Plan Review Notes
Plan Review Notes For Permit 06061286
Permit Number 06061286
Review Stop M
Sequence Number 1
Notes
Date Text
2006-08-21 00:00:00DENIED:DIESEL GENERATOR
  
 1.PLEASE PROVIDE SITE PLAN.INDICATE
 LOCATION OF THE DIESEL GENERATOR.SHOW
 DISTANCES/CLEARANCES FROM THE PROPERTY
 LINES, BUILDING, FRESH AIR INTAKES,
 WINDOWS, DOORS, LOUVERS, ETC.
  
 2.PROVIDE ANCHORING DETAIL.
  
 3.PROVIDE SUBMITTAL DETAIL OF THE
 GENERATOR WITH RESPECT TO FUEL SUPPLY,
 SHUT OF VALVES, VENTS, ETC.
  
 4.INDICATE PROTECTION FROM DAMAGE IF
 REQUIRED PER 2004 FMC 303.4
  
 5.DIESEL GENERATORS SHALL COMPLY WITH
 NFPA 110 & CHAPTER 13 OF THE 2004 FMC.
  