Plan Review Notes
Plan Review Notes For Permit 06061252
Permit Number 06061252
Review Stop E
Sequence Number 2
Notes
Date Text
2006-11-03 11:19:19********* UNSAT 2ND REVIEW***********
  
  
 ** PLEASE SEE MANY COMMENTS FROM PREVIOUS REVIEW WHICH
 STILL NEED TO BE ADDRESSED AND MANY NEW COMMENTS DUE TO
 COMPLETE CHANGE IN ELECTRICAL RISER DIAGRAM, PANEL
 SCHEDULES AND PLANS SUBMITTED.
  
 ** PLEASE SEE COMMENTS BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW AND WHETHER OR NOT THEY WERE ADDRESSED.
 PLEASE SEE COMPLETELY NEW COMMENTS ADDED TO THE BOTTOM
 OF THE REVIEW.
  
 1) NOTE: NO, SAME NOTE, PLEASE SEE ONCE AGAIN REDLINED
 AREAS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING RECEPTS PER 210.52. 2',6' ,12' RULE
 ALL WALL SPACES FOR NEW AREAS AND NEW CONVERTED AREAS
 WHICH USED TO BE THE KITCHEN.
  
 2) NOTE:NO, PLEASE ALSO SEE COMMENTS WITH RESPECT
 CIRCUITING AS SHOWN ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING EITHER EXISTING OR NEW DINING RM
 DEDICATED CIRCUIT REQUIRED. PLEASE SEE 210.52B1,
 210.11C1, 220.16 ON ONE OR MORE OF THE SM APPL
 CIRCUITS.
 ** PLEASE SEE THE DINING ROOM MAY NOT BE CIRCUITED TO
 THE GARAGE AS NOTED ON PANEL SCHEDULE. (THIS WOULD BE
 OK, ONLY FOR LIGHTING CIR).
  
 3) NOTE: NO, PLEASE STILL SEE MOST HAVE BEEN ADDED
 HOWEVER NOT ALL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING GFI RECEPT SPACING ALONG MANY AREAS
 OF THE KITCHEN COUNTER SPACES.
 210.52C1
  
 4) NOTE:OK, NOW SHOWN, HOWEVER SEE NEW COMMENTS WITH
 RESPECT TO THE LOCATION(S) NOT MEETING CODE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING LOCATION OF NEW AHU FOR ADDITION.
 PLEASE SHOW LOCATION AND PLEASE ALSO SEE 440.11 FOR
 MISSING DISCONNECTS FOR BOTH THE AHU AND CU.
  
 5) NOTE: OK.
  
 6) NOTE: NO, PLEASE SEE THIS IS THE SAME COMMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING NEW OR EXISTING REAR RECEPT PER
 210.52E (GFI PER 210.8A)
  
 7) NOTE:NO, SAME NOTE.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING GFI RECEPT FOR NEW BATH RM OFF THE
 GARAGE.
 210.52D, 210.11C3
  
 8) NOTE:OK, HOWEVER GFI DESIGNATION IS NOT CLEAR?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY NEW OR EXISTING GARAGE GFI.
 210.52G, 210.8A
  
 9) NOTE:NO, PLEASE SEE NOTE ABOVE FOR MISSING.
  
 ** PREVIOUS REVIEW NOTE A**
 PLEASE SEE MISSING REQUIRED DEDICATED BATH(S) RM
 CIRCUITS(S). 210.52D,210.11C3.
  
 10) NOTE:NO, PLEASE SEE SA DEVICES ARE REQUIRED
 WITHIN 12" OFTHE HIGHEST POINT ON A FLAT CEILING.
 PLEASE SEE MASTER BEDRM. AN EXACT ARCHITECTURAL REVIEW
 OF THETRAY CEILING DETAIL WAS NOT DONE, HOWEVER
 PLEASE BE SURE THIS SA IS EITHER MOVED IN FIELD OR
 NOTED ON PLANS TO MEET 11.8.3 NFPA-72 2002.
 PLEASE SEE NEW NOTE FOR CIRCUITING AND AFCI.
  
 ** PREVIOUS REVIEW NOTE:PLEASE SEE MISSING SMOKE ALARM
 REQUIRED IN NEW AND EXISTING DWELLING PER NFPA-72
 11.5.1.1,11.8.3
 PLEASE SEE THESE SHALL ALL BE HARDWIRED INLINE AND ARC
 FAULT PROTECTED PER
 210.12B
 PLEASE SEE SA IN MASTER BEDRM SHALL BE INSTALLED WITHIN
 3' OF THE HIGHEST POINT OF THE SLOPED CEILING OR 12" OF
 THE FLAT CEILING AREA IF A TRAY/FLAT AREA.
  
 11) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ALL ROOM AND AREA DESIGNATIONS ON
 PLANS.
 106.1.2 FBC ADMIN SECT.
  
 12) NOTE: NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MIN CLEARANCES DO NOT SEEM TO BE MET FOR
 NEW CLOSET LTS PER 410.8
  
 13) NOTE: OK, HOWEVER SEE COMMENT WITH RESPECT TOP LOAD
 CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS APPEAR TO SHOW A "JACUZZI/SPA TUB" YET
 PANEL SCHEDULE AND LOAD CALCULATIONS DO NOT INDICATE
 EITHER??
 PLEASE ALSO INDICATE THE REQUIRED GFI PROTECTION.
 680.71, 106.1.2 FBC ADMIN SECT.
  
 14) NOTE:NO, PLEASE SEE SYSTEM IS NOT SHOWN AT ALL.
 PLEASE ALSO SEE NEW NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 250.50, AS THE NEW FOOTER STEEL IS REQUIRED
 TO PART OF THE GROUNDING ELECTRODE SYSTEM.
  
 15) NOTE: NO, PLEASE SEE NEW COMMENTS AS A COMPLETELY
 NEW SERVICE RISER IS NOW SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER INDICATES "CURRENT SERVICE", THIS IS
 TAKEN AS EXISTING SERVICE, YET THE PANEL SCHEDULE IS
 NOTED AS BEING THE "PROPOSED" PANEL?
 IS THIS EXISTING OR NEW?
 PLEASE CLARIFY.
  
 16) NOTE:NO, PLEASE SEE MIN OCP FOR AHU(S) NOT
 CORRECT. PLEASE SEE PREVIOUS REVIEWNOTE AND PLEASE
 SEE NEW NOTES FOR OTHER COMMENTS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER ONLY SEEMS TO BE SHOWING ONE A/C
 SYSTEM?
 PLEASE ALSO SEE THE FOLLOWING COMMENTS.
 PLEASE SEE NOTE ON PANEL SCHEDULE MENTIONS 1-5KW AND
 1-10KW, HOWEVER PANEL SCHEDULE SHOWS 10KW UNITS.
 PANEL ALSO SHOWS "4-SPACES"??
 PLEASE CLARIFY THIS. PLEASE SEPARATE THESE OF THE
 "4-SPACES" IS FOR TWO SEPARATE A/C AHU'S.
 PLEASE ALSO SEE THAT THE OCP FOR THE AHU'S SHALL BE
 SIZED AT A MIN OF 125%.
 PLEASE SEE AHU'S ARE SHOWN W/ 40A OCP.
 PLEASE SEE 424.3B, 240.4, 310.16, 440.11 ETC.
  
 17) NOTE:NO, NOT DONE. PLEASE SEE CALCULATIONS
 SUBMITTED ARE NOT CODE COMPLIANT.
 THERE ARE FAR TOO MANY INDIVIDUAL ITEMS TO BE MENTIONED
 IN DETAIL FOR COMPLIANCE. PLEASE SEE 220.31B.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 220.31B, 220.21 FOR MIN LOAD CALCULATIONS
 FOR SERVICE.
 PLEASE ALSO SEE MIN LOADS FOR A/C SYSTEM SHALL BE
 SHOWN. PLEASE SEE THE LARGER OF THE TWO LOADS SHALL BE
 INDICATED IN LOADS CALCS. LOADS SHOWN DO NOT CORRELATE
 WITH EITHER THE NOTE FOR ONE 5KW AND ONE-10KW OR THE
 TWO 10KW UNITS AS NOTED ON PANEL SCHEDULE.
 PLEASE ADJUST AND REVISE CALCULATIONS.
  
 18) NOTE: NO, SAME NOTE **
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE LOAD CALCULATIONS MENTIONS 2-RANGES, YET
 PLANS DO NOT CORRELATE WITH THIS?
 PLEASE SEE PLANS INDICATE ONE RANGE AND AN "OVEN"?
 PLEASE SEE PANEL SCHEDULE DOES NOT SHOW OVEN.
 PLEASE VERIFY ALL KW LOADS, OCP AND CIRCUITS.
 408.4, 240.4, 310.16 ETC
  
 19) NOTE: NO, PLEASE SEE MINIMUM OF "2" ARE REQUIRED.
 PLEASE ALSO SEE COMMENTS WITH RESPECT DINING RM
 CIRCUIT(S) FROM PREVIOUS REVIEW. OK, FOR SM APPL ONLY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.52B1, 210.11C1, 220.16A FOR MIN 1500VA
 FOR SM APPL CIRCUITS.
 (PLANS SHOW 1400).
  
 20) NOTE: NO, SEE OTHER NOTES FOR LOAD CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE DEDICATED DISHWASHER IS SHOWN ON LOAD
 CALCS, YET NOT ON PANEL SCHEDULE.
 PLEASE SEE DISPOSAL(S) ON PANEL SCHEDULE, HOWEVER NOT
 IN LOAD CALCS.?
 PLEASE SEE OTHER WHICH ARE NOT LISTED.
 PLEASE BE SURE TO GO THROUGH ALL CIRCUITS ON THE HOUSE
 PANEL NEW AND EXISTING, LIST IN LOAD CALCULATIONS, AND
 SHOW ON PANEL SCHEDULE AND ADJUST LOAD CALCULATIONS
 ACCORDINGLY.
 215.5, 220.31B, ETC.
  
 21) NOTE: OK, HOWEVER AS PANEL SCHEDULE(S) ARE NOT
 COMPLETE ATE THIS TIME, PLEASE BE SURE TO THE SAME WHEN
 OTHER ITEMS ARE ADDED TO PANEL SCHEDULE(S).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL SCHEDULE SHALL INDICATE ALL CONDUCTOR
 SIZES PER 310.16, 240.4, 215.5, 408.4 ETC
 FBC 106.1.2, ADMIN SECT
  
 22) NOTE: OK. SEE NEW NOTES.
  
 23) NOTE: ? SEE NEW NOTES AS A COMPLETELY NEW RISER WAS
 SUBMITTED AND THIS PREVIOUS NOTE WOULD NO LONGER APPLY.
 NO CONDUCTORS ARE SHOWN?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER SHOWS AN "EQUIPMENT GROUNDING
 CONDUCTOR FROM METER TO THE MAIN?? IT IS NOTED THAT
 THIS IS EXISTING; HOWEVER THE #8 SHOULD NOT BE LOCATED
 IN THIS SEGMENT OF THE SEC'S. PLEASE SEE 250.6,
 240.24B, AS THIS CREATES "OBJECTIONABLE CURRENT" BY
 PARALLELING THE NEUTRAL.
 PLEASE KNOW, "IF" THIS CONDUCTOR IS INSTALLED, EVEN IF
 EXISTING, THIS MUST BE REMOVED.
 PLEASE BE SURE THIS IS THERE AS NOTED ON RISER BEFORE
 REVISING AND RESUBMITTING PLANS.
  
