| 2006-07-05 00:00:00 | ********* UNSAT *********** |
| | |
| | |
| | ** PLEASE SEE COMMENTS FROM ZONING |
| | REVIEW WHICH WILL AFFECT ELECTRICAL |
| | PLANS AND DESIGN. |
| | |
| | 1) NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52. 2',6'12' RULE ALL WALL SPACES |
| | FOR NEW AREAS AND NEW CONVERTED AREAS |
| | WHICH USED TO BE THE KITCHEN. |
| | |
| | 2) NOTE: PLEASE SEE MISSING EITHER |
| | EXISTING OR NEW DINING RM DEDICATE |
| | CIRCUIT REQUIRED. PLEASE SEE 210.52B1,210.11C1,220.16 |
| | ON ONE OR MORE |
| | OF THE SM APPL CIRCUITS. |
| | ** PLEASE SEE THE DINING ROOM MAY NOT BE |
| | CIRCUITED TO THE GARAGE AS NOTED ON |
| | PANEL SCHEDULE. (THIS WOULD BE OK,ONLY |
| | FOR LIGHTING CIR). |
| | |
| | 3) NOTE: PLEASE SEE MISSING GFI RECEPT |
| | SPACING ALONG MANY AREAS OF THE KITCHEN |
| | COUNTER SPACES. |
| | 210.52C1 |
| | |
| | 4) NOTE: PLEASE SEE MISSING LOCATION OF |
| | NEW AHUFOR ADDITION. PLEASE SHOW |
| | LOCATION AND PLEASE ALSO SEE 440.11 FOR |
| | MISSING DISCONNECTS FOR BOTH THE AHU AND |
| | CU. |
| | |
| | 5) NOTE: PLEASE SEE MISSING GFI RECEPT |
| | FOR CU. |
| | 210.63, 210.8A |
| | |
| | 6) NOTE: PLEASE SEE MISSING NEW OR |
| | EXISTING REAR RECEPT PER 210.52E (GFI |
| | PER 210.8A) |
| | |
| | 7) NOTE: PLEASE SEE MISSING GFI RECEPT |
| | FOR NEW BATH RM OFF THE GARAGE. |
| | 210.52D,210.11C3 |
| | |
| | 8) NOTE: PLEASE CLARIFY NEW OR EXISTING |
| | GARAGE GFI. |
| | 210.52G, 210.8A |
| | |
| | 9) NOTE: PLEASE SEE MISSING REQUIRED |
| | DEDICATED BATH(S) RM CIRCUITS(S). 210.52D,210.11C3. |
| | |
| | 10) NOTE: PLEASE SEE MISSING SMOKE |
| | DETECTORS REQUIRED IN NEW AND EXISTING |
| | DWELLING PER NFPA-72 11.5.1.1,11.8.3 |
| | PLEASE SEE THESE SHALL ALL BE HARDWIRED |
| | INLINE AND ARC FAULT PROTECTED PER |
| | 210.12B |
| | PLEASE SEE SD IN MASTER BEDRM SHALL BE |
| | INSTALLED WITHIN 3' OF THE HIGHEST POINT |
| | OF THE SLOPED CEILING OR 12" OF THE FLAT |
| | CEILING AREA IF A TRAY/FLAT AREA. |
| | |
| | 11) NOTE: PLEASE PROVIDE ALL ROOM AND |
| | AREA DESIGNATIONS ON PLANS. |
| | 106.1.2 FBC ADMIN SECT. |
| | |
| | 12) NOTE: PLEASE SEE MIN CLEARANCES DO |
| | NOT SEEM TO BE MET FOR NEW CLOSET LTS. |
| | PER 410.8 |
| | |
| | 13) NOTE: PLEASE SEE PLANS APPEAR TO |
| | SHOW A "JACUZZI/SPA TUB" YET PANEL |
| | SCHEDULE AND LOAD CALCULATIONS DO NOT |
| | INDICATE EITHER?? |
| | PLEASE ALSO INDICATE THE REQUIRED GFI |
| | PROTECTION. |
| | 680.71, 106.1.2 FBC ADMIN SECT. |
| | |
| | 14) NOTE: PLEASE SEE 250.50, AS THE NEW |
| | FOOTER STEEL IS REQUIRED TO PART OF THE |
| | GROUNDING ELECTRODE SYSTEM. |
| | |
| | 15) NOTE: PLEASE SEE RISER INDICATES |
| | "CURRENT SERVICE", THIS IS TAKEN AS |
| | EXISTING SERVICE, YET THE PANEL SCHEDULE |
| | IS NOTED AS BEING THE "PROPOSED" PANEL? |
| | IS THIS EXISTING OR NEW? |
| | PLEASE CLARIFY. |
| | |
| | 16) NOTE: PLEASE SEE RISER ONLY SEEMS TO |
| | BE SHOWING ONE A/C SYSTEM? |
| | PLEASE ALSO SEE THE FOLLOWING COMMENTS. |
| | PLEASE SEE NOTE ON PANEL SCHEDULE |
| | MENTIONS 1-5KW AND 1-10KW, HOWEVER PANEL |
| | SCHEDULE SHOWS 10KW UNITS. |
| | PANEL ALSO SHOWS "4-SPACES"?? |
| | PLEASE CLARIFY THIS. PLEASE SEPARATE |
| | THESE OF THE "4-SPACES" IS FOR TWO |
| | SEPARATE A/C AHU'S. |
| | PLEASE ALSO SEE THAT THE OCP FOR THE |
| | AHU'S SHALL BE SIZED AT A MIN OF 125%. |
| | PLEASE SEE AHU'S ARE SHOWN W/ 40A OCP. |
