2006-06-27 00:00:00******** UNSAT ***********
  
 1) NOTE: PLEASE CLARIFY AND COMPLETE
 RISER.
 PLEASE SEE NEW J-BOX APPEARS TO BE
 LOCATED IN GROUND, YET RISER SHOWS "EMT"
 AS THE CONDUIT.
 PLEASE PROVIDE PLANS WITH MIN 1/8" SCALE
 AND PLEASE DRAW RISER AS AN ELEVATION.
  
 2) NOTE: PLEASE CLARIFY OF THE 800A MAIN
 FEED STHE GUTTER?
 PLEASE COMPLETE ALL NEW CONDUCTORS BEING
 INSTALLED IN GUTTER AND NEW MAN MTS'S.
 215.5,240.4,310.16
 PLEASE SEE BOTH MTS'S NEED SHOW THE OCP
 IN EACH AS THE ONLY FEED COMEING FROM
 GEN CONNECTION IS ONLY RATED AT 200A'S??
  
  
 3) NOTE: PLEASE PROVIDE THE MANUFACTURES
 SPECS/CUT SHEETS FOR BOTH MTS DEVICES.
 NEED TO VERIFY THE REQUIREMENT FOR
 230.70,230.72,230.76,230.79 ETC.
 110.3, 215.5,
 FBC 106.1.2 ADMIN SECT.
  
  
 4) NOTE: PLEASE BE SURE THE PERSON
 RESPONSIBLE FOR PLANS/DESIGN PRINTS AND
 SIGNS PLANS/DESIGN.
 FBC ADMIN SECT 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  