Plan Review Notes
Plan Review Notes For Permit 06061209
Permit Number 06061209
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-27 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE COMPLETE ELECTRICAL
 RISER DIAGRAM SHOWING ALL MIN CONDUCTOR
 SIZES, FOR SEC'S , FEEDERS, BRANCH
 CIRCUIT(S). PLEASE INDICATE OCP FOR EACH
 OF THE ABOVE.
 PLEASE COMPLETE RISER DIAGRAM.
 PLEASE SUBMIT AIC RATINGS OF NEW MAIN.
 PLEASE SEE RECEPT IS BEING SHOWN BEING
 FED THROUGH METER WHICH IS NOT
 PERMITTED.
  
 215.5,310.16,240.4,230.7,250.50 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  