| | PLEASE SEE 424.3B,240.4,310.16,440.11 |
| | ETC |
| | |
| | 17) NOTE: PLEASE SEE 220.31B, 220.21 FOR |
| | MIN LOAD CALCULATIONS FOR SERVICE. |
| | PLEASE ALSO SEE MIN LOADS FOR A/C SYSTEM |
| | SHALL BE SHOWN. PLEASE SEE THE LARGER OF |
| | THE TWO LOADS SHALL BE INDICATED IN |
| | LOADS CALCS. LOADS SHOWN DO NOT |
| | CORRELATE WITH EITHER THE NOTE FOR ONE |
| | 5KW AND ONE-10KW OR THE TWO 10KW UNITS |
| | AS NOTED ON PANEL SCHEDULE. |
| | PLEASE ADJUST AND REVISE CALCULATIONS. |
| | |
| | 18) NOTE: PLEASE SEE LOAD CALCULATIONS |
| | MENTIONS 2-RANGES, YET PLANS DO NOT |
| | CORRELATE WITH THIS? |
| | PLEASE SEE PLANS INDICATE ONE RANGE AND |
| | AN "OVEN"? PLEASE SEE PANEL SCHEDULE |
| | DOES NOT SHOW OVEN. |
| | PLEASE VERIFY ALL KW LOADS, OCP AND |
| | CIRCUITS. |
| | 408.4,240.4,310.16 ETC |
| | |
| | 19) NOTE: PLEASE SEE |
| | 210.52B1,210.11C1,220.16A FOR MIN 1500VA |
| | FOR SM APPL CIRCUITS. (PLANS SHOW 1400). |
| | |
| | 20) NOTE: PLEASE SEE DEDICATED |
| | DISHWASHER IS SHOWN ON LOAD CALCS, YET |
| | NOT ON PANEL SCHEDULE. |
| | PLEASE SEE DISPOSAL(S) ON PANEL |
| | SCHEDULE, HOWEVER NOT IN LOAD CALCS.? |
| | PLEASE SEE OTHER WHICH ARE NOT LISTED. |
| | PLEASE BE SURE TO GO THROUGH ALL |
| | CIRCUITS ON THE HOUSE PANEL NEW AND |
| | EXISTING, LIST IN LOAD CALCS, SHOW ON |
| | PANEL SCHEDULE AND ADJUST LOAD |
| | CALCULATIONS ACCORDINGLY. |
| | 215.5,220.31B,ETC. |
| | |
| | 21) NOTE: PLEASE SEE PANEL SCHEDULE |
| | SHALL INDICATE ALL CONDUCTOR SIZES PER |
| | 310.16,240.4,215.5,408.4 ETC |
| | FBC 106.1.2, ADMIN SECT |
| | |
| | 22) NOTE: PLEASE CLARIFY "4-SPACES SHOWN |
| | FOR THE 2-POLE 60A BREAKER FOR THE POOL |
| | SUB PANEL?? |
| | 106.1.2 |
| | |
| | 23) NOTE: PLEASE SEE RISER SHOWS AN |
| | "EQUIPMENT GROUNDING CONDUCTOR FROM |
| | METER TO THE MAIN?? IT IS NOTED THAT |
| | THIS IS EXISTING, HOWEVER THE #8 SHOULD |
| | NOT BE LOCATED IN THIS SEGMENT OF THE |
| | SEC'S. PLEASE SEE 250.6,240.24B, AS THIS |
| | CREATES "OBJECTIONABLE CURRENT" BY |
| | PARALLELING THE NEUTRAL. |
| | PLEASE KNOW, "IF" THIS CONDUCOTOR IS |
| | INSTALLED , EVEN IF EXISTING, THIS MUST |
| | BE REMOVED. |
| | PLEASE BE SURE THIS IS THERE AS NOTED ON |
| | RISER BEFORE REVISING AND RESUBMITTING |
| | PLANS. |
| | |
| | 24) NOTE: PLEASE SHOW THE LOCATION OF |
| | THE EXISTING SERVICE. |
| | 215.5,240.24B,408.7 ETC |
| | |
| | 25) NOTE: PLEASE SEE 680.22B1 FOR MIN |
| | CLEARANCES FOR LIGHTING FIXTURES FROM |
| | POOL. PLEASE SEE LTS ETC AS SHOWN DO NOT |
| | MEET THE MIN DISTANCES REQUIRED FOR THE |
| | NEW ADDITION. |
| | PLEASE SEE SCONCES SHOWN ARE EVEN CLOSER |
| | WHICH WILL ALSO NOT BE PERMITTED. |
| | |
| | 26) NOTE: PLEASE LIST ALL THE REQUIRED |
| | ARC FAULT PROTECTED CIRCUITS PER 2002 |
| | NEC 210.12B |
| | |
| | |
| | ** PLEASE KNOW DUE TO THE EXTENT OF |
| | COMMENTS, PLEASE BE SURE TO SEE ONE |
| | REDLINED SET AS MANY OF THE ABOVE ITEMS |
| | WERE "REDLINED". THIS IS IN NO WAY ALL |
| | POSSIBLE LOCATIONS. |
| | |
| | **IMPORTANT** |
| | AFTER ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS AND BEFORE |
| | RESUBMITTING PLANS. PLEASE BE SURE TO |
| | COMPLETELY REMOVE ALL OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT NEW SHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. THIS WILL HELP TO AVOID ANY |
| | DELAYS IN THE PROCESSING OF PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |