| Plan Review Notes For Permit 06061209 |
| Permit Number |
06061209 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-10-17 07:46:04 | *** UNSAT 3RD REVIEW ***** | | | | | | *** PLEASE SEE NOTES FROM PREVIOUS REVIEW. | | | *** PLEASE SUBMIT AND COMPLETE A RISER DIAGRAM FOR NEW | | | SERVICE MEETING 2002 NEC FOR CODE COMPLIANCE. | | | | | | | | | 1) NOTE: PLANS STILL DO NOT CONTIAN THE PRINTED NAME | | | AND SIGNATURE OF THE PERSON RESPONSIBLE FOR PLANS. | | | FBC ADMIN SECT 106.1.2 | | | | | | 2) NOTE: GROUNDING ELECTRODE SYSTEM NOT COMPLETE. | | | 250.50, 250.56 | | | | | | 3) NOTE: RISER SHOWS 30A BREAKER TO 20A GFI. | | | 240.4, 310.16, 210.21 | | | | | | 4) NOTE: PLEASE SEE RISER SHOWS2-"PO" BREAKER FROM | | | FPL???? | | | | | | 5) NOTE: PLEASE INDICATE MAIN. 230.70, 230.71. | | | | | | 6) NOTE: RISER NOT COMPLETE WITH CONDUCTORS. HOW MANY ? | | | TO EACH ? EQUIPMENT GROUNDING? ETC ETC | | | 240.4,310.16,250.110, 250.24B. | | | | | | 7) NOTE: HOW AND WHAT IS THIS UNIT /RISER BEING BUILT | | | ON. | | | | | | | | | ** PLEASE KNOW, ONE SET OF EACH OF THE PLANS HAVE BEEN | | | RETAINED. | | | | | | | | | PLEASE SUBMIT FOR REVIEW. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|