Plan Review Notes
Plan Review Notes For Permit 06061252
Permit Number 06061252
Review Stop E
Sequence Number 3
Notes
Date Text
2006-12-25 09:34:59*** UNSET 3RD REVIEW ***
  
 ** PLEASE SEE THERE ARE COMMENTS FROM BOTH PREVIOUS
 REVIEWS WHICH STILL ARE IN NEED OF ADDRESSING. PLEASE
 SEE SOME ARE FROM THE FIRST REVIEW AND SOME ARE FROM
 THE SECOND REVIEW AS THE ELECTRICAL RISER HAD
 COMPLETELY CHANGED FROM THE INITIAL REVIEW.
  
 ** PLEASE KNOW THAT THIS REVIEW WILL ALSO BRING NEW
 COMMENTS AS RISER AND SOME INFORMATION HAS CHANGED ONCE
 AGAIN FROM THE PREVIOUS TWO SETS OF PLANS SUBMITTED FOR
 REVIEW. THESE COMMENTS ARE BEING NOTED BACK TO PREVIOUS
 REVIEW IN MOST CASES.
  
 ** PLEASE SEE NOTE BELOW WHICH REFERENCE BACK TO THE
 TWO PREVIOUS REVIEWS AND THE NUMERICAL IDENTIFICATION
 OF EACH NOTE WHICH HAS BEEN REPEATED FORM THE FIRST AND
 SECOND REVIEW. SOME ONLY REFERENCE TO NOTES FROM THE
 SECOND REVIEW AS THE SECOND REVIEW CONTAINED NUMEROUS
 NEW NOTES BASED ON THE CHANGES MADE TO PLANS.
  
 1) NOTE: PLEASE SEE SOME AREAS OF PLANS WHICH ARE
 MISSING RECEPTACLES PER 210.52. THESE WERE REDLINED ON
 BOTH SETS OF THE PREVIOUS SUBMITTED PLANS FOR
 LOCATIONS, HOWEVER NOT ALL OF THOSE REDLINED AREAS WERE
 DONE.
 PLEASE SEE THE 2FT, 6FT, AND 12FT RULE.
 PREVIOUS REVIEW(S)
  
 2) NOTE: PLEASE SEE NOTE #10 FROM THE PREVIOUS TWO
 REVIEWS WHICH SEEMED TO BE ADDRESS BY THE ADDITION OF
 THE SA /SMOKE ALARM DEVICES, HOWEVER SEE SYMBOL LEGEND
 FOR THESE ADDED DEVICES WHICH INDICATES THESE AS WALL
 MOUNTED CLOSET FIXTURES?
 PLEASE CORRELATE SYMBOL LEGEND WITH THE ACTUAL DEVICE
 BEING INSTALLED.
 PREVIOUS REVIEW(S) NOTE #10
  
 3) NOTE: PLEASE PROVIDE ROOM AND AREA DESIGNATIONS ON
 PLANS FOR ALL ROOMS.
 FBC 106.1.2. (ON ELECTRICAL SHEETS)
 PREVIOUS REVIEW(S) NOTE #11
  
 4) NOTE: PLEASE SEE CLOSET LIGHTS EVEN AS SHOWN MOUNTED
 ABOVE CLOSET DOORS DO NOT SEEM TO MEET 410.8. PLEASE
 SEE THIS SECTION 410.8 D(1) AS INCANDESCENT FIXTURES
 REQUIRE A GREATER CLEARANCE THAN FLUORESCENT. PLEASE
 SEE SYMBOL LEGEND FOR THIS TYPE OF FIXTURE SHOWS
 INCANDESCENT AND PER SCALE ON PLANS AND THE FIXTURE
 BEING MOUNTED OFF THE WALL WOULD PLACE THESE WITH IN
 12" OF SHELVING.
 PLEASE ALSO SEE SYMBOL LEGEND AND FIXTURE SCHEDULE NEED
 TO CORRELATE. PLEASE SEE THE SAME SYMBOL AS BEING SHOWN
 AS A WALL MOUNTED FIXTURE IS ALSO SHOWN AS CEILING
 MOUNTED.
 PREVIOUS REVIEW(S) NOTE #12
  
 5) NOTE: PLEASE SEE LOAD CALCULATIONS FOR SERVICE STILL
 DO NOT INDICATE THE DEDICATED JACUZZI CIRCUIT.
 PLEASE SEE THE LOAD ON PANEL SCHEDULE DOES NOT
 CORRELATE WITH THE KVA SHOWN ON PANEL SCHEDULE.
 PREVIOUS REVIEW(S) NOTE #13
  
 6) NOTE: PLEASE SEE MISSING EITHER EXISTING OR NEW COLD
 WATER PIPE AS PART OF THE GROUNDING ELECTRODE SYSTEM.
 THESE PLANS NOW INDICATE ALL AS EXISTING EXCEPT FOR A
 NEW NOTE FOR THE REQUIRED FOOTER STEEL AND A NEW DETAIL
 FOR STRUCTURAL STEEL COLUMNS.
 (MISSING CWP). 250.50
 PREVIOUS REVIEW(S) NOTE #14
  
