Plan Review Notes
Plan Review Notes For Permit 06061280
Permit Number 06061280
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-27 00:00:00 
 ** UNSAT **
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE PROVIDE A MAIN
 DISCONNECT OUTSIDE WITH OCP TO MEET
 230.70.
  
 3) NOTE: PLEASE INCLUDE CWP AS PART OF
 THE GE SYSTEM.250.50
  
 4) NOTE: PLEASE INCLUDE THE # OF SEC'S
 AND FEEDERS ON RISER.
  
 5) NOTE: PLEASE INDICATE OF THE PANEL
 INSIDE WILL BE MLO, OR MCB?
  
 6) NOTE: PLEASE ALSO SHOW OR NOTE
 LOCATION OF PANEL IN KITCHEN AS PANEL
 WILL BE REQUIRED TO MEET 110.26, 408.7
 EVEN IF AN EXISTING LOCATION.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  