2006-07-13 00:00:00DENIED;
 1.AUTOMATIC CLOTHES WASHER IS REQUIRED
 TO DISCHARGE DOWN STREAM OF THE BATHROOM
 GROUP. FBC-2004 PLUMBING SEC. 909.1.
 2.AUTOMATIC CLOTHES WASHER BRANCH DRAIN
 IS REQUIRED TO BE 3" SEC. 406.3. SHOW
 CLEANOUT ON WASHER STACK AT 48" ABOVE
 FINISH FLOOR.