| 2006-07-07 00:00:00 | ***** UNSAT ****** |
| | |
| | 1) NOTE: PLEASE KNOW, PLANS ARE NOT |
| | COMPLETE AT THIS TIME FOR SUFFICIENT |
| | REVIEW FOR CODE COMPLIANCE. |
| | PLEASE SEE TWO DIFFERENT SIZES OF ATS |
| | ARE NOTED ON PLANS. |
| | PLEASE SEE NO PLANS SUBMITTED FOR |
| | LOCATIONS OF EQUIPMENT, NO SITE PLANS, |
| | NO DETAIL FOR MOUNTING, NO AIC RATINGS, |
| | CURRENT CODES IN EFFECT NOT SHOWN, PLANS |
| | ARE NOT SIGNED, DATED OR SEALEDETC |
| | ETC. |
| | PLEASE SEE FS 471.003, FS 471.025 |
| | PLEASE SEE NEC. |
| | PLEASE SEE NFPA-70 2002, NFPA-110 2002, |
| | NFPA-101 2003, FBC 2004 ETC |
| | PLEASE SEE COMMENTS AND CODES FROM OTHER |
| | TRADES FOR CURRENT CODE RELEVANT TO EACH |
| | TRADE. |
| | |
| | 2) NOTE: PLEASE SEE VALUE SHALL INCLUDE |
| | ALL LABOR AND MATERIRALS, EVEN IF ANY |
| | EQUIPMENT IS OWNER SUPPLIED. PLEASE |
| | KNOW, THE VALUE MAY BE ADJUSTED BY THIS |
| | OFFICE PER MARSHAL'S/ SWIFT GUIDE. |
| | FBC 108.3 ADMIN SECT. |
| | |
| | 3) NOTE: PLEASE SEE PLANS NOTE A |
| | SEPARATELY DERIVED SYSTEM, YET ATS IS |
| | 3-POLE. THIS WOULD REQUIRE 4-POLE PLEASE |
| | VERIFY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |