Plan Review Notes
Plan Review Notes For Permit 06061209
Permit Number 06061209
Review Stop E
Sequence Number 4
Notes
Date Text
2006-11-09 15:20:11**** UNSAT ****
  
 *** PLEASE SEE COMMENTS BASED ON NEW REVISED RISER
 SUBMITTED.
  
 1) NOTE:PLEASE SEE RISER NOW SHOWS A MAIN BREAKER
 PANEL WITH A 125A MAIN, WITH #6'S ON RISER???
 PLEASE ALSO SEE RISER SHOWS A 60A MAIN??
 PLEASE CORRELATE.
  
 2) NOTE: PLEASE SEE AN "EQUIPMENT GROUNDIGN CONDUCTOR"
 IS ALSO BEING SHOWN FROM THE METER TO THE FIRST MEANS
 OF DISCONNECT WHICH IS NOT PERMITTED.
 250.6, 250.24.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  