 7) NOTE: PLEASE SEE CORRELATE OF THE A/C SYSTEMS IS
 STILL NOT DONE. PLEASE SEE WHAT IS BEING SHOWN IN LOAD
 CALCULATIONS AND THE LOADS ON PANEL SCHEDULES ARE
 DIFFERENT. PLEASE SEE 424.3B FOR MINIMUM SIZING OF THE
 OVER CURRENT PROTECTION DEVICES. PLEASE CORRELATE
 PANELS AS ONE SHOWS 5600 AS EXISTING AND LOAD
 CALCULATIONS INDICATE 11,200 AS EXISTING FOR THE SAME
 UNIT. PLANS SHOW 5KW, PLANS ALSO SHOW THREE CONDENSING
 UNITS?
 PLEASE SEE LOADS FOR THE NEW ARE ALSO NOT BEING DONE ON
 EMERGENCY SUB PANEL CORRECTLY. PLEASE SEE OTHER
 COMMENTS FOR THIS.
 PREVIOUS REVIEW(S) NOTE #16 AND NOTE #36
 FBC 106.1.2 ADMIN SECTION. PLEASE CORRELATE ALL.
  
 8) NOTE: PLEASE SEE 220.31B FOR REQUIRED LOAD
 CALCULATIONS. PLEASE SEE THERE ARE STILL SEVERAL ITEMS
 NOT INCLUDED ON THE MAIN HOUSE LOAD SUMMARY WHICH ARE
 SHOWN ON PANEL SCHEDULES.
 PLEASE SEE MISSING DINING ROOM, JACUZZI, CORRECT A/C
 (?), DISHWASHER, DISPOSAL ETC.
 PLEASE KNOW IT IS REQUIRED TO CONTAIN THE LOAD
 CALCULATIONS FOR EACH PANEL AND THEN THOSE LOADS SHALL
 CORRELATE WITH THE MAIN PANEL SCHEDULE FOR EACH
 INDIVIDUAL LOAD ON EACH PANEL. THE MAIN LOAD SUMMARY
 SHALL INCLUDE ALL LOADS WITH THE PERMITTED DE-RATINGS
 AS PERMITTED PER THE CODE SECTION ABOVE AS GIVEN.
 PLEASE SEE LOADS ON PANELS SHOWN IN KVA DO NOT
 CORRELATE WITH WHAT APPEARS TO BE AMPERAGES?
 PLEASE SEE THE 2002 NEC.
 PREVIOUS REVIEW(S) NOTE #17 AND NOTE #20, #36, #37,
 #40
  
 9) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 WITH
 RESPECT TO DINING ROOM CIRCUIT. PLEASE SEE LOAD
 CALCULATIONS NOTE ABOVE WHICH MENTIONS THIS AS ONE OF
 THE CIRCUITS NOT LISTED.
 PREVIOUS REVIEW(S) NOTE # 19
  
 10) NOTE: PLEASE IDENTIFY ALL SERVICE EQUIPMENT FOR
 WHICH IS EXISTING AND WHICH IS NEW. THE EM PANEL IS NOW
 THE ONLY PANEL WHICH IS DARKENED AS BEING NEW, HOWEVER
 PLEASE SEE AS ATTACHED PLANS AND PERMIT FOR GENERATOR
 PERMIT INDICATES THIS PANEL ALREADY DONE UNDER A
 SEPARATE PERMIT.
 PLEASE IDENTIFY NEW AND EXISTING.
 FBC 106.1.2 ADMIN SECTION.
 PREVIOUS REVIEW(S) NOTE #23 AND #24
  
 11) NOTE: PLEASE SEE MISSING THE CIRCUITING AND ARC
 FAULT PROTECTION INDICATION FOR THE SMOKE ALARMS AS
 REQUIRED PER 210.12.
 PREVIOUS REVIEW(S) NOTE #26 AND #38
  
 12) NOTE: PLEASE KNOW UNTIL A CORRECTED LOAD
 CALCULATION CAN BE SUBMITTED FOR REVIEW, THE SIZE OF
 THE SERVICE, SERVICE ENTRANCE CONDUCTORS, GROUNDING
 ELECTRODE AND OTHER ITEMS CAN NOT BE DONE AT THIS
 TIME.
 PREVIOUS REVIEW NOTE(S). #28, 29, 30, 31, 34ETC.
  
