| 2006-06-27 00:00:00 | ***DENIED*** | | | | | | 1) BATTERY ROOM SHALL REMAIN LOCKED WHEN | | | NOT OCCUPIED. | | | | | | 2) PLEASE INDICATE DOOR SWING. DOORS TO | | | BATTERY ROOMS SHALL OPEN OUTWARD, AND BE | | | EQUIPPED WITH QUICK OPENING HARDWARE. | | | | | | 3) EMERGENCY EXITS, AND EMERGENCY | | | LIGHTING IS REQUIRED. | | | | | | 4) ACCESS TO MULTI-PURPOSE FIRE | | | EXTINGUISHER(S) SHALL BE PROVIDED. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|