2006-08-02 00:00:00******** UNSAT *******
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW
 NOTES AND COMPLETE RISER DIAGRAM.
 PLEASE SEE RISER SHOWS #10-12AWG?? FOR
 BOTH THE FEED TO PANEL AND THE FEED TO
 EXISTING IRRIGATION SYSTEM.
 PELASE SEE PANEL IS SHOWN AS 2X30A
 BREAKER PANEL?? THIS IS UNCLEAR AT THIS
 TIME. IS THIS A 2-POLE 30A BREAKER FOR
 MAIN? OR DOES THIS CONTAIN 2-30A
 BREAKERS/ IF SO WHAT DO THESE TWEO
 BREAKERS FEED. THE DUPLEX RECEPTS DO NOT
 APPEAR TO BE 30A?
 PLEASE ALSO SEE NOTE AT LOWER LEFT HAND
 SIDE OF PANEL SHOWS 2-POLE FUSE PANEL?
 PLEASE VERIFY IF PANEL IS GOING TO BE A
 FUSE PANEL OR BREAKER PANEL.
 PLEASE SEE 240.4.310.16,215.5, ETC
  
 2) NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE SYSTEM.
 250.50,250.66
  
 3) NOTE: PLEASE BE SURE THE PLANS/DESIGN
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS.
 FBC 106.1.21
  
 ** PLEASE SEE COMMENTS ALSO ATTACHED
 FROM PREVIOUS REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  