2006-08-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06061286
 ADD: 1000 36TH ST
 CONT: BROWN & BROWN ELEC
 TEL: (561)703-9569
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) THE ADDRESS ON THE PERMIT APPLICATION
 AND PLANS DO NOT CORRELATE, PLEASE
 CORRECT.
  
 4) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 5) PLEASE PROVIDE THE LOCATION OF SAID
 GENERATOR ON THE PROPERTY.VENTING MAY BE
 AN ISSUE.
 PROVIDE PLANS ENOUGH TO VERIFY LOCATION
 OF GENERATOR VERSES BUILDING OPENINGS
 WINDOWS, DOORS OR SOFFIT TYPE VENTS,
 ETC.
  
 MECHANICAL CODE
 804.3.4 HORIZONTAL TERMINATIONS.
 HORIZONTAL TERMINATIONS SHALL COMPLY
 WITH THE FOLLOWING REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO
 WALKWAYS, THE TERMINATION OF MECHANICAL
 DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3
 FEET (914 MM) ABOVE ANY FORCED AIR INLET
 LOCATED WITHIN 10 FEET (3048 MM).
 3.THE VENT SYSTEM SHALL TERMINATE
 AT LEAST 4 FEET (1219 MM) BELOW, 4 FEET
 (1219 MM) HORIZONTALLY FROM OR 1 FOOT
 (305 MM) ABOVE ANY DOOR, WINDOW OR
 GRAVITY AIR INLET INTO THE BUILDING.
 4.THE VENT TERMINATION POINT SHALL
 NOT BE LOCATED CLOSER THAN 3 FEET (914
 MM) TO AN INTERIOR CORNER FORMED BY TWO
 WALLS PERPENDICULAR TO EACH OTHER.
 5.THE VENT TERMINATION SHALL NOT BE
 MOUNTED DIRECTLY ABOVE OR WITHIN 3 FEET
 (914 MM) HORIZONTALLY FROM AN OIL TANK
 VENT OR GAS METER.
 6.THE BOTTOM OF THE VENT
 TERMINATION SHALL BE LOCATED AT LEAST 12
 INCHES (305 MM) ABOVE FINISHED GRADE.
  
 804.3.5 VERTICAL TERMINATIONS.
 VERTICAL TERMINATIONS SHALL COMPLY WITH
 THE FOLLOWING REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO
 WALKWAYS, THE TERMINATION OF MECHANICAL
 DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3
 FEET (914 MM) ABOVE ANY FORCED AIR INLET
 LOCATED WITHIN 10 FEET (3048 MM).
 3.WHERE THE VENT TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF
 STRUCTURE, THE TERMINATION POINT SHALL
 BE LOCATED AT LEAST 3 FEET (914 MM) FROM
 SUCH STRUCTURE.
 4.THE VENT SHALL TERMINATE AT LEAST
 4 FEET (1219 MM) BELOW, 4 FEET (1219 MM)
 HORIZONTALLY FROM, OR 1 FOOT (305 MM)
 ABOVE ANY DOOR, WINDOW OR GRAVITY AIR
 INLET FOR THE BUILDING.
 5.A VENT CAP SHALL BE INSTALLED TO
 PREVENT RAIN FROM ENTERING THE VENT
 SYSTEM.
 6.THE VENT TERMINATION SHALL BE
 LOCATED AT LEAST 3 FEET (914 MM)
 HORIZONTALLY FROM ANY PORTION OF THE
 ROOF STRUCTURE.
  
 501.2 OUTDOOR DISCHARGE.
  
 THE AIR REMOVED BY EVERY MECHANICAL
 EXHAUST SYSTEM SHALL BE DISCHARGED
 OUTDOORS AT A POINT WHERE IT WILL NOT
 CAUSE A NUISANCE AND FROM WHICH IT
 CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM. AIR SHALL NOT BE
 EXHAUSTED INTO AN ATTIC OR CRAWL SPACE
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
 401.5 OPENING LOCATION.
 OUTDOOR AIR EXHAUST AND INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET
 (3048 MM) FROM LOT LINES OR BUILDINGS ON
 THE SAME LOT. WHERE OPENINGS FRONT ON A
 STREET OR PUBLIC WAY, THE DISTANCE SHALL
 BE MEASURED TO THE CENTERLINE OF THE
 STREET OR PUBLIC WAY.