| Plan Review Notes For Permit 06061252 |
| Permit Number |
06061252 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-01-31 14:39:17 | * | | 2007-01-31 14:35:44 | GENERATOR SUBMITTALS IN PACKAGE ARE TO BE GIVEN BACK TO | | | OWNER AS THE GEN SCOPE OF WORK IS EXISTING. | | | THE GENERATOR/ATS IS TO HAVE CONTACTS FOR LOAD SHEDDING | | | OF THE HEAT STRIP ON THE AHU AS THE GEN IS NOT RATED | | | FOR LOAD OF HEAT ALSO. THIS NOTE WAS HIGH-LIGHTED ON | | | PLANS. | | | | | | PLANS STAMPED AND ROUTED TO BUILDING |
|