 24) NOTE: NO/ OK, PLEASE SEE THE SERVICE IS NOW SHOWN
 HOWEVER IT IS NO LONGER SHOWN AS EXISTING AND PLEASE
 SEE COMPLETE SET OF NEW COMMENTS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW THE LOCATION OF THE EXISTING SERVICE.
 215.5, 240.24B, 408.7 ETC
  
 25) NOTE:NO, SAME NOTE .
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 680.22B1 FOR MIN CLEARANCES FOR LIGHTING
 FIXTURES FROM POOL. PLEASE SEE LTS ETC AS SHOWN DO NOT
 MEET THE MIN DISTANCES REQUIRED FOR THE NEW ADDITION.
 PLEASE SEE SCONCES SHOWN ARE EVEN CLOSER WHICH WILL
 ALSO NOT BE PERMITTED.
  
 26) NOTE: OK/ NO, PLEASE SEE NOT ALL ARE SHOWN, HOWEVER
 SEE NEW NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE LIST ALL THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS PER 2002
 NEC 210.12B
  
  
 ***** NEW NOTES 2ND REVIEW **********
  
 27) NOTE: PLEASE SEE A COMPLETELY NEW RISER IS BEING
 SHOWN AND SUBMITTED. PLEASE SEE THIS SERVICE IS BEING
 SHOWN BUT NOT CLEAR WHAT, HOW OR WHERE THIS SERVICE IS
 MOUNTED AS NO BUILDING OR STRUCTURE IS SHOWN.
 PLEASE ALSO SEE LOCATION AS SHOWN PLACES SERVICE CLOSER
 THAN 3 FT FROM PROPERTY LINE WHICH WOULD NOT GIVE THE
 PERMITTED CLEARANCES PER 110.26
  
 28) NOTE: PLEASE COMPLETE RISER WITH ALL SEC?S, FROM
 METER TO MAIN.
 310.15B6, 310.16, 240.4 , 230,42 ETC.
  
 29) NOTE: PLEASE SEE RISER MENTIONS TO SEE PANEL
 SCHEDULE FOR GROUNDING ELECTRODE CONDUCTOR, HOWEVER
 THIS WAS NOT LOCATED. PLEASE SEE SERVICE IS NOW BEING
 SHOWN AS 300A'S, AND NO NEW GEC IS SHOWN.
  
 30) NOTE: PLEASE ALSO SEE 310.15B6, 250.66 FOR SIZING
 OF THE NEW GEC, MIN PER 250.66 WOULD BE #2.
  
 31) NOTE: PLEASE SEE FEEDERS FROM MAIN TO PANEL "LA" ,
 AND OCP F.24B, 250.110,OR NEW PANEL. PLEASE INDICATE
 THE CORRECT SIZE FOR THE EQUIPMENT GROUNDING CONDUCTOR
 WHICH IS BASED ON THE OCP AND PER 250.122.
 250
  
 32) NOTE: PLEASE CORRELATE RISER AND PANEL LA, AS ONE
 SHOWS MCB AND THE OTHER MLO.
 FBC ADMIN SECT 106.1.2
  
 33) NOTE: PLEASE SEE NOW THAT AHU'S ARE ALL SHOWN
 PLEASE SEE 424.3B (AS PREVIOUSLY NOTED ), HOWEVER MOST
 IMPORTANT, PLEASE SEE 240.24D AND 110.26 AS THIS SHALL
 NOT BE LOCATED ON CLOTHES CLOSET AS SHOWN.
  
 34) NOTE: PLEASE SUBMIT AND COORDINATE AIC RATINGS FOR
 ALL SERVICE EQUIPMENT.
 110.9, 240.12.
 SHOWN FOR SOME, HOWEVER NOT ALL.
  
 35) NOTE: PLEASE SEE THIS PLAN IS NOW SHOWING A
 GENERATOR WHICH WAS NOT ON PREVIOUS PLANS. PLEASE ALSO
 KNOW THE EXISTING PERMIT/PLANS FOR THE INSTALLATION OF
 A GENERATOR DOES NOT CORRELATE WITH THESE PLANS
 SUBMITTED. THEGEN/ ATS/ RISER/ SITE / PRIMEMOVER ETC
 ARE ALL DIFFERENT ON THE GEN PERMIT.
  
