Plan Review Notes
Plan Review Notes For Permit 06061252
Permit Number 06061252
Review Stop E
Sequence Number 4
Notes
Date Text
2007-01-31 14:39:17*
2007-01-31 14:35:44GENERATOR SUBMITTALS IN PACKAGE ARE TO BE GIVEN BACK TO
 OWNER AS THE GEN SCOPE OF WORK IS EXISTING.
 THE GENERATOR/ATS IS TO HAVE CONTACTS FOR LOAD SHEDDING
 OF THE HEAT STRIP ON THE AHU AS THE GEN IS NOT RATED
 FOR LOAD OF HEAT ALSO. THIS NOTE WAS HIGH-LIGHTED ON
 PLANS.
  
 PLANS STAMPED AND ROUTED TO BUILDING