| Plan Review Notes For Permit 06061271 |
| Permit Number |
06061271 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-27 00:00:00 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE PROVIDE AN ELECTRICAL | | | RISER DIAGRAM SHOWING THE NEW PROPOSED | | | CONDUCTORS FROM METER TO EXISTING MAINS. | | | PLEASE INCDICATE IF THE EXISTING MAIN IS | | | LOCATED OUTSIDE AND THE SIZE FO THE | | | EXISTING OCP AT MAIN. | | | PLEASE INCLUDE THE NEW GROUNDING | | | ELECTRODE SYSTEM ON RISER. 2-MIN GRND | | | RODS, CWP,. | | | 215.5,250.50,310.16,240.4 | | | | | | | | | 2) NOTE: PLEASE BE SURE THE RISER | | | CONTAINS THE PRINTED NAME AND SIGNATURE | | | OF THE PERSONRESPONSIBLE FOR | | | PLAN/DESIGN. | | | FBC 106.1.2 ADMIN SEC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|