 PLEASE KNOW AS SHOWN ON THIS RISER THIS IS NOT
 PERMITTED.
 PLEASE SUBMIT ALL OF THE MANUFACTURES SPECS AND CUT
 SHEETS ON THE EQUIPMENT NOW BEING PROPOSED ON THIS
 RISER WHICH DOES NOT CORRELATE WITH GEN PERMIT.
 UNABLE TO REVIEW FOR CODE COMPLIANCE AT THIS TIME.
 225.31, 90.7, 110.3.
 PLEASE COMPLETE AND CORRELATE RISER AS SHOWN. PLEASE
 KNOW, IF INDEED SERVICE IS BEING INCREASED A COMPLETE
 REVISION TO THE GEN PERMIT WILL BE REQUIRED.
 FBC ADMIN SECT 106.1.2, NEC 2002.
  
 36) NOTE: PLEASE SEE WITH THE NEW CALCULATIONS AS SHOWN
 FOR AHU, PLEASE CORRELATE THE 11KW, 10KW, AND AMPERAGE
 AS SHOWN.
 PLEASE SEE HOW COULD 10KW AND 5KW MAKE 11.2KVA? PLEASE
 SEE ALSO PERVIOUSNOTES FOR OCP ETC.
 220.31B, 220.21, 424 ETC THERE ARE MANY ARTICLES WHICH
 COULD BE REFERENCED, HOWEVER PLEASE CORRELATE.
  
 37)NOTE: PLEASE CORRELATE LOAD ON EM PANEL AS SHOWN
 AS 8.5A'S WHERE KW RATING AND LOAD IS SUBSTANTIALLY
 HIGHER.
 215.5, 220 ETC.
  
 38) NOTE: PLEASE SEE MISSING CIRCUITING FOR SA'S (
 SMOKE ALARMS). PLEASE ALSO SEE 210.12B FOR REQUIRED
 PROTECTION.
  
 39) NOTE: PLEASE SEE NEC 210.11C2, 220.16 FOR MIN VA
 FOR LAUNDRY AND WASHERCIRCUIT.
  
 40) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS A "A" AND "C"
 PHASE YET THIS IS AND SHOULD BE "A" AND "B" PHASE.
 PLEASE ALSO SEE THE AMPERAGE'S AS SHOWN ON PANEL
 SCHEDULE(S) DO NOT SEEM TO CORRELATE WITH THE KVA/ KW
 LOADS AS SHOWN??
 UNABLE TO VERIFY MANY ITEMS.
 215.5,220.31B,310.16,240.4 ETC
  
 41) NOTE: PLEASE SEE 220.3B (4) RECESSED LUMINAIRES
 (LIGHTING FIXTURES). AN OUTLET SUPPLYING RECESSED
 LUMINAIRE(S) [LIGHTING FIXTURE(S)] SHALL BE COMPUTED
 BASED ON THE MAXIMUM VOLT-AMPERE RATING OF THE
 EQUIPMENT AND LAMPS FOR WHICH THE LUMINAIRE(S)
 [FIXTURE(S)] IS RATED.
 PLEASE LIST ON THE FIXTURE SCHEDULE THE FIXTURE AND THE
 MAX WATTAGE PER FIXTURE AS SHOWN.
 PLEASE ADJUST AND INCLUDE INTO THE LOAD CALCULATIONS.
 THESE ARE NOT PART OF THE GEN LTS, AS THEY EXCEED THE
 NORMAL AMOUNT FOR GEN LTS.
  
 42) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 THE DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE. THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 PLEASE KNOWONE COPY OF EACH OF THE ELECTRICALPLANS
 ARE BEING RETAINED AT THIS TIME.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
  
  
 ** PLEASE KNOW DUE TO THE EXTENT OF COMMENTS; PLEASE BE
 SURE TO SEE ONE REDLINED SET AS MANY OF THE ABOVE ITEMS
 WERE "REDLINED". THIS IS IN NO WAY ALL POSSIBLE
 LOCATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
  
 561-805-6717
 [email protected]
  