Plan Review Notes
Plan Review Notes For Permit 06061271
Permit Number 06061271
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-27 00:00:00** UNSAT **
  
 1) NOTE: PLEASE PROVIDE AN ELECTRICAL
 RISER DIAGRAM SHOWING THE NEW PROPOSED
 CONDUCTORS FROM METER TO EXISTING MAINS.
 PLEASE INCDICATE IF THE EXISTING MAIN IS
 LOCATED OUTSIDE AND THE SIZE FO THE
 EXISTING OCP AT MAIN.
 PLEASE INCLUDE THE NEW GROUNDING
 ELECTRODE SYSTEM ON RISER. 2-MIN GRND
 RODS, CWP,.
 215.5,250.50,310.16,240.4
  
  
 2) NOTE: PLEASE BE SURE THE RISER
 CONTAINS THE PRINTED NAME AND SIGNATURE
 OF THE PERSONRESPONSIBLE FOR
 PLAN/DESIGN.
 FBC 106.1.2 ADMIN SEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  