| Plan Review Notes For Permit 06061286 |
| Permit Number |
06061286 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-18 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE CLARIFY SIZE AND LOCATION OF | | | FUEL TANK AS PLANS AND SPEC SHEETS | | | INDICATE DIFFERENT GALLON AMOUNTS. | | | | | | 2) PLEASE PROVIDE SITE PLAN INDICATING | | | LOCATION OF GENERATOR AND FUEL TANK | | | ILLUSTRATING DIMENSIONS TO BUILDING | | | OPENINGS AND PROPERTY LINES. | | | | | | 3) WHEN REFERENCING CODES, PLEASE | | | INCLUDE THE ADOPTED EDITIONS, NFPA 101 | | | 2003, NFPA 110 2002, ETC. | | | | | | 4) IF THE POSSIBILITY OF MECHANICAL | | | DAMAGE EXISTS, PLEASE ILLUSTRATE | | | SAFEGUARDS ON PLANS. IF NOT, PLEASE | | | ADVISE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|