| 2006-11-03 11:19:19 | ********* UNSAT 2ND REVIEW*********** |
| | |
| | |
| | ** PLEASE SEE MANY COMMENTS FROM PREVIOUS REVIEW WHICH |
| | STILL NEED TO BE ADDRESSED AND MANY NEW COMMENTS DUE TO |
| | COMPLETE CHANGE IN ELECTRICAL RISER DIAGRAM, PANEL |
| | SCHEDULES AND PLANS SUBMITTED. |
| | |
| | ** PLEASE SEE COMMENTS BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW AND WHETHER OR NOT THEY WERE ADDRESSED. |
| | PLEASE SEE COMPLETELY NEW COMMENTS ADDED TO THE BOTTOM |
| | OF THE REVIEW. |
| | |
| | 1) NOTE: NO, SAME NOTE, PLEASE SEE ONCE AGAIN REDLINED |
| | AREAS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING RECEPTS PER 210.52. 2',6' ,12' RULE |
| | ALL WALL SPACES FOR NEW AREAS AND NEW CONVERTED AREAS |
| | WHICH USED TO BE THE KITCHEN. |
| | |
| | 2) NOTE:NO, PLEASE ALSO SEE COMMENTS WITH RESPECT |
| | CIRCUITING AS SHOWN ON PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING EITHER EXISTING OR NEW DINING RM |
| | DEDICATED CIRCUIT REQUIRED. PLEASE SEE 210.52B1, |
| | 210.11C1, 220.16 ON ONE OR MORE OF THE SM APPL |
| | CIRCUITS. |
| | ** PLEASE SEE THE DINING ROOM MAY NOT BE CIRCUITED TO |
| | THE GARAGE AS NOTED ON PANEL SCHEDULE. (THIS WOULD BE |
| | OK, ONLY FOR LIGHTING CIR). |
| | |
| | 3) NOTE: NO, PLEASE STILL SEE MOST HAVE BEEN ADDED |
| | HOWEVER NOT ALL. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING GFI RECEPT SPACING ALONG MANY AREAS |
| | OF THE KITCHEN COUNTER SPACES. |
| | 210.52C1 |
| | |
| | 4) NOTE:OK, NOW SHOWN, HOWEVER SEE NEW COMMENTS WITH |
| | RESPECT TO THE LOCATION(S) NOT MEETING CODE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING LOCATION OF NEW AHU FOR ADDITION. |
| | PLEASE SHOW LOCATION AND PLEASE ALSO SEE 440.11 FOR |
| | MISSING DISCONNECTS FOR BOTH THE AHU AND CU. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: NO, PLEASE SEE THIS IS THE SAME COMMENT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING NEW OR EXISTING REAR RECEPT PER |
| | 210.52E (GFI PER 210.8A) |
| | |
| | 7) NOTE:NO, SAME NOTE. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING GFI RECEPT FOR NEW BATH RM OFF THE |
| | GARAGE. |
| | 210.52D, 210.11C3 |
| | |
| | 8) NOTE:OK, HOWEVER GFI DESIGNATION IS NOT CLEAR? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY NEW OR EXISTING GARAGE GFI. |
| | 210.52G, 210.8A |
| | |
| | 9) NOTE:NO, PLEASE SEE NOTE ABOVE FOR MISSING. |
| | |
| | ** PREVIOUS REVIEW NOTE A** |
| | PLEASE SEE MISSING REQUIRED DEDICATED BATH(S) RM |
| | CIRCUITS(S). 210.52D,210.11C3. |
| | |
| | 10) NOTE:NO, PLEASE SEE SA DEVICES ARE REQUIRED |
| | WITHIN 12" OFTHE HIGHEST POINT ON A FLAT CEILING. |
| | PLEASE SEE MASTER BEDRM. AN EXACT ARCHITECTURAL REVIEW |
| | OF THETRAY CEILING DETAIL WAS NOT DONE, HOWEVER |
| | PLEASE BE SURE THIS SA IS EITHER MOVED IN FIELD OR |
| | NOTED ON PLANS TO MEET 11.8.3 NFPA-72 2002. |
| | PLEASE SEE NEW NOTE FOR CIRCUITING AND AFCI. |
| | |
| | ** PREVIOUS REVIEW NOTE:PLEASE SEE MISSING SMOKE ALARM |
| | REQUIRED IN NEW AND EXISTING DWELLING PER NFPA-72 |
| | 11.5.1.1,11.8.3 |
| | PLEASE SEE THESE SHALL ALL BE HARDWIRED INLINE AND ARC |
| | FAULT PROTECTED PER |
| | 210.12B |
| | PLEASE SEE SA IN MASTER BEDRM SHALL BE INSTALLED WITHIN |
| | 3' OF THE HIGHEST POINT OF THE SLOPED CEILING OR 12" OF |
| | THE FLAT CEILING AREA IF A TRAY/FLAT AREA. |
| | |
| | 11) NOTE:NO, SAME NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE ALL ROOM AND AREA DESIGNATIONS ON |
| | PLANS. |
| | 106.1.2 FBC ADMIN SECT. |
| | |
| | 12) NOTE: NO, SAME NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MIN CLEARANCES DO NOT SEEM TO BE MET FOR |
| | NEW CLOSET LTS PER 410.8 |
| | |
| | 13) NOTE: OK, HOWEVER SEE COMMENT WITH RESPECT TOP LOAD |
| | CALCULATIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS APPEAR TO SHOW A "JACUZZI/SPA TUB" YET |
| | PANEL SCHEDULE AND LOAD CALCULATIONS DO NOT INDICATE |
| | EITHER?? |
| | PLEASE ALSO INDICATE THE REQUIRED GFI PROTECTION. |
| | 680.71, 106.1.2 FBC ADMIN SECT. |
| | |
| | 14) NOTE:NO, PLEASE SEE SYSTEM IS NOT SHOWN AT ALL. |
| | PLEASE ALSO SEE NEW NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 250.50, AS THE NEW FOOTER STEEL IS REQUIRED |
| | TO PART OF THE GROUNDING ELECTRODE SYSTEM. |
| | |
| | 15) NOTE: NO, PLEASE SEE NEW COMMENTS AS A COMPLETELY |
| | NEW SERVICE RISER IS NOW SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE RISER INDICATES "CURRENT SERVICE", THIS IS |
| | TAKEN AS EXISTING SERVICE, YET THE PANEL SCHEDULE IS |
| | NOTED AS BEING THE "PROPOSED" PANEL? |
| | IS THIS EXISTING OR NEW? |
| | PLEASE CLARIFY. |
| | |
| | 16) NOTE:NO, PLEASE SEE MIN OCP FOR AHU(S) NOT |
| | CORRECT. PLEASE SEE PREVIOUS REVIEWNOTE AND PLEASE |
| | SEE NEW NOTES FOR OTHER COMMENTS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE RISER ONLY SEEMS TO BE SHOWING ONE A/C |
| | SYSTEM? |
| | PLEASE ALSO SEE THE FOLLOWING COMMENTS. |
| | PLEASE SEE NOTE ON PANEL SCHEDULE MENTIONS 1-5KW AND |
| | 1-10KW, HOWEVER PANEL SCHEDULE SHOWS 10KW UNITS. |
| | PANEL ALSO SHOWS "4-SPACES"?? |
| | PLEASE CLARIFY THIS. PLEASE SEPARATE THESE OF THE |
| | "4-SPACES" IS FOR TWO SEPARATE A/C AHU'S. |
| | PLEASE ALSO SEE THAT THE OCP FOR THE AHU'S SHALL BE |
| | SIZED AT A MIN OF 125%. |
| | PLEASE SEE AHU'S ARE SHOWN W/ 40A OCP. |
| | PLEASE SEE 424.3B, 240.4, 310.16, 440.11 ETC. |
| | |
| | 17) NOTE:NO, NOT DONE. PLEASE SEE CALCULATIONS |
| | SUBMITTED ARE NOT CODE COMPLIANT. |
| | THERE ARE FAR TOO MANY INDIVIDUAL ITEMS TO BE MENTIONED |
| | IN DETAIL FOR COMPLIANCE. PLEASE SEE 220.31B. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 220.31B, 220.21 FOR MIN LOAD CALCULATIONS |
| | FOR SERVICE. |
| | PLEASE ALSO SEE MIN LOADS FOR A/C SYSTEM SHALL BE |