 13) NOTE: PLEASE SEE AHU AND OVER CURRENT PROTECTION IS
 STILL BEING SHOWN IN CLOSET FOR AHU WHICH IS NOT
 PERMITTED.
 PREVIOUS REVIEW NOTE #33
  
 14) NOTE: PLEASE SEE PREVIOUS NOTES ABOVE AND NOTE #35,
 # 37 FROM PREVIOUS REVIEW WHICH REQUESTED FOR
 CORRELATION OF THE EXISTING GENERATOR PERMIT AND PLANS
 WITH THE PLANS CURRENTLY BEING SUBMITTED. PLEASE SEE
 THE LOAD ON THE EMERGENCY PANEL FAR EXCEEDS THAT OF THE
 RATING OF THE GENERATOR. PLEASE SEE AS THE GENERATOR
 RATED LOAD UNDER PROPANE AND NATURAL GAS ARE TWO
 RATINGS. PLEASE SEE THAT IN EITHER CASE, THE LOAD ON
 THE GENERATOR EXCEEDS RATING OF UNIT. PLEASE SEE THE
 CALCULATIONS SUBMITTED UNDER THE GENERATOR PERMIT DOES
 NOT CONTAIN ALL THE LOADS NOW SHOWN ON THIS EM PANEL
 SCHEDULE.
 PLEASE PROVIDE DETAILED LOAD SHEDDING DETAILS FOR SOME
 LOADS WHICH MAY BE REMOVED BY MEANS OF CONTROL DEVICES,
 AND/ OR DELETE LOADS.
 702.5, 220.31
 PLEASE SEE THE CONDUCTORS FROM THE GENERATOR ON THESE
 PLANS DO NOT CORRELATE WITH THE CONDUCTORS ON GENERATOR
 PLANS. THIS UNIT IS NOT RATED FOR 100A'S.
 PLEASE SEE COMMENTS ABOVE WITH RESPECT TO CORRELATION
 OF LOAD CALCULATIONS.
 PLEASE SEE PREVIOUS REVIEW NOTE #35
 ** PLEASE KNOW ON A SIDE NOTE, ALL PLANS, PERMIT AND SO
 FORTH FROM WHAT SHOULD REMAIN ON JOBSITE WAS SUBMITTED
 WITH THIS PERMIT APPLICATION PACKAGE. PLEASE DO NOT
 SUBMIT, AS THESE SHOULD REMAIN IN THE POSSESSION OF THE
 OWNER ON THE PROPERTY AT ALL TIMES. WE CONTAIN RECORDS
 OF THESE AS THIS IS HOW I CAME UP WITH THE COMMENTS FOR
 THE GENERATOR PLANS AND LOADS NOT MATCHING.
  
 15) NOTE: PLEASE SEE ON THE PREVIOUS REVIEW NOTE #42, A
 NOTICE WAS GIVEN TO THE DESIGN PROFESSIONAL WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE WITH
 RESPECT TO FLORIDA STATUTES 553.80(2)(B).
 PLEASE KNOW BASED ON THIS THE THIRD REVIEW WITH SEVERAL
 COMMENTS STILL BEING NOTED FOR THE SAME CODES
 COMPLIANCE ISSUES, THIS OFFICE HAS NOW ASSESSED A 4X
 TIMES FOR THE PLAN REVIEW PORTION OF THE BASE PERMIT
 FEE. THIS FEE OF $2,400.00 IS ASSESSED TO THE DESIGNER
 OF RECORD AND IS NOT THE RESPONSIBILITY OF THE
 OWNER/CONTRACTOR.
 PLEASE KNOW ONE SET OF ELECTRICAL PLANS WILL BE
 RETAINED ONCE AGAIN FOR FILE CREATED.
 PLEASE ALSO KNOW TO DATE NO CONTACT HAS BEEN MADE TO
 THIS REVIEWER FOR ANY QUESTIONS OR COMMENTS REGARDING
 THE TWO PREVIOUS REVIEWS.
 PLEASE KNOW THIS FEE WILL BE REQUIRED TO BE PAID BEFORE
 PLANS CAN BE RESUBMITTED AS REQUIRED UNDER THE FS AS
 NOTED.
  
 16) NOTE: PLEASE SEE AS NOTED AT THE END OF PREVIOUS
 REVIEWS AND ** WITH ** IMPORTANT*, REQUESTED ALL
 OLD/VOIDED SHEETS TO BE REMOVED FROM SETS AND ONLY TO
 INSERT NEW REVISED SHEETS INTO TWO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 THE ONLY SHEET WHICH SHOULD BE KEPT AND PLACED ON THE
 COVE OF EACH SET FOR REFERENCE SHOULD BE THE SHEET
 CONTAINING THE STAMP FROM PALM BEACH COUNTY FOR IMPACT
 FEES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
2006-12-25 08:07:532006-12-25 08:07:53
 IN PROGRESS
2006-12-24 20:02:382006-12-24 20:02:38
 TO CONTINUE, REVIEW STOPPED. NOTES TO FOLLOW ONCE
 REVIEW IS COMPLETED ON 12/25.
2006-12-24 19:14:04IN ELEC FOR REVIEW