| Plan Review Notes For Permit 06061237 |
| Permit Number |
06061237 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-27 00:00:00 | ******** UNSAT *********** | | | | | | 1) NOTE: PLEASE CLARIFY AND COMPLETE | | | RISER. | | | PLEASE SEE NEW J-BOX APPEARS TO BE | | | LOCATED IN GROUND, YET RISER SHOWS "EMT" | | | AS THE CONDUIT. | | | PLEASE PROVIDE PLANS WITH MIN 1/8" SCALE | | | AND PLEASE DRAW RISER AS AN ELEVATION. | | | | | | 2) NOTE: PLEASE CLARIFY OF THE 800A MAIN | | | FEED STHE GUTTER? | | | PLEASE COMPLETE ALL NEW CONDUCTORS BEING | | | INSTALLED IN GUTTER AND NEW MAN MTS'S. | | | 215.5,240.4,310.16 | | | PLEASE SEE BOTH MTS'S NEED SHOW THE OCP | | | IN EACH AS THE ONLY FEED COMEING FROM | | | GEN CONNECTION IS ONLY RATED AT 200A'S?? | | | | | | | | | 3) NOTE: PLEASE PROVIDE THE MANUFACTURES | | | SPECS/CUT SHEETS FOR BOTH MTS DEVICES. | | | NEED TO VERIFY THE REQUIREMENT FOR | | | 230.70,230.72,230.76,230.79 ETC. | | | 110.3, 215.5, | | | FBC 106.1.2 ADMIN SECT. | | | | | | | | | 4) NOTE: PLEASE BE SURE THE PERSON | | | RESPONSIBLE FOR PLANS/DESIGN PRINTS AND | | | SIGNS PLANS/DESIGN. | | | FBC ADMIN SECT 106.1.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|