Plan Review Notes
Plan Review Notes For Permit 06061268
Permit Number 06061268
Review Stop E
Sequence Number 2
Notes
Date Text
2006-10-15 19:55:50******** UNSAT 2ND REVIEW *******
  
 ** PLEASE NOTE(S) FROM PREVIOUS WHICH ARE STILL IN NEED
 OF ADDRESSING AND SOME NEW NOTES DUE TO PLANS
 SUBMITTED.
 NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS REVIEW
 WITH NEW NOTES ADDED TO LOWER PORTION.
  
 1) NOTE: OK. VERIFIED.
  
 2) NOTE: OK.
  
 3) NOTE: NO, PLEASE SEE PLANS DO NOT SEEM TO INDICATE
 ALL ELECTRICAL IN ROOM, LTS ETC. PLEASE SEEMIN SIZE
 OF LOADS FOR CIRCUITS.
 PLEASE SEE NEC 645 FOR ALL REQUIREMENTS. PLEASE ALSO
 SEE NFPA-75 FOR ANY CONSTRUCTION METHODS ALONG WIHT
 MECHNICAL WHERE APPLICABLE).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE PLANS AND PLANS
 SEE NFPA-70 645 AND NFPA-75 FOR
 REQUIREMENTS IN "IT" RMS.
 PLEASE PROVIDE COMPLETED INFORMATION FOR
 REVIEW.
  
 4) NOTE:NO, NONE SUBMITTED FOR REVIEW.
 110.3, 90.7
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR NEW EQUIPMENT BEING INSTALLED.
 110.3, 90.7
  
 5) NOTE:NO, NO ADJUSTMENT WAS MADE. PLEASE KNOW, IF
 ONE IS NOT ADJUSTED TO SCOPEOF WORK , ONE WILL BE
 ASSESSED AS REQUIRED UDENR THE FBC AND MARSHALL'S &
 SWIFT GUIDE AS ADOPTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE VALUE SHALL INCLUDE
 ALL LABOR AND MATERIRALS, EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED. PLEASE
 KNOW, THE VALUE MAY BE ADJUSTED BY THIS
 OFFICE PER MARSHAL'S/ SWIFT GUIDE.
 FBC 108.3 ADMIN SECT.
  
  
 ** NEW NOTE **
  
  
 6) NOTE: PLEASE SEE FAC 61G15-23.002 AND FLORIDA
 STATUES 471.025, AS ALL SIGNATURES BY THE DESIGN
 PROFESSIONALS SHALL BE ORIGINAL. "RUBBER STAMPS" AND/OR
 "PHOTO-COPIED" SIGNATURES WITH A RAISED SEAL DOES NOT
 MAKE THE PLANS/ DOCUMNETS VALID. PLEASE KNOW, AS PLANS
 SUBMITTED DO NOT CONTAIN ORIGINAL SIGNATURE(S) FROM
 MORE THAN ONE DESIGNER INCLUDING COVER SHEET , ONE SET
 OF PLANS ARE BEING RETAINED BY THIS OFFICE AT THIS
 TIME. PLEASE CONTACT THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS OF THERE ARE ANY QUESTIONS, OR THIS OFFICE.
 PLANS MAY BE PROCESSED TO THE BOARD.
 PLEASE ADDRESS.
  
 7) NOTE: PLEASE ALSO SEE FS553.80(2)(B) WITH REPSECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE ON PLANS. THIS IS
 ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  