| Plan Review Notes For Permit 06061237 |
| Permit Number |
06061237 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-08-06 00:00:00 | *** UNSAT2ND REVIEW ****** | | | | | | ** PLEASE SEE SOME NOTE ARE NEW DUE TO | | | RISER BEING REVISED. | | | | | | 1) NOTE: PLEASE CLARIFY AND COMPLETE | | | RISER. | | | PLEASE SEE RISER SHOWS A 800A SERVICE, | | | HOWEVER SEC'S ARE ONLY SHOWN FOR A 400A | | | SERVICE. PREVIOUS RISER SUBMITTED 800A'S | | | 240.4,310.16 | | | | | | 2) NOTE: PLEASE SEE GROUNDING ELECTRODE | | | IS SHOWN ON THE EXISTING RISER AS #4 | | | WHICH IS WAY TOO SMALL PER TABLE IN | | | 250.66. PLEASE SEE "NEW" RISER DOES NOT | | | SHOW ANY GE SYSTEM. | | | 250.66 | | | | | | 3) NOTE: PLEASE SEE "EQUIPMENT GROUNDING | | | CONDUCTORS" ARE BEING SHOWN BEFORE THE | | | FIRST MEANS OF DISCONNECTS. | | | 250.6,250.24B | | | | | | 4) NOTE: PLEASE PROVIDE CONDUCTORS FROM | | | J-BOX TO THE MTS. | | | | | | 5) NOTE: PLEASE BE SURE THE PERSON | | | RESPONSIBLE FOR PLANSSHALL CONTAIN THE | | | PRINTED NAME AND SIGNATURE. | | | FBC 106.1.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|