| Plan Review Notes For Permit 06061252 |
| Permit Number |
06061252 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-11-03 14:35:00 | *** DENIED *** | | | 1) THE ARCHITECT NEED TO PUT THE DATE WHEN HE SIGNED | | | THE PLANS, PER FAC 61G-16.003. | | | | | | 2) MANUAL J CALCULATIONS WILL NEED TO BE FOR THE WHOLE | | | HOUSE, AS THE NEW A/C SYSTEM IS SERVICING HALF OF THE | | | EXISTING HOUSE THAT WAS SERVICED BY THE EXISTING A/C | | | SYSTEM, AND NOW THE EXISTING A/C SYSTEM MAY BE OVER | | | SIZED FOR JUST TWO ROOMS. ALSO PLEASE SUBMIT ALL | | | INFORMATION ON THE EXISTING A/C SYSTEM. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|