROVIDED WITH 9.5.3.1.1 CHAINS OR STAYS |
| | TO RETAIN CYLINDERS OR CONTAINERS |
| | |
| | 5) A.5.1.3.3.2 ELECTRIC WIRING AND |
| | EQUIPMENT IN STORAGE ROOMS FOR OXYGEN |
| | AND NITROUS OXIDE ARE NOT REQUIRED TO BE |
| | EXPLOSION PROOF. |
| | |
| | 6) A.5.1.3.4 SEE FIGURE A.5.1.3.4. A |
| | FOUR-VALVE BYPASS ARRANGEMENT IS |
| | ILLUSTRATED. THREE-WAY VALVES ARE |
| | PERMITTED IN LIEU OF THE FOUR VALVES |
| | SHOWN. |
| | |
| | 7) 11-7.2 SALES AND SERVICE COUNTERS , |
| | TELLER WINDOWS, INFORMATION COUNTERS. |
| | (2) AT TICKETING COUNTERS , TELLER |
| | STATIONS IN A BANK, REGISTRATION |
| | COUNTERS IN HOTELS AND MOTELS, BOX |
| | OFFICE TICKET COUNTERS , AND OTHER |
| | COUNTERS THAT MAY NOT HAVE A CASH |
| | REGISTER BUT AT WHICH GOODS OR SERVICES |
| | ARE SOLD OR DISTRIBUTED, EITHER: |
| | (I) A PORTION OF THE MAIN COUNTER WHICH |
| | IS A MINIMUM OF 36 INCHES (915 MM) IN |
| | LENGTH SHALL BE PROVIDED WITH A MAXIMUM |
| | HEIGHT OF 36 INCHES (915 MM); |
| | |
| | 8)2004 EXISTING BUILDING CODE 605.2 THE |
| | MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THIS SECTION. |
| | EXCEPTIONS: |
| | 1. WHERE THE WORK AREA AND THE MEANS OF |
| | EGRESS SERVING IT COMPLIES WITH THE |
| | FLORIDA FIRE PREVENTION CODE . |
| | 2. MEANS OF EGRESS CONFORMING TO THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING |
| | CODE, BUILDING AND THE FLORIDA FIRE |
| | PREVENTION CODE UNDER WHICH THE BUILDING |
| | WAS CONSTRUCTED SHALL BE CONSIDERED |
| | COMPLIANT MEANS OF EGRESS IF, IN THE |
| | OPINION OF THE CODE OFFICIAL, THEY DO |
| | NOT CONSTITUTE A DISTINCT HAZARD TO |
| | LIFE. {EXIT |
| | STAIRWAYS,CHUTES,JANITORCLOSETS, GUEST |
| | ROOMS, SERVICE ROOMS, ETC., SHALL NOT |
| | OPEN INTO THE ELEVATOR LOBBY.1982 |
| | STANDARD BUILDING CODE SEC.506.6 (1)} |
| | |
| | 9)11-4.13.6 MANEUVERING CLEARANCES AT |
| | DOORS . MINIMUM MANEUVERING CLEARANCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIGURE 11-25 . THE FLOOR OR GROUND AREA |
| | WITHIN THE REQUIRED CLEARANCES SHALL BE |
| | LEVEL AND CLEAR. SEE SHEET A-3 WHERE |
| | CABINETS ARE INCROUCHING ON THE MINIMUM |
| | OF 18" ON THE PULL-SIDE OF THE DOORS. |
| | |
| | 10) SEE FBC SEC.435.3/435.4 AND 435.5 |
| | FOR THE REQUIREMENTS OF RADIATION. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL:(561)805-6726 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |