Plan Review Notes
Plan Review Notes For Permit 06061237
Permit Number 06061237
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-06 00:00:00*** UNSAT2ND REVIEW ******
  
 ** PLEASE SEE SOME NOTE ARE NEW DUE TO
 RISER BEING REVISED.
  
 1) NOTE: PLEASE CLARIFY AND COMPLETE
 RISER.
 PLEASE SEE RISER SHOWS A 800A SERVICE,
 HOWEVER SEC'S ARE ONLY SHOWN FOR A 400A
 SERVICE. PREVIOUS RISER SUBMITTED 800A'S
 240.4,310.16
  
 2) NOTE: PLEASE SEE GROUNDING ELECTRODE
 IS SHOWN ON THE EXISTING RISER AS #4
 WHICH IS WAY TOO SMALL PER TABLE IN
 250.66. PLEASE SEE "NEW" RISER DOES NOT
 SHOW ANY GE SYSTEM.
 250.66
  
 3) NOTE: PLEASE SEE "EQUIPMENT GROUNDING
 CONDUCTORS" ARE BEING SHOWN BEFORE THE
 FIRST MEANS OF DISCONNECTS.
 250.6,250.24B
  
 4) NOTE: PLEASE PROVIDE CONDUCTORS FROM
 J-BOX TO THE MTS.
  
 5) NOTE: PLEASE BE SURE THE PERSON
 RESPONSIBLE FOR PLANSSHALL CONTAIN THE
 PRINTED NAME AND SIGNATURE.
 FBC 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]