Plan Review Notes
Plan Review Notes For Permit 06061252
Permit Number 06061252
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-05 00:00:00********* UNSAT ***********
  
  
 ** PLEASE SEE COMMENTS FROM ZONING
 REVIEW WHICH WILL AFFECT ELECTRICAL
 PLANS AND DESIGN.
  
 1) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52. 2',6'12' RULE ALL WALL SPACES
 FOR NEW AREAS AND NEW CONVERTED AREAS
 WHICH USED TO BE THE KITCHEN.
  
 2) NOTE: PLEASE SEE MISSING EITHER
 EXISTING OR NEW DINING RM DEDICATE
 CIRCUIT REQUIRED. PLEASE SEE 210.52B1,210.11C1,220.16
 ON ONE OR MORE
 OF THE SM APPL CIRCUITS.
 ** PLEASE SEE THE DINING ROOM MAY NOT BE
 CIRCUITED TO THE GARAGE AS NOTED ON
 PANEL SCHEDULE. (THIS WOULD BE OK,ONLY
 FOR LIGHTING CIR).
  
 3) NOTE: PLEASE SEE MISSING GFI RECEPT
 SPACING ALONG MANY AREAS OF THE KITCHEN
 COUNTER SPACES.
 210.52C1
  
 4) NOTE: PLEASE SEE MISSING LOCATION OF
 NEW AHUFOR ADDITION. PLEASE SHOW
 LOCATION AND PLEASE ALSO SEE 440.11 FOR
 MISSING DISCONNECTS FOR BOTH THE AHU AND
 CU.
  
 5) NOTE: PLEASE SEE MISSING GFI RECEPT
 FOR CU.
 210.63, 210.8A
  
 6) NOTE: PLEASE SEE MISSING NEW OR
 EXISTING REAR RECEPT PER 210.52E (GFI
 PER 210.8A)
  
 7) NOTE: PLEASE SEE MISSING GFI RECEPT
 FOR NEW BATH RM OFF THE GARAGE.
 210.52D,210.11C3
  
 8) NOTE: PLEASE CLARIFY NEW OR EXISTING
 GARAGE GFI.
 210.52G, 210.8A
  
 9) NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH(S) RM CIRCUITS(S). 210.52D,210.11C3.
  
 10) NOTE: PLEASE SEE MISSING SMOKE
 DETECTORS REQUIRED IN NEW AND EXISTING
 DWELLING PER NFPA-72 11.5.1.1,11.8.3
 PLEASE SEE THESE SHALL ALL BE HARDWIRED
 INLINE AND ARC FAULT PROTECTED PER
 210.12B
 PLEASE SEE SD IN MASTER BEDRM SHALL BE
 INSTALLED WITHIN 3' OF THE HIGHEST POINT
 OF THE SLOPED CEILING OR 12" OF THE FLAT
 CEILING AREA IF A TRAY/FLAT AREA.
  
 11) NOTE: PLEASE PROVIDE ALL ROOM AND
 AREA DESIGNATIONS ON PLANS.
 106.1.2 FBC ADMIN SECT.
  
 12) NOTE: PLEASE SEE MIN CLEARANCES DO
 NOT SEEM TO BE MET FOR NEW CLOSET LTS.
 PER 410.8
  
 13) NOTE: PLEASE SEE PLANS APPEAR TO
 SHOW A "JACUZZI/SPA TUB" YET PANEL
 SCHEDULE AND LOAD CALCULATIONS DO NOT
 INDICATE EITHER??
 PLEASE ALSO INDICATE THE REQUIRED GFI
 PROTECTION.
 680.71, 106.1.2 FBC ADMIN SECT.
  
 14) NOTE: PLEASE SEE 250.50, AS THE NEW
 FOOTER STEEL IS REQUIRED TO PART OF THE
 GROUNDING ELECTRODE SYSTEM.
  
 15) NOTE: PLEASE SEE RISER INDICATES
 "CURRENT SERVICE", THIS IS TAKEN AS
 EXISTING SERVICE, YET THE PANEL SCHEDULE
 IS NOTED AS BEING THE "PROPOSED" PANEL?
 IS THIS EXISTING OR NEW?
 PLEASE CLARIFY.
  
 16) NOTE: PLEASE SEE RISER ONLY SEEMS TO
 BE SHOWING ONE A/C SYSTEM?
 PLEASE ALSO SEE THE FOLLOWING COMMENTS.
 PLEASE SEE NOTE ON PANEL SCHEDULE
 MENTIONS 1-5KW AND 1-10KW, HOWEVER PANEL
 SCHEDULE SHOWS 10KW UNITS.
 PANEL ALSO SHOWS "4-SPACES"??
 PLEASE CLARIFY THIS. PLEASE SEPARATE
 THESE OF THE "4-SPACES" IS FOR TWO
 SEPARATE A/C AHU'S.
 PLEASE ALSO SEE THAT THE OCP FOR THE
 AHU'S SHALL BE SIZED AT A MIN OF 125%.
 PLEASE SEE AHU'S ARE SHOWN W/ 40A OCP.
 PLEASE SEE 424.3B,240.4,310.16,440.11
 ETC
  
 17) NOTE: PLEASE SEE 220.31B, 220.21 FOR
 MIN LOAD CALCULATIONS FOR SERVICE.
 PLEASE ALSO SEE MIN LOADS FOR A/C SYSTEM
 SHALL BE SHOWN. PLEASE SEE THE LARGER OF
 THE TWO LOADS SHALL BE INDICATED IN
 LOADS CALCS. LOADS SHOWN DO NOT
 CORRELATE WITH EITHER THE NOTE FOR ONE
 5KW AND ONE-10KW OR THE TWO 10KW UNITS
 AS NOTED ON PANEL SCHEDULE.
 PLEASE ADJUST AND REVISE CALCULATIONS.
  
 18) NOTE: PLEASE SEE LOAD CALCULATIONS
 MENTIONS 2-RANGES, YET PLANS DO NOT
 CORRELATE WITH THIS?
 PLEASE SEE PLANS INDICATE ONE RANGE AND
 AN "OVEN"? PLEASE SEE PANEL SCHEDULE
 DOES NOT SHOW OVEN.
 PLEASE VERIFY ALL KW LOADS, OCP AND
 CIRCUITS.
 408.4,240.4,310.16 ETC
  
 19) NOTE: PLEASE SEE
 210.52B1,210.11C1,220.16A FOR MIN 1500VA
 FOR SM APPL CIRCUITS. (PLANS SHOW 1400).
  
 20) NOTE: PLEASE SEE DEDICATED
 DISHWASHER IS SHOWN ON LOAD CALCS, YET
 NOT ON PANEL SCHEDULE.
 PLEASE SEE DISPOSAL(S) ON PANEL
 SCHEDULE, HOWEVER NOT IN LOAD CALCS.?
 PLEASE SEE OTHER WHICH ARE NOT LISTED.
 PLEASE BE SURE TO GO THROUGH ALL
 CIRCUITS ON THE HOUSE PANEL NEW AND
 EXISTING, LIST IN LOAD CALCS, SHOW ON
 PANEL SCHEDULE AND ADJUST LOAD
 CALCULATIONS ACCORDINGLY.
 215.5,220.31B,ETC.
  
 21) NOTE: PLEASE SEE PANEL SCHEDULE
 SHALL INDICATE ALL CONDUCTOR SIZES PER
 310.16,240.4,215.5,408.4 ETC
 FBC 106.1.2, ADMIN SECT
  
 22) NOTE: PLEASE CLARIFY "4-SPACES SHOWN
 FOR THE 2-POLE 60A BREAKER FOR THE POOL
 SUB PANEL??
 106.1.2
  
 23) NOTE: PLEASE SEE RISER SHOWS AN
 "EQUIPMENT GROUNDING CONDUCTOR FROM
 METER TO THE MAIN?? IT IS NOTED THAT
 THIS IS EXISTING, HOWEVER THE #8 SHOULD
 NOT BE LOCATED IN THIS SEGMENT OF THE
 SEC'S. PLEASE SEE 250.6,240.24B, AS THIS
 CREATES "OBJECTIONABLE CURRENT" BY
 PARALLELING THE NEUTRAL.
 PLEASE KNOW, "IF" THIS CONDUCOTOR IS
 INSTALLED , EVEN IF EXISTING, THIS MUST
 BE REMOVED.
 PLEASE BE SURE THIS IS THERE AS NOTED ON
 RISER BEFORE REVISING AND RESUBMITTING
 PLANS.
  
 24) NOTE: PLEASE SHOW THE LOCATION OF
 THE EXISTING SERVICE.
 215.5,240.24B,408.7 ETC
  
 25) NOTE: PLEASE SEE 680.22B1 FOR MIN
 CLEARANCES FOR LIGHTING FIXTURES FROM
 POOL. PLEASE SEE LTS ETC AS SHOWN DO NOT
 MEET THE MIN DISTANCES REQUIRED FOR THE
 NEW ADDITION.
 PLEASE SEE SCONCES SHOWN ARE EVEN CLOSER
 WHICH WILL ALSO NOT BE PERMITTED.
  
 26) NOTE: PLEASE LIST ALL THE REQUIRED
 ARC FAULT PROTECTED CIRCUITS PER 2002
 NEC 210.12B
  
  
 ** PLEASE KNOW DUE TO THE EXTENT OF
 COMMENTS, PLEASE BE SURE TO SEE ONE
 REDLINED SET AS MANY OF THE ABOVE ITEMS
 WERE "REDLINED". THIS IS IN NO WAY ALL
 POSSIBLE LOCATIONS.
  
 **IMPORTANT**
 AFTER ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS AND BEFORE
 RESUBMITTING PLANS. PLEASE BE SURE TO
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. THIS WILL HELP TO AVOID ANY
 DELAYS IN THE PROCESSING OF PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  