| | SHOWN. PLEASE SEE THE LARGER OF THE TWO LOADS SHALL BE |
| | INDICATED IN LOADS CALCS. LOADS SHOWN DO NOT CORRELATE |
| | WITH EITHER THE NOTE FOR ONE 5KW AND ONE-10KW OR THE |
| | TWO 10KW UNITS AS NOTED ON PANEL SCHEDULE. |
| | PLEASE ADJUST AND REVISE CALCULATIONS. |
| | |
| | 18) NOTE: NO, SAME NOTE ** |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE LOAD CALCULATIONS MENTIONS 2-RANGES, YET |
| | PLANS DO NOT CORRELATE WITH THIS? |
| | PLEASE SEE PLANS INDICATE ONE RANGE AND AN "OVEN"? |
| | PLEASE SEE PANEL SCHEDULE DOES NOT SHOW OVEN. |
| | PLEASE VERIFY ALL KW LOADS, OCP AND CIRCUITS. |
| | 408.4, 240.4, 310.16 ETC |
| | |
| | 19) NOTE: NO, PLEASE SEE MINIMUM OF "2" ARE REQUIRED. |
| | PLEASE ALSO SEE COMMENTS WITH RESPECT DINING RM |
| | CIRCUIT(S) FROM PREVIOUS REVIEW. OK, FOR SM APPL ONLY. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 210.52B1, 210.11C1, 220.16A FOR MIN 1500VA |
| | FOR SM APPL CIRCUITS. |
| | (PLANS SHOW 1400). |
| | |
| | 20) NOTE: NO, SEE OTHER NOTES FOR LOAD CALCULATIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE DEDICATED DISHWASHER IS SHOWN ON LOAD |
| | CALCS, YET NOT ON PANEL SCHEDULE. |
| | PLEASE SEE DISPOSAL(S) ON PANEL SCHEDULE, HOWEVER NOT |
| | IN LOAD CALCS.? |
| | PLEASE SEE OTHER WHICH ARE NOT LISTED. |
| | PLEASE BE SURE TO GO THROUGH ALL CIRCUITS ON THE HOUSE |
| | PANEL NEW AND EXISTING, LIST IN LOAD CALCULATIONS, AND |
| | SHOW ON PANEL SCHEDULE AND ADJUST LOAD CALCULATIONS |
| | ACCORDINGLY. |
| | 215.5, 220.31B, ETC. |
| | |
| | 21) NOTE: OK, HOWEVER AS PANEL SCHEDULE(S) ARE NOT |
| | COMPLETE ATE THIS TIME, PLEASE BE SURE TO THE SAME WHEN |
| | OTHER ITEMS ARE ADDED TO PANEL SCHEDULE(S). |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PANEL SCHEDULE SHALL INDICATE ALL CONDUCTOR |
| | SIZES PER 310.16, 240.4, 215.5, 408.4 ETC |
| | FBC 106.1.2, ADMIN SECT |
| | |
| | 22) NOTE: OK. SEE NEW NOTES. |
| | |
| | 23) NOTE: ? SEE NEW NOTES AS A COMPLETELY NEW RISER WAS |
| | SUBMITTED AND THIS PREVIOUS NOTE WOULD NO LONGER APPLY. |
| | NO CONDUCTORS ARE SHOWN? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE RISER SHOWS AN "EQUIPMENT GROUNDING |
| | CONDUCTOR FROM METER TO THE MAIN?? IT IS NOTED THAT |
| | THIS IS EXISTING; HOWEVER THE #8 SHOULD NOT BE LOCATED |
| | IN THIS SEGMENT OF THE SEC'S. PLEASE SEE 250.6, |
| | 240.24B, AS THIS CREATES "OBJECTIONABLE CURRENT" BY |
| | PARALLELING THE NEUTRAL. |
| | PLEASE KNOW, "IF" THIS CONDUCTOR IS INSTALLED, EVEN IF |
| | EXISTING, THIS MUST BE REMOVED. |
| | PLEASE BE SURE THIS IS THERE AS NOTED ON RISER BEFORE |
| | REVISING AND RESUBMITTING PLANS. |
| | |
| | 24) NOTE: NO/ OK, PLEASE SEE THE SERVICE IS NOW SHOWN |
| | HOWEVER IT IS NO LONGER SHOWN AS EXISTING AND PLEASE |
| | SEE COMPLETE SET OF NEW COMMENTS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SHOW THE LOCATION OF THE EXISTING SERVICE. |
| | 215.5, 240.24B, 408.7 ETC |
| | |
| | 25) NOTE:NO, SAME NOTE . |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 680.22B1 FOR MIN CLEARANCES FOR LIGHTING |
| | FIXTURES FROM POOL. PLEASE SEE LTS ETC AS SHOWN DO NOT |
| | MEET THE MIN DISTANCES REQUIRED FOR THE NEW ADDITION. |
| | PLEASE SEE SCONCES SHOWN ARE EVEN CLOSER WHICH WILL |
| | ALSO NOT BE PERMITTED. |
| | |
| | 26) NOTE: OK/ NO, PLEASE SEE NOT ALL ARE SHOWN, HOWEVER |
| | SEE NEW NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE LIST ALL THE REQUIRED ARC FAULT PROTECTED |
| | CIRCUITS PER 2002 |
| | NEC 210.12B |
| | |
| | |
| | ***** NEW NOTES 2ND REVIEW ********** |
| | |
| | 27) NOTE: PLEASE SEE A COMPLETELY NEW RISER IS BEING |
| | SHOWN AND SUBMITTED. PLEASE SEE THIS SERVICE IS BEING |
| | SHOWN BUT NOT CLEAR WHAT, HOW OR WHERE THIS SERVICE IS |
| | MOUNTED AS NO BUILDING OR STRUCTURE IS SHOWN. |
| | PLEASE ALSO SEE LOCATION AS SHOWN PLACES SERVICE CLOSER |
| | THAN 3 FT FROM PROPERTY LINE WHICH WOULD NOT GIVE THE |
| | PERMITTED CLEARANCES PER 110.26 |
| | |
| | 28) NOTE: PLEASE COMPLETE RISER WITH ALL SEC?S, FROM |
| | METER TO MAIN. |
| | 310.15B6, 310.16, 240.4 , 230,42 ETC. |
| | |
| | 29) NOTE: PLEASE SEE RISER MENTIONS TO SEE PANEL |
| | SCHEDULE FOR GROUNDING ELECTRODE CONDUCTOR, HOWEVER |
| | THIS WAS NOT LOCATED. PLEASE SEE SERVICE IS NOW BEING |
| | SHOWN AS 300A'S, AND NO NEW GEC IS SHOWN. |
| | |
| | 30) NOTE: PLEASE ALSO SEE 310.15B6, 250.66 FOR SIZING |
| | OF THE NEW GEC, MIN PER 250.66 WOULD BE #2. |
| | |
| | 31) NOTE: PLEASE SEE FEEDERS FROM MAIN TO PANEL "LA" , |
| | AND OCP F.24B, 250.110,OR NEW PANEL. PLEASE INDICATE |
| | THE CORRECT SIZE FOR THE EQUIPMENT GROUNDING CONDUCTOR |
| | WHICH IS BASED ON THE OCP AND PER 250.122. |
| | 250 |
| | |
| | 32) NOTE: PLEASE CORRELATE RISER AND PANEL LA, AS ONE |
| | SHOWS MCB AND THE OTHER MLO. |
| | FBC ADMIN SECT 106.1.2 |
| | |
| | 33) NOTE: PLEASE SEE NOW THAT AHU'S ARE ALL SHOWN |
| | PLEASE SEE 424.3B (AS PREVIOUSLY NOTED ), HOWEVER MOST |
| | IMPORTANT, PLEASE SEE 240.24D AND 110.26 AS THIS SHALL |
| | NOT BE LOCATED ON CLOTHES CLOSET AS SHOWN. |
| | |
| | 34) NOTE: PLEASE SUBMIT AND COORDINATE AIC RATINGS FOR |
| | ALL SERVICE EQUIPMENT. |
| | 110.9, 240.12. |
| | SHOWN FOR SOME, HOWEVER NOT ALL. |
| | |
| | 35) NOTE: PLEASE SEE THIS PLAN IS NOW SHOWING A |
| | GENERATOR WHICH WAS NOT ON PREVIOUS PLANS. PLEASE ALSO |
| | KNOW THE EXISTING PERMIT/PLANS FOR THE INSTALLATION OF |
| | A GENERATOR DOES NOT CORRELATE WITH THESE PLANS |
| | SUBMITTED. THEGEN/ ATS/ RISER/ SITE / PRIMEMOVER ETC |
| | ARE ALL DIFFERENT ON THE GEN PERMIT. |
| | |
| | PLEASE KNOW AS SHOWN ON THIS RISER THIS IS NOT |
| | PERMITTED. |
| | PLEASE SUBMIT ALL OF THE MANUFACTURES SPECS AND CUT |
| | SHEETS ON THE EQUIPMENT NOW BEING PROPOSED ON THIS |
| | RISER WHICH DOES NOT CORRELATE WITH GEN PERMIT. |
| | UNABLE TO REVIEW FOR CODE COMPLIANCE AT THIS TIME. |
| | 225.31, 90.7, 110.3. |
| | PLEASE COMPLETE AND CORRELATE RISER AS SHOWN. PLEASE |
| | KNOW, IF INDEED SERVICE IS BEING INCREASED A COMPLETE |
| | REVISION TO THE GEN PERMIT WILL BE REQUIRED. |
| | FBC ADMIN SECT 106.1.2, NEC 2002. |
| | |
| | 36) NOTE: PLEASE SEE WITH THE NEW CALCULATIONS AS SHOWN |
| | FOR AHU, PLEASE CORRELATE THE 11KW, 10KW, AND AMPERAGE |
| | AS SHOWN. |
| | PLEASE SEE HOW COULD 10KW AND 5KW MAKE 11.2KVA? PLEASE |
| | SEE ALSO PERVIOUSNOTES FOR OCP ETC. |
| | 220.31B, 220.21, 424 ETC THERE ARE MANY ARTICLES WHICH |
| | COULD BE REFERENCED, HOWEVER PLEASE CORRELATE. |
| | |
| | 37)NOTE: PLEASE CORRELATE LOAD ON EM PANEL AS SHOWN |
| | AS 8.5A'S WHERE KW RATING AND LOAD IS SUBSTANTIALLY |
| | HIGHER. |
| | 215.5, 220 ETC. |
| | |
| | 38) NOTE: PLEASE SEE MISSING CIRCUITING FOR SA'S ( |
| | SMOKE ALARMS). PLEASE ALSO SEE 210.12B FOR REQUIRED |
| | PROTECTION. |
| | |
| | 39) NOTE: PLEASE SEE NEC 210.11C2, 220.16 FOR MIN VA |
| | FOR LAUNDRY AND WASHERCIRCUIT. |
| | |
| | 40) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS A "A" AND "C" |
| | PHASE YET THIS IS AND SHOULD BE "A" AND "B" PHASE. |
| | PLEASE ALSO SEE THE AMPERAGE'S AS SHOWN ON PANEL |
| | SCHEDULE(S) DO NOT SEEM TO CORRELATE WITH THE KVA/ KW |
| | LOADS AS SHOWN?? |
| | UNABLE TO VERIFY MANY ITEMS. |
| | 215.5,220.31B,310.16,240.4 ETC |
| | |
| | 41) NOTE: PLEASE SEE 220.3B (4) RECESSED LUMINAIRES |
| | (LIGHTING FIXTURES). AN OUTLET SUPPLYING RECESSED |
| | LUMINAIRE(S) [LIGHTING FIXTURE(S)] SHALL BE COMPUTED |
| | BASED ON THE MAXIMUM VOLT-AMPERE RATING OF THE |
| | EQUIPMENT AND LAMPS FOR WHICH THE LUMINAIRE(S) |
| | [FIXTURE(S)] IS RATED. |
| | PLEASE LIST ON THE FIXTURE SCHEDULE THE FIXTURE AND THE |
| | MAX WATTAGE PER FIXTURE AS SHOWN. |
| | PLEASE ADJUST AND INCLUDE INTO THE LOAD CALCULATIONS. |
| | THESE ARE NOT PART OF THE GEN LTS, AS THEY EXCEED THE |
| | NORMAL AMOUNT FOR GEN LTS. |
| | |
| | 42) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | THE DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE |
| | COMPLIANCE. THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | PLEASE KNOWONE COPY OF EACH OF THE ELECTRICALPLANS |
| | ARE BEING RETAINED AT THIS TIME. |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | |
| | |
| | |
| | ** PLEASE KNOW DUE TO THE EXTENT OF COMMENTS; PLEASE BE |
| | SURE TO SEE ONE REDLINED SET AS MANY OF THE ABOVE ITEMS |
| | WERE "REDLINED". THIS IS IN NO WAY ALL POSSIBLE |
| | LOCATIONS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE TO |
| | CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTRUCTION SERVICES DEPT. |
| | |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2006-11-02 19:15:51 | IN ELEC FROM ZON ON 11/2 |