Plan Review Notes
Plan Review Notes For Permit 06061294
Permit Number 06061294
Review Stop B
Sequence Number 1
Notes
Date Text
2006-07-07 00:00:00 
  
 ****CORRECTIONS****
  
 MRYRON JACOBS, BUILDING PLANS EXAMINER
 561-805-6726 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED
 ITEMS APPLY
  
  
  
 _XX___1.PROVIDE BUILDING HEIGHT ON
 THE PLAN.DESIGN PRESSURES FOR
 BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND
 MUST BE DONE BY AN ENGINEER. DOCUMENTS
 PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED
 SEALED ORIGINALS FAC61G15-23.002.
  
 __XX__2.PROVIDE A COPY OF THE CONDO
 ASSOCIATION APPROVAL IF NECESSARY.
  
 ____3.COMPLETE THE ATTACHED
 INSTALLATION SCHEDULE OR PROVIDE
 REQUIRED INFORMATION IN A SIMILAR
 FORMAT.YOU NEED TO SHOW ANCHOR SPACING
 BY CIRCLING IT ON THE APPROPRIATE CHARTS
 ON THE PRODUCT APPROVAL.PLEASE USE INK
 RATHER THAN HIGHLIGHTER.
  
 ____4.FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72,
 WWW.FLORIDABUILDING.ORG.
  
 _XX___5.ON THE PRODUCT APPROVAL,
 MARK WHICH DETAILS APPLY TO THIS JOB.
 PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 _XX___6.SHOW THE EMERGENCY MEANS OF
 ESCAPE, FBC R310.
  
 _XX___7.PROVIDE A FLOOR PLAN SHOWING
 WHERE THE SHUTTERS WILL BE INSTALLED AND
 PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 4 ABOVE.
  
 8) THE DESIGN PRESSURE CALCULATION
 SHALL BE DESIGN TO MEET WIND SPEED OF
 140MPH NOT 85MPH. THE PRESSURES GIVEN
 ARE TO LOW FOR THIS AREA.
  
  
 ******SUBMIT A COMPLETED
 INSTALLATION SCHEDULE WITH ALL
 REQUIRED INFORMATION, SAMPLE
 ATTACHED***
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL(561)805-6726
  
